Plan Review Notes
Plan Review Notes For Permit 09060159
Permit Number 09060159
Review Stop E
Sequence Number 2
Notes
Date Text
2009-10-01 09:45:31 
 **PROVISO **
  
  
  
 1) NOTE: THIS IS NOTE #4 FROM PREVIOUS REVIEW IS STILL
 APPLICABLE. PLEASE SEE NEC 230.70, 71. THE CITY OF WEST
 PALM BEACH IS AWARE OF THE OLD PREVIOUS TECHNICAL
 AMENDMENTS BEFORE THE 2001 FBC. HOWEVER THE NEC STATES
 THE DISTANCE OF UNPROTECTED CONDUCTORS IS UP TO THE
 AHJ. THIS AHJ HAS REMAINED WITH NO MORE THAN 8FT BASED
 KEEPING WITH THE PREVIOUS TECHNICAL AMENDED CODES. SOME
 JURISDICTIONS HAVE A 0 FT REQUIREMENT THAT DOES NOT
 PERMIT UNPROTECTED CONDUCTORS INSIDE THE BUILDING AT
 ALL.
 THE INSTALLATION FOR THE NEW SERVICE ENTRANCE
 CONDUCTORS IS NEW. THERE HAVE BEEN SEVERAL OTHERS WHICH
 HAVE EITHER POURED INTO A CONCRETE TROUGH OR PLACED
 UNDER SLAB TO MINIMIZE THE LENGTH INSIDE BUILDING.
 PLEASE SEE 230.6 FOR CONDUCTORS INSIDE BUILDING. THIS
 WAS GONE OVER THE CHIEF ELECTRICAL INSPECTOR ALSO.
 THE CONDUCTORS FOR EM ATS/MAIN MUST MEET 700.9C, D1
  
 **IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  