2009-07-13 14:59:44 | REVIEW #: 1ST |
| ACTION: DENIED |
| |
| FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS |
| FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| |
| 1. THERE DO NOT APPEAR TO BE ANY PROVISIONS FOR |
| VENTILATION ON PLANS. THE MINIMUM VENTILATION RATE OF |
| OUTDOOR AIR SHALL BE DETERMINED IN ACCORDANCE WITH |
| FBC-M SECTION 403.3. PROVIDE VENTILATION CALCULATIONS |
| TO DETERMINE THE REQUIRED RATE OF VENTILATION FOR EACH |
| SPACE IN ACCORDANCE WITH FBC-M TABLE 403.3. SHOW MEQANS |
| AND LOCATION OF VENTILATION AIR INTAKE IN ACCORDANCE |
| WITH FBC-M 401.4. |
| |
| 2. PAGE A2 SHOWS AN EXHAUST FAN ON THE PLANS BUT NO |
| INFORMATION IS PROVIDED REGARDING THE FAN. PROVIDE FAN |
| DATA SHOWING THE EXHAUST RATE IN ACCORDANCE WITH FBC-M |
| TABLE 403.3. ALSO, SHOW THE MEANS AND LOCATION OF |
| EXHAUST DUCT DISSCHHARGE IINCORDANCE WITH FBC-M 401.4 |
| AND FBC-M 501.2. |
| |
| 3. A RETURN AIR TRANSFER DUCT IS SHOWN FOR THE |
| CONFERENCE ROOM. THE TRANSFER DUCT IS NOT SIZED IN |
| ACCORDANCE WITH THE EXCEPTIONS UNDER FBC-M 601.4. SIZE |
| THIS RETURN TRANSFER DUCT IN ACCORDANCE WITH THE |
| EXCEPTIONS OR A FIELD TEST WILL BE REQUIRED AT TIME OF |
| FINAL INSPECTION TO DETERMINE THE ACTUAL PRESSURE |
| DIFFERENTIAL ACROSS THE CLOSED DOOR. |
| |
| 4. EQUIPMENT SCHEDULE CALLS FOR AHU TO PROVED 2000 CFM |
| OF SUPPLY WHILE FLOOR PLAN ONLY CALLS FOR 1540 CFM. |
| WHICH IS CORRECT? PLEASE COORDINATE FLOOR PLAN AND |
| EQUIPMENT SCHEDULE ENSURING EQUIPMENT IS PROPERLY SIZED |
| FOR THE COOLING LOADS IN ACCORDANCE WITH FBC-M 312.1. |
| NOTE: THE MODEL NUMBERS LISTED ON THE SCHEDULE INDICATE |
| A 4 TON SYSTEM. IF A 5 TON SYSTEM IS INSTALLED, PROVIDE |
| DUCT SMOKE DETECTOR ON SUPPLY SIDE IN ACCORDANCE WITH |
| FBC-M 606.2.1. |
| |
| 5. CONDENSING UNIT STAND INFORMATION ON PLANS IS |
| OUT-DATED AND PARTIALLY ILLEGIBLE. PLEASE SUBMIT AN |
| ACTUAL CURRENT PRODUCT APPROVAL OR THE PROPOSED STAND, |
| APPROVED IN WRITING BY THE DESIGNER OF RECORD IN |
| ACCORDANCE WITH FBC-B 106.3.3. |
| |
| 6. ENERGY CODE COMPLIANCE FORM SUBMITTED IS OUT OF |
| DATE. THE CORRECT FORM IS 400B-08 AS OF MARCH 1, 2009. |
| |