2009-07-13 14:59:44REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. THERE DO NOT APPEAR TO BE ANY PROVISIONS FOR
 VENTILATION ON PLANS. THE MINIMUM VENTILATION RATE OF
 OUTDOOR AIR SHALL BE DETERMINED IN ACCORDANCE WITH
 FBC-M SECTION 403.3. PROVIDE VENTILATION CALCULATIONS
 TO DETERMINE THE REQUIRED RATE OF VENTILATION FOR EACH
 SPACE IN ACCORDANCE WITH FBC-M TABLE 403.3. SHOW MEQANS
 AND LOCATION OF VENTILATION AIR INTAKE IN ACCORDANCE
 WITH FBC-M 401.4.
  
 2. PAGE A2 SHOWS AN EXHAUST FAN ON THE PLANS BUT NO
 INFORMATION IS PROVIDED REGARDING THE FAN. PROVIDE FAN
 DATA SHOWING THE EXHAUST RATE IN ACCORDANCE WITH FBC-M
 TABLE 403.3. ALSO, SHOW THE MEANS AND LOCATION OF
 EXHAUST DUCT DISSCHHARGE IINCORDANCE WITH FBC-M 401.4
 AND FBC-M 501.2.
  
 3. A RETURN AIR TRANSFER DUCT IS SHOWN FOR THE
 CONFERENCE ROOM. THE TRANSFER DUCT IS NOT SIZED IN
 ACCORDANCE WITH THE EXCEPTIONS UNDER FBC-M 601.4. SIZE
 THIS RETURN TRANSFER DUCT IN ACCORDANCE WITH THE
 EXCEPTIONS OR A FIELD TEST WILL BE REQUIRED AT TIME OF
 FINAL INSPECTION TO DETERMINE THE ACTUAL PRESSURE
 DIFFERENTIAL ACROSS THE CLOSED DOOR.
  
 4. EQUIPMENT SCHEDULE CALLS FOR AHU TO PROVED 2000 CFM
 OF SUPPLY WHILE FLOOR PLAN ONLY CALLS FOR 1540 CFM.
 WHICH IS CORRECT? PLEASE COORDINATE FLOOR PLAN AND
 EQUIPMENT SCHEDULE ENSURING EQUIPMENT IS PROPERLY SIZED
 FOR THE COOLING LOADS IN ACCORDANCE WITH FBC-M 312.1.
 NOTE: THE MODEL NUMBERS LISTED ON THE SCHEDULE INDICATE
 A 4 TON SYSTEM. IF A 5 TON SYSTEM IS INSTALLED, PROVIDE
 DUCT SMOKE DETECTOR ON SUPPLY SIDE IN ACCORDANCE WITH
 FBC-M 606.2.1.
  
 5. CONDENSING UNIT STAND INFORMATION ON PLANS IS
 OUT-DATED AND PARTIALLY ILLEGIBLE. PLEASE SUBMIT AN
 ACTUAL CURRENT PRODUCT APPROVAL OR THE PROPOSED STAND,
 APPROVED IN WRITING BY THE DESIGNER OF RECORD IN
 ACCORDANCE WITH FBC-B 106.3.3.
  
 6. ENERGY CODE COMPLIANCE FORM SUBMITTED IS OUT OF
 DATE. THE CORRECT FORM IS 400B-08 AS OF MARCH 1, 2009.
  