2009-06-10 14:25:27NEW FIRE ALARM EQUIPMENT FOR THE PALM BEACH
 PHOTOGRAPHIC CENTER AT CITY CENTER.
  
 1. NEW SMOKE DETECTORS SHALL BE INSTALLED A MINIMUM OF
 AT LEAST 3' FROM AIR CONDITIONER DIFFUSERS.
  
 2. THE NEW SMOKE DETECTORS THAT ARE PLANNED TO BE
 INSTALLED SHALL NOT EXCEED THE MANUFACTURER'S
 RECOMMENDATION OR NFPA 72, THE NATIONAL FIRE ALARM CODE
 WITH REGARDS TO SPACING OR AREAS OF COVERAGE.
  
 3. ALL NEW DEVICES WILL BE TESTED TO ENSURE PROPER
 FUNCTION AFTER INSTALLATION.
  
 4. PLEASE ENSURE THAT THE SMOKE DETECTORS REMAIN
 COVERED TO PREVENT CONTAMINATION WHILE OTHER TRADES ARE
 STILL WORKING INSIDE THE TENANT SPACE.
  
 5. PLEASE BE ADVISED THAT SHOULD THE EXISTING FIRE
 ALARM SYSTEM NEED TO BE SHUT DOWN FOR MORE THAN FOUR
 HOURS IN A TWENTY FOUR HOUR PERIOD, A FIRE WATCH WILL
 BE REQUIRED. FIRE WATCH ACTIVITIES SHALL BE APPROVED BY
 THE BATTALION CHIEF OF FIRE PREVENTION OR HIS DESIGNEE
 AND ALL FIRE WATCHES MUST BE REQUESTED IN WRITING. MORE
 INFORMATION ON FIRE WATCH PROCEDURES CAN BE OBTAINED BY
 CALLING 804-4709.
  
 6. ACCEPTANCE TESTING FOR THE NEW DEVICES WILL NEED TO
 OCCUR AFTER HOURS SO AS TO NOT TO DISRUPT CITY CENTER
 EMPLOYEES OR LIBRARY PATRONS.
  
 7. INSTALLATION SUBJECT TO FIELD INSPECTION AND
 APPROVAL.
  
 8. NO LEGEND COULD BE LOCATED ON THE DRAWINGS.
  
  
 APPROVED PROVISO:
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX