Plan Review Notes For Permit 09060210 |
Permit Number |
09060210 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-07-01 14:04:54 | DENIED | | REFERENCE: | | FBC-2007 PLUMBING | | | | 1. SHT A-2 SANITARY RISER DIAGRAM. THE SINK SHALL NOT | | DISCHARGE INTO THE HORIZONTAL WET VENT OF THE TOILET | | ROOM FIXTURES. SECTION 909.1. | | | | 2. SHT A-2 WATER RISER DIAGRAM. AIR CHAMBERS ARE NOT | | APPROVED. PDI-2H 201. PLEASE DELETE FROM RISER DIAGRAM. | | IF WATER HAMMER ARRESTORS ARE INSTALLED, (SECTION | | 604.9), THEN THEY SHALL BE INSTALLED NEAR THE FIXTURES, | | IN AN "EFFECTIVE RANGE" NOT IN THE CEILING. | | | | 3. THE WATER HEATER SHALL BE PROVIDED WITH THERMAL | | EXPANSION CONTROL. SECTION 607.13.2. PLEASE INDICATE | | METHOD. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | ONE SET OF THEM LOOSELY ON TOP OF THE | | COLLATED PLANS TO BE REVIEWED. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | |
|