2009-06-10 10:01:39RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST.
 REVIEW UNDER 2007 FLORIDA RESIDENTIAL CODE WITH 2009
 REVISIONS.
  
 1- CLEARLY MARK ON NOA 09-0224.01 SUBMITTED WHICH BASE
 SHEET FASTENING OPTION ON SELECTED APPROVED ASSEMBLY IS
 GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 CALCULATED DESIGN PRESSURES OF SEC. R301 OF 2007
 FLORIDA RESIDENTIAL CODE.
  
 2- PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL
 LIMITATION #7. SEE NOA SUBMITTED.
  
 3- RAS 117 CALCULATIONS NEED TO BE SIGNED AND SEALED AS
 REQUIRED BY GENERAL LIMITATION #7 ON SHEET 31 OF NOA
 09-0224.01 SUBMITTED.
 ***NOTE: DESIGN PROFESSIONAL DOING THE CALCULATIONS TO
 TAKE INTO CONSIDERATION THAT ACCORDING TO THE 2009
 REVISIONS TO SEC. R301 OF 2007 FLORIDA RESIDENTIAL CODE
 THIS BUILDING IS LOCATED ON EXPOSURE "C".
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712