2009-07-09 17:02:33 | |
| ** DENIED ** |
| |
| 1) NOTE: PLEASE PROVIDE SELECTIVE COORDINATION STUDY |
| FOR 700 AND 701 SYSTEMS. PLEASE SEE 701.27, 701.18 AND |
| 240.12. NFPA-110 6.5.1 |
| |
| 2) NOTE: PLEASE PROVIDE ELEVATION FOR EPS EQUIPMENT |
| MEETING THE 100 YR STORM ELEVATIONS OR LEVELS ON THE |
| SLOSH CHARTS FOR AREA. |
| PLEASE SEE NFPA-110 7.2.3 |
| |
| 3) NOTE: PLEASE SEE 7.2.2 AND 7.2.1. LOCATIONS OF |
| EQUIPMENT CLEARANCES OF ATS EQUIPMENT TWICE THE |
| MINIMUMS PER 110.26 OF NFPA-70. |
| |
| 4) NOTE: PLEASE KNOW THAT NO MORE THAN 8FT OF |
| UNPROTECTED CONDUCTORS ARE PERMITTED INSIDE THE |
| BUILDING. PLEASE SEE 230.70, 230.6 FOR WHAT IS |
| CONSIDERED OUTSIDE THE BUILDING. |
| |
| 5) NOTE: IT IS UNCLEAR OF THE INTENT OF SERVICE RISER. |
| IT APPEARS THE EXISTING 2000AMP SERVICE WILL BE TAPPED |
| AND FED FROM NEW 400AMP SERVICE. THE LOADS SHOWN PER |
| 220.87 ARE INDICATED HOWEVER THE MINIMUM SERVICE SIZE |
| FOR BUILDING IS STILL REQUIRED TO BE SIZED PER MINIMUM |
| LOAD CALCULATIONS. |
| THIS IS BASED ON DETERMINING EXISTING LOADS. |
| THE REMAINDER OF 220 WOULD APPLY FOR MINIMUM SERVICE |
| SIZE. |
| |
| ** IF THIS IS NOT THE INTENT THEN PLEASE CALL TO GO |
| OVER. BASED ON THE RISER IT APPEARS THE LINE SIDE OF |
| GUTTER WHICH IS FED FROM THE EXISTING 2000AMP MAIN WILL |
| BECOME NEW SERVICE FEEDERS. |
| |
| *** PLEASE BE AWARE OF OTHER COMMENTS FROM OTHER TRADES |
| WHICH WILL AFFECT PLANS. |
| |
| |
| |
| |
| |
| ** IMPORTANT ** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |