2009-06-10 14:25:27 | NEW FIRE ALARM EQUIPMENT FOR THE PALM BEACH |
| PHOTOGRAPHIC CENTER AT CITY CENTER. |
| |
| 1. NEW SMOKE DETECTORS SHALL BE INSTALLED A MINIMUM OF |
| AT LEAST 3' FROM AIR CONDITIONER DIFFUSERS. |
| |
| 2. THE NEW SMOKE DETECTORS THAT ARE PLANNED TO BE |
| INSTALLED SHALL NOT EXCEED THE MANUFACTURER'S |
| RECOMMENDATION OR NFPA 72, THE NATIONAL FIRE ALARM CODE |
| WITH REGARDS TO SPACING OR AREAS OF COVERAGE. |
| |
| 3. ALL NEW DEVICES WILL BE TESTED TO ENSURE PROPER |
| FUNCTION AFTER INSTALLATION. |
| |
| 4. PLEASE ENSURE THAT THE SMOKE DETECTORS REMAIN |
| COVERED TO PREVENT CONTAMINATION WHILE OTHER TRADES ARE |
| STILL WORKING INSIDE THE TENANT SPACE. |
| |
| 5. PLEASE BE ADVISED THAT SHOULD THE EXISTING FIRE |
| ALARM SYSTEM NEED TO BE SHUT DOWN FOR MORE THAN FOUR |
| HOURS IN A TWENTY FOUR HOUR PERIOD, A FIRE WATCH WILL |
| BE REQUIRED. FIRE WATCH ACTIVITIES SHALL BE APPROVED BY |
| THE BATTALION CHIEF OF FIRE PREVENTION OR HIS DESIGNEE |
| AND ALL FIRE WATCHES MUST BE REQUESTED IN WRITING. MORE |
| INFORMATION ON FIRE WATCH PROCEDURES CAN BE OBTAINED BY |
| CALLING 804-4709. |
| |
| 6. ACCEPTANCE TESTING FOR THE NEW DEVICES WILL NEED TO |
| OCCUR AFTER HOURS SO AS TO NOT TO DISRUPT CITY CENTER |
| EMPLOYEES OR LIBRARY PATRONS. |
| |
| 7. INSTALLATION SUBJECT TO FIELD INSPECTION AND |
| APPROVAL. |
| |
| 8. NO LEGEND COULD BE LOCATED ON THE DRAWINGS. |
| |
| |