Plan Review Notes
Plan Review Notes For Permit 09060159
Permit Number 09060159
Review Stop M
Sequence Number 1
Notes
Date Text
2009-07-13 13:51:03REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. ALL APPLIANCES EXPOSED TO WIND SHALL BE DESIGNED AND
 INSTALLED FOR WIND RESISTANCE IN ACCORDANCE WITH FBC-M
 301.12. PAGE 31 OF THE SUBMITTAL PACKAGE INDICATES THE
 WEATHERPROOF ENCLOSURE WAS DESIGNED TO ASCE 7-98 FOR
 WIND RESISTANCE. THE CURRENT REFERENCE STANDARD IN THE
 2007 FBC FOR WIND RESISTANCE IS ASCE 7-05 IN ACCORDANCE
 WITH FBC-B CHAPTER 35. PLEASE UPDATE ALL WIND
 RESISTANCE ANALYTICAL DATA AND DESIGN CRITERIA TO
 REFLECT COMPLIANCE WITH THE CURRENTLY ADOPTED REFERENCE
 STANDARD.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: