Plan Review Notes For Permit 09060159 |
Permit Number |
09060159 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2009-10-01 09:45:31 | | | **PROVISO ** | | | | | | | | 1) NOTE: THIS IS NOTE #4 FROM PREVIOUS REVIEW IS STILL | | APPLICABLE. PLEASE SEE NEC 230.70, 71. THE CITY OF WEST | | PALM BEACH IS AWARE OF THE OLD PREVIOUS TECHNICAL | | AMENDMENTS BEFORE THE 2001 FBC. HOWEVER THE NEC STATES | | THE DISTANCE OF UNPROTECTED CONDUCTORS IS UP TO THE | | AHJ. THIS AHJ HAS REMAINED WITH NO MORE THAN 8FT BASED | | KEEPING WITH THE PREVIOUS TECHNICAL AMENDED CODES. SOME | | JURISDICTIONS HAVE A 0 FT REQUIREMENT THAT DOES NOT | | PERMIT UNPROTECTED CONDUCTORS INSIDE THE BUILDING AT | | ALL. | | THE INSTALLATION FOR THE NEW SERVICE ENTRANCE | | CONDUCTORS IS NEW. THERE HAVE BEEN SEVERAL OTHERS WHICH | | HAVE EITHER POURED INTO A CONCRETE TROUGH OR PLACED | | UNDER SLAB TO MINIMIZE THE LENGTH INSIDE BUILDING. | | PLEASE SEE 230.6 FOR CONDUCTORS INSIDE BUILDING. THIS | | WAS GONE OVER THE CHIEF ELECTRICAL INSPECTOR ALSO. | | THE CONDUCTORS FOR EM ATS/MAIN MUST MEET 700.9C, D1 | | | | **IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|