Plan Review Notes
Plan Review Notes For Permit 09060210
Permit Number 09060210
Review Stop E
Sequence Number 1
Notes
Date Text
2009-07-04 08:36:45 
  
  
  
 ** DENIED REVIEW **
  
 1) NOTE: PLEASE BE SURE PLANS CONTAIN THE CODES UNDER
 ADOPTION BY THE STATE OF FLORIDA.
 PLEASE SEE FAC 69A-60.004 AND 69A-3.012 AS THE
 APPLICABLE NFPA-101 IS THE 2006. PLANS SHOW 2003.
  
 2) NOTE: THE SUBMITTED FORM FOR ENERGY CODE COMPLIANCE
 IS FROM THE 2004 FBC. PLEASE KNOW THAT UNDER THE 2007
 FBC WITH 2009 REVISIONS THERE IS NO LONGER A METHOD
 *C*. ALL PERMIT APPLICATIONS AFTER MARCH 1ST, 2009 NEED
 TO BE UNDER THE REVISED FBC CHAPTER 13.
 PLEASE SEE 13-415.AB.5 FOR LIGHTING PERFORMANCE
 CALCULATIONS AND LEVELS PERMITTED.
 IF THERE ARE ANY QUESTIONS ON THIS PLEASE CALL.
 PLEASE KEEP IN MIND A FIXTURE LEGEND WITH SPECIFIC
 FIXTURES IS NEEDED TO VERIFY MINIMUM CODE COMPLIANCE.
  
 3) NOTE: PLEASE SEE 13-415.AB.1.2 FOR ROOMS WHICH ARE
 REQUIRED TO CONTAIN AUTOMATED LIGHTING CONTROLS WHETHER
 OR NOT THEY ARE IN A BUILDING GREATER THAN 5K SQ FT. T
 THIS WOULD BE THE KITCHEN/BREAK ROOM, CONFERENCE ROOM.
  
 4) NOTE: PLEASE SEE 422.13 OF THE 2005 NEC. WATER
 HEATER LOAD IS CONSIDERED A CONTINUOUS LOAD WHICH
 REQUIRES LOAD TO BE SHOWN AND FIGURED AT 125%.
  
 5) NOTE: PLEASE SEE 600.5 FOR REQUIRED SIGN CIRCUIT.
 THIS DOES NOT REQUIRE A SIGN TO BE INSTALLED ONLY
 PROVISIONS FOR CIRCUIT AT FRONT DOOR AREA LOCATION.
 ( VA TO BE FIGURED IS 1200VA)
  
 6) NOTE: THE LOAD CALCULATIONS SHOWN ON PLANS IS BASED
 ON A RESIDENTIAL HOUSE. PLEASE SEE NEC
 220.12,220.14,220.42,220.44, 220.43,220.56,220.60, ETC
 AND 215.3, 230.42 FOR ALL OTHER CONTINUOUS LOADS AND
 LARGEST MOTOR LOADS AT 125%.
  
 7) NOTE: PLEASE SEE 700.12F FOR CIRCUITING OF EXIT AND
 EMERGENCY LIGHTS. NO CIRCUITING SHOWN, MUST BE TO LOCAL
 LIGHTING BRANCH CIRCUIT.
  
 8) NOTE: PLEASE SEE 13-415.AB.1.4 FOR EXTERIOR LIGHTING
 CONTROLS. MAY NOT BE ONLY A SINGLE POLE SWITCH.
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  