Date Text
2009-07-09 17:02:33 
 ** DENIED **
  
 1) NOTE: PLEASE PROVIDE SELECTIVE COORDINATION STUDY
 FOR 700 AND 701 SYSTEMS. PLEASE SEE 701.27, 701.18 AND
 240.12. NFPA-110 6.5.1
  
 2) NOTE: PLEASE PROVIDE ELEVATION FOR EPS EQUIPMENT
 MEETING THE 100 YR STORM ELEVATIONS OR LEVELS ON THE
 SLOSH CHARTS FOR AREA.
 PLEASE SEE NFPA-110 7.2.3
  
 3) NOTE: PLEASE SEE 7.2.2 AND 7.2.1. LOCATIONS OF
 EQUIPMENT CLEARANCES OF ATS EQUIPMENT TWICE THE
 MINIMUMS PER 110.26 OF NFPA-70.
  
 4) NOTE: PLEASE KNOW THAT NO MORE THAN 8FT OF
 UNPROTECTED CONDUCTORS ARE PERMITTED INSIDE THE
 BUILDING. PLEASE SEE 230.70, 230.6 FOR WHAT IS
 CONSIDERED OUTSIDE THE BUILDING.
  
 5) NOTE: IT IS UNCLEAR OF THE INTENT OF SERVICE RISER.
 IT APPEARS THE EXISTING 2000AMP SERVICE WILL BE TAPPED
 AND FED FROM NEW 400AMP SERVICE. THE LOADS SHOWN PER
 220.87 ARE INDICATED HOWEVER THE MINIMUM SERVICE SIZE
 FOR BUILDING IS STILL REQUIRED TO BE SIZED PER MINIMUM
 LOAD CALCULATIONS.
 THIS IS BASED ON DETERMINING EXISTING LOADS.
 THE REMAINDER OF 220 WOULD APPLY FOR MINIMUM SERVICE
 SIZE.
  
 ** IF THIS IS NOT THE INTENT THEN PLEASE CALL TO GO
 OVER. BASED ON THE RISER IT APPEARS THE LINE SIDE OF
 GUTTER WHICH IS FED FROM THE EXISTING 2000AMP MAIN WILL
 BECOME NEW SERVICE FEEDERS.
  
 *** PLEASE BE AWARE OF OTHER COMMENTS FROM OTHER TRADES
 WHICH WILL AFFECT PLANS.
  
  
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  