Date Text
2009-10-05 15:42:07***FAILED***
  
 1. PLEASE SHOW THE PROPOSED HEDGING ON THE PLANS,
 INCLUDING MATERIAL HEIGHT AND SPACING. NOTE THAT SINCE
 THE GENERATOR HEIGHT IS APPROXIMATELY 9.5 FEET THE
 HEDGE MATERIAL NEEDS TO BE AT LEAST 8 FEET IN HEIGHT AT
 THE TIME OF INSTALLATION. AS AN ALTERNATIVE, A 10 FOOT
 FENCE COULD BE INSTALLED AROUND THE GENERATOR WHICH
 WOULD ALLOW YOU TO INSTALL THE HEDGES AT 24 INCHES IN
 HEIGHT. IN ANY EVENT, BEAR IN MIND THE REQUIRED
 CLEARANCES FOR THE GENERATOR SO THAT FENCING AND/OR
 LANDSCAPE MATERIALS DO NOT INCROACH INTO IT.
  
 NOTE THAT WHATEVER COMBINATION OF PLANTS AND FENCING IS
 USED, IT MUST BE SHOWN ON THE PLAN WITH DIMENSIONS AND
 SPECIFICATIONS.
  