2009-06-12 10:18:51 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW 2ND | | CHECKLIST. | | REVIEW UNDER 2007 FL. RESIDENTIAL CODE W/ 2009 | | REVISIONS. | | | | 1- CLEARLY MARK ON FLAT ROOF NOA 07-0730.03 SUBMITTED | | WHICH BASE SHEET FASTENING OPTION IS GOING TO BE | | INSTALLED TO VERIFY COMPLIANCE WITH DESIGN PRESSURES OF | | SEC. R301. (REPEAT COMMENT. NOA SUBMITTED DOESN'T | | IDENTIFY FASTENING OPTION). | | | | 2- PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT | | PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL | | LIMITATION #7. (REPEAT COMMENT. CALCULATIONS WERE NOT | | SUBMITTED). | | | | ***NOTE: I EXPLAINED TO MARK ON 6/10/09 THAT RAS 117 | | CALCULATIONS ARE ALWAYS REQUIRED. ONLY WHEN NOA | | REQUIRES RAS 117 CALCULATIONS TO BE SIGNED AND SEALED, | | THEN THEY NEED TO BE SIGNED AND SEALED. OTHERWISE, | | CALCULATIONS OR PRESCRIPTIVE METHOD ON CONTRACTOR'S | | LETTERHEAD ARE ACCEPTABLE. I DIDN'T TELL MARK THAT HE | | HAS TO USE A TAMKO PRODUCT APPROVAL AS COMMENTED ON THE | | RE-SUBMITTAL FORM. CONTRACTOR IS FREE TO SELECT ANY | | PRODUCT HE/SHE WANTS TO USE. WE DON'T REQUEST ANY | | SPECIFIC PRODUCT APPROVAL. WE ONLY ENFORCE WHAT THE | | PRODUCT APPROVAL REQUIRES. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712. |
|