2009-09-09 11:03:04 | |
| ** DENIED 2ND REVIEW ** |
| |
| ** PLEASE SEE SEVERAL COMMENTS FROM PREVIOUS REVIEW ARE |
| STILL IN NEED OF ADDRESSING. |
| |
| 1) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE |
| CALCULATIONS IN COMPLIANCE WITH THE * MINIMUM* FOR THE |
| FBC 13-415.AB.5. A NEW FORM B WAS SUBMITTED HOWEVER |
| WHEN USING A FORM B FOR MINIMUM PRESCRIPTIVE YOU WOULD |
| USE ONE FOR EACH *SPACE TYPE*. NOT ONE FORM WHEN YOU |
| HAVE MULTIPLE SPACES PER TABLE 13-415.B.1. |
| SEE 13-415.AB.2.2 FOR EXTERIOR, NOTHING SHOWN. ( SIGN |
| CIRCUIT IS NOT INCLUDED, EXEMPT). |
| THE SPACE TYPE AS LISTED ON THE FORM B SUBMITTED STATES |
| * FLUORESCENT*. HOW CAN THE SPACE TYPE BE FLUORESCENT? |
| THIS WOULD BE LISTED UNDER FIXTURE TYPE FOR EACH SPACE. |
| PART OF THE LIGHTING SPACE BY SPACE IS BEING SHOWN ON |
| PLANS HOWEVER DUE TO THE INCONSISTENCIES ON THE FIXTURE |
| LEGEND. CODE COMPLIANCE IS NOT SHOWN. IN FACT BASED ON |
| SOME OF THE FIXTURE INFORMATION THE MAXIMUM LIGHTING |
| ALLOWANCE LEVELS ARE EXCEEDED. |
| SOME EXAMPLES WILL BE GIVEN. |
| |
| FOR EXAMPLE: FIXTURE TYPE *A* IS SHOWN AS 3-32W WITH AN |
| OVER ALL AT 107WATTS DUE TO THE BALLAST POWER FACTOR. |
| HOWEVER PLEASE SEE *LAMP TYPE LISTING ON THE FIXTURE |
| TABLE. THIS CLEARLY STATES THERE WILL BE (4)-F32 W |
| BULBS. |
| |
| FOR EXAMPLE: THE SAME IS NOTED FOR FIXTURE B AS NOTED |
| FOR FIXTURE *A*. THE LAMP LEGEND INDICATES (4) F32W |
| BULBS. |
| |
| FOR EXAMPLE: PLEASE SEE FIXTURE TYPE *D* WHICH STATES |
| IT IS AN INCANDESCENT FIXTURE YET ALSO STATES IT IS A |
| RECESSED FLUORESCENT DOWN LIGHT. |
| |
| ** ON THE PREVIOUS REVIEW ON THIS NOTE THIS REVIEWER |
| STATED TO CALL TO GO OVER THIS COMMENT IF THERE WERE |
| ANY QUESTIONS. TO DATE THIS DID NOT OCCUR. THE COMMENT |
| REMAINS TO CALL IF THERE ARE QUESTIONS. |
| |
| |
| 2) NOTE: PLEASE SEE COMMENT #1 ABOVE. THERE ARE TWO |
| COPIES OF *FORM B* SUBMITTED. BOTH ARE SIGNED AND DATED |
| BY THE ARCHITECT WITH APPROPRIATE LICENSE NUMBER |
| HOWEVER THERE IS NO RAISED SEAL. FS 481.221 |
| ** THIS IS BEING NOTED IN CASE DESIGNER DOES SUBMIT NEW |
| FORM B FOR LIGHTING COMPLIANCE FOR EACH SPACE TYPE. |
| AS STATED, CALL TO GO OVER HOW COMPLIANCE CAN BE SHOWN |
| FOR PRESCRIPTIVE WITHOUT HAVING TO FILL OUT A FORM FOR |
| EACH SPACE. |
| |
| 3) NOTE: PLEASE SEE COMMENT FROM PREVIOUS REVIEW WHICH |
| REQUIRED LIGHTING CONTROLS IN SPECIFIC ROOMS STATED IN |
| 13-415.AB.1.2 TO MEET THE FBC. AUTOMATED LIGHTING |
| CONTROLS WERE ADDED TO ALL OTHER ROOMS EXCEPT THE TWO |
| ROOMS AS NOTED IN THE PREVIOUS REVIEW. THE ONLY TWO |
| ROOMS IN THIS BUILDING WHICH IS LESS THAN 5K SQ FT THAT |
| REQUIRES AUTOMATED LIGHTING CONTROLS IS THE |
| KITCHEN/BREAK ROOM AND THE CONFERENCE ROOM. |
| |
| ** AS A SIDE NOTE: EVEN THOUGH AUTOMATED LIGHTING |
| CONTROLS ARE NOT REQUIRED IN THE OTHER ROOMS, THEY MAY |
| CERTAINLY BE INSTALLED AS SHOWN ON PLANS. |
| |
| 4) NOTE: PLEASE SEE PREVIOUS NOTE WITH RESPECT TO |
| EXTERIOR LIGHTING CONTROLS. IT WAS NOTED THAT THERE |
| WERE EXTERIOR LIGHTS ON SINGLE POLE SWITCHES WHICH WAS |
| NOT PERMITTED AS SHOWN. THE PLANS NOW HAVE A NOTE WHICH |
| STATES ALL EXTERIOR LIGHTS TO BE ON A TIME CLOCK. |
| HOWEVER THE SINGLE POLE SWITCH IS ALSO STILL SHOWN?? |
| PLEASE KNOW THAT A STANDARD TIME CLOCK DOES NOT MEET |
| ONE OF THE TWO ACCEPTABLE METHODS PER 13-415.AB.1.4. IF |
| THIS IS GOING TO BE A TIME CLOCK THEN IT MUST BE |
| *ASTRONOMICAL TYPE* WITH A MINIMUM OF 10HRS BATTERY |
| BACK UP FOR PROGRAMMING. |
| |
| 5) NOTE: PLEASE SEE PREVIOUS NOTE WITH RESPECT TO WATER |
| HEATER LOADS ON STORAGE TYPE OF WATER HEATERS WHICH ARE |
| REQUIRED TO BE SHOWN AND FIGURED AT 125%. SEE 422.13. |
| THIS TYPE OF LOAD UNDER THE CHANGE IN THE 2005 NEC IS |
| NOW CONSIDERED A CONTINUOUS LOAD. ALL CONTINUOUS LOADS |
| ARE REQUIRED TO BE SHOWN AT 125%. |
| PLEASE SEE THE FOLLOWING TEXT WHICH IS TAKEN DIRECTLY |
| FROM THE 2005 NEC HANDBOOK. *** IF THERE ARE QUESTIONS, |
| PLEASE CALL. |
| ** PLEASE SEE LAST SENTENCE IN NOTES** |
| |
| **THE REVISION TO 422.13 SPECIFICALLY IDENTIFIES AN |
| ELECTRIC WATER HEATER WITH A STORAGE CAPACITY OF 120 |
| GAL OR LESS AS A CONTINUOUS LOAD. THIS REVISION |
| REQUIRES THE BRANCH CIRCUIT OVERCURRENT DEVICE AND |
| CONDUCTORS TO BE SIZED BASED ON 125 PERCENT OF THE |
| WATER HEATER NAMEPLATE RATING UNLESS THE OVERCURRENT |
| DEVICE AND THE ASSEMBLY IT IS INSTALLED IN ARE LISTED |
| TO BE USED AT 100 PERCENT OF ITS CONTINUOUS CURRENT |
| RATING. IN ADDITION, FEEDERS AND SERVICES THAT SUPPLY |
| WATER HEATER BRANCH CIRCUITS ARE ALSO IMPACTED BY THE |
| FACT THAT THIS TYPE OF EQUIPMENT IS CONSIDERED TO BE A |
| CONTINUOUS LOAD.** |
| |
| 6) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO |
| MINIMUM LOAD CALCULATIONS REQUIRED TO BE SHOWN FOR A |
| COMMERCIAL. |
| THE PREVIOUS CALCULATIONS THAT WERE SUBMITTED WERE |
| BASED ON RESIDENTIAL USE. THE CALCULATIONS SUBMITTED DO |
| NOT MEET NEC. SEE |
| 220.12,220.14,220.42,220.44,220.56,220.60, 215.3 AND |
| 230.42. THERE ARE OTHER SECTIONS IN 220. |
| |
| FOR EXAMPLE: |
| THE NEW CALCULATIONS INDICATE RECEPTACLES AT A TOTAL OF |
| (4) AND A TOTAL OF 7500VA. THERE ARE MORE THAN 4 |
| RECEPTACLES. |
| |
| FOR EXAMPLE; THE TOTAL LIGHTING LOAD IS SHOWN AT |
| 1014VA. HOW IS THIS POSSIBLE WHEN THE LIGHTING LOAD |
| SHOWN FOR THE INTERIOR LIGHTING ALONE ON SPACE BY SPACE |
| IS 1917VA. ( WHICH MAY OR MAY NOT BE ACCURATE BASED ON |
| FIXTURE LEGEND). |
| |
| ** PLEASE SEE NOTE ABOVE WITH RESPECT TO LOAD |
| CALCULATIONS. WHEN KNOWN LIGHTING LOAD EXCEED THE NEC |
| MINIMUM WATTS PER SQUARE FOOT, THEN THE HIGHER MUST BE |
| USED. |
| ** SEE NOTES ABOVE WITH RESPECT TO WATER HEATER LOAD. |
| |
| 7) NOTE: NEW COMMENT: THE FRONT LOCATION STATES THE * |
| EXIT SIGN TO BE ON TIME CLOCK*. PLEASE SEE NFPA-70 |
| 700.12F AND NFPA-101 7.8,7.9, THE EXIT SIGN MAY NOT BE |
| ON A TIME CLOCK. |
| ** THIS MAY BE SOME SORT OF MISPRINT??? |
| |
| 8) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| REPEAT COMMENTS. THIS IS ONLY A NOTICE. |
| |
| |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |