Plan Review Notes
Plan Review Notes For Permit 09060212
Permit Number 09060212
Review Stop B
Sequence Number 2
Notes
Date Text
2009-06-12 10:18:51RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW 2ND
 CHECKLIST.
 REVIEW UNDER 2007 FL. RESIDENTIAL CODE W/ 2009
 REVISIONS.
  
 1- CLEARLY MARK ON FLAT ROOF NOA 07-0730.03 SUBMITTED
 WHICH BASE SHEET FASTENING OPTION IS GOING TO BE
 INSTALLED TO VERIFY COMPLIANCE WITH DESIGN PRESSURES OF
 SEC. R301. (REPEAT COMMENT. NOA SUBMITTED DOESN'T
 IDENTIFY FASTENING OPTION).
  
 2- PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL
 LIMITATION #7. (REPEAT COMMENT. CALCULATIONS WERE NOT
 SUBMITTED).
  
 ***NOTE: I EXPLAINED TO MARK ON 6/10/09 THAT RAS 117
 CALCULATIONS ARE ALWAYS REQUIRED. ONLY WHEN NOA
 REQUIRES RAS 117 CALCULATIONS TO BE SIGNED AND SEALED,
 THEN THEY NEED TO BE SIGNED AND SEALED. OTHERWISE,
 CALCULATIONS OR PRESCRIPTIVE METHOD ON CONTRACTOR'S
 LETTERHEAD ARE ACCEPTABLE. I DIDN'T TELL MARK THAT HE
 HAS TO USE A TAMKO PRODUCT APPROVAL AS COMMENTED ON THE
 RE-SUBMITTAL FORM. CONTRACTOR IS FREE TO SELECT ANY
 PRODUCT HE/SHE WANTS TO USE. WE DON'T REQUEST ANY
 SPECIFIC PRODUCT APPROVAL. WE ONLY ENFORCE WHAT THE
 PRODUCT APPROVAL REQUIRES.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712.