2009-09-03 10:57:14 | **PROVISO** | | OUTSIDE AIR CALCULATIONS SHOW VENTILATION RATE IN | | EXCESS OF THAT REQUIRED BY FBC-M TABLE 403.3. REVISE | | CALCULATIONS TO SHOW A VENTILATION RATE BASED ON THE | | OCCUPANT LOADS SHOWN ON TABLE 403.3. IF VENTILATION | | RATE EXCEEDS 300 CFM, A MOTORIZED DAMPER IS REQUIRED ON | | THE OUTSIDE AIR INTAKE IN ACCORDANCE WITH FBC-B | | 13-409.AB.3.3. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|