Plan Review Notes
Plan Review Notes For Permit 09060210
Permit Number 09060210
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-06-29 10:06:04*****DENIED*****
  
  
 1. EFFECTIVE 12/31/08, THE 2006 EDITION OF NFPA 101,
 LIFE SAFETY CODE, SHALL BE REFERENCED. ON SHEET A-1,
 GENERAL NOTE #1, UPDATE TO CURRENT NFPA 101 EDITION.
  
 2. THE ACTUAL/CORRECT ADDRESS SHALL BE IN THE TITLE
 BLOCK OF EACH SUBMITTED SHEET. THE CORRECT ZIP CODE FOR
 THIS PROJECT SITE IS 33407, NOT 33405 AS LISTED.
  
 3. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 4. INDICATE THE OCCUPANCY CLASSIFICATION AND OCCUPANT
 LOAD FOR THIS PROJECT SITE.
  
 5. INDICATE IF THE BUILDING IS EQUIPPED WITH FIRE
 SPRINKLER AND/OR FIRE ALARM SYSTEMS.
  
 6. SHOW THE LOCATION OF THE 2A:10BC RATED FIRE
 EXTINUISHER(S) WHICH SATIFIES THE 75' TRAVEL DISTANCE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722