Plan Review Notes
Plan Review Notes For Permit 09060175
Permit Number 09060175
Review Stop B
Sequence Number 2
Notes
Date Text
2009-08-07 11:33:07BUILDING PLAN REVIEW
 PERMIT: 09060175
 ADD: 1302 PARKER AVE
 CONT: PLAN REVIEW/ TBA
 TEL: (561)706-0429 / ALBERT MARINCLLO
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 AUGUST 07/2009
 2ND REVIEW
 ACTION: DENIED
  
 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009 SUPPLEMENTS.
  
 2) PLANS ARE CURRENTLY IN AS A PLAN REVIEW, BUT WHEN
 THEY ARE SUBMITTED FOR PERMIT, THEY WILL NEED TO BE
 SIGNED AND SEALED.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
 FL ADMIN CODE 61G16.003 ARCHITECTS
  
 3) COMPLIED.
  
 4) 2ND REQUEST, SHEET GC-503 GENERAL NOTE# 2 INDICATES
 A SOILS REPORT BY DUNKLEBURGER ENGINEERING AND TESTING
 WAS COMPLETED JULY 16, 2008, PLEASE SUPPLY (2) RAISED
 SEAL ORIGINALS.
  
 5) 2ND REQUEST, THERE ARE STRUCTURES FOUND ON THIS
 SHEET STRUCTUREE WITH WEIR AS WELL AS HANDRAILS,
 ALTHOUGH THE WEIR WILBE LOW GRADE THE HANDRAIL WILL BE
 ABOVE GRADE AND SUBJECT TO WIND. SHEET GC-502 DOES NOT
 INDICATE WIND DESIGN CRITERIA:1603.1.4 WIND DESIGN
 DATA. SHEET E-501 ALSO HAS LIGHT POLES THAT WILL NEED
 TO HAVE WHAT WIND DESIGN CRITERIA WOULD HAVE BEEN USED
 IN CALCULATING IF THEY WILL WITHSTAND 140 MPH WIND, IF
 DERATING FACTORS WERE USED.
  
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
  
 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
  
 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
  
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.