2009-06-23 15:58:58 | BUILDING PLAN REVIEW |
| PERMIT: 09060159 |
| ADD: 1501 S FLAGLER DR. |
| CONT: CARPENTER ELECTRIC |
| TEL: (561)848-7881 |
| FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW |
| ACTION: DENIED |
| |
| 1) PLANS SUBMITTED INDICATE THE 2004 FBC , FOR PERMIT |
| (FIRST TIME REVIEW) AFTER MARCH 1ST, 2009 SHALL BE |
| REVIEWED TO THE 2007 FBC BUILDING WITH 2009 |
| SUPPLEMENTS. PLEASE UPDATE PLANS. |
| |
| 2) FOR MAINTENANCE AND WEEKLY VISUAL INSPECTION OF |
| GENERATOR A ELEVATED PLATFORM, STAIR AND GUARDRAIL |
| SYSTEM WILL BE REQUIRED. NFPA 110: 8.4 OPERATIONAL |
| INSPECTION AND TESTING. |
| |
| 8.4.1* EPSSS, INCLUDING ALL APPURTENANT COMPONENTS, |
| SHALL BE INSPECTED WEEKLY AND EXERCISED UNDER LOAD AT |
| LEAST MONTHLY. |
| |
| 2A ) STAIRS 1009.3 EXCEPTION# 7. INDUSTRIAL EQUIPMENT |
| ACCESS STAIRS AND LANDINGS THAT SERVE AS A COMPONENT OF |
| THE MEANS OF EGRESS FROM THE INVOLVED EQUIPMENT AND DO |
| NOT SERVE MORE THAN |
| 20 PEOPLE SHALL BE PERMITTED TO HAVE A MINIMUM CLEAR |
| WIDTH OF 22 INCHES (559 MM), MINIMUM TREAD DEPTH OF 10 |
| INCHES (254 MM), MAXIMUM RISER HEIGHT OF 9 INCHES (229 |
| MM), MINIMUM |
| HEADROOM OF 6 FEET 8 INCHES (2032 MM), AND A MAXIMUM |
| HEIGHT BETWEEN LANDINGS OF 12 FEET (36 576 MM). |
| |
| 2B ) GAURDRAILS: 1012.1 WHERE REQUIRED. |
| GUARDS SHALL BE LOCATED ALONG OPEN-SIDED WALKING |
| SURFACES, INDUSTRIAL EQUIPMENT PLATFORMS, LANDINGS |
| WHICH ARE LOCATED MORE THAN 30 INCHES (762 MM) ABOVE |
| THE FLOOR OR GRADE BELOW. |
| GUARDS SHALL BE ADEQUATE IN STRENGTH AND ATTACHMENT IN |
| ACCORDANCE WITH SECTION 1607.7. |
| |
| 2C ) GUARD 1012.3 OPENING LIMITATIONS. EXCEPTIONS: |
| 2. AT ELEVATED WALKING SURFACES FOR ACCESS TO AND USE |
| OF ELECTRICAL, MECHANICAL OR PLUMBING SYSTEMS OR |
| EQUIPMENT, GUARDS SHALL HAVE BALUSTERS OR BE OF SOLID |
| MATERIALS SUCH THAT A SPHERE WITH A DIAMETER OF 21 |
| INCHES (533 MM) CANNOT PASS THROUGH ANY OPENING. |
| 3.IN AREAS WHICH ARE NOT OPEN TO THE PUBLIC WITHIN |
| OCCUPANCIES IN GROUP I-3, F, H OR S, BALUSTERS, |
| HORIZONTAL INTERMEDIATE RAILS OR OTHER CONSTRUCTION |
| SHALL NOT PERMIT A SPHERE WITH A |
| DIAMETER OF 21 INCHES (533 MM) TO PASS THROUGH ANY |
| OPENING. |
| |
| JIM WITMER C. B. O. |
| BUILDING PLAN REVIEW II |
| |
| TEL: (561)805-6715 |
| FAX: (561)805-6731 |
| E-MAIL: [email protected] |
| SURVEY: |
| WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| |
| |
| |
| |