2009-06-23 15:58:58BUILDING PLAN REVIEW
 PERMIT: 09060159
 ADD: 1501 S FLAGLER DR.
 CONT: CARPENTER ELECTRIC
 TEL: (561)848-7881
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1) PLANS SUBMITTED INDICATE THE 2004 FBC , FOR PERMIT
 (FIRST TIME REVIEW) AFTER MARCH 1ST, 2009 SHALL BE
 REVIEWED TO THE 2007 FBC BUILDING WITH 2009
 SUPPLEMENTS. PLEASE UPDATE PLANS.
  
 2) FOR MAINTENANCE AND WEEKLY VISUAL INSPECTION OF
 GENERATOR A ELEVATED PLATFORM, STAIR AND GUARDRAIL
 SYSTEM WILL BE REQUIRED. NFPA 110: 8.4 OPERATIONAL
 INSPECTION AND TESTING.
  
 8.4.1* EPSSS, INCLUDING ALL APPURTENANT COMPONENTS,
 SHALL BE INSPECTED WEEKLY AND EXERCISED UNDER LOAD AT
 LEAST MONTHLY.
  
 2A ) STAIRS 1009.3 EXCEPTION# 7. INDUSTRIAL EQUIPMENT
 ACCESS STAIRS AND LANDINGS THAT SERVE AS A COMPONENT OF
 THE MEANS OF EGRESS FROM THE INVOLVED EQUIPMENT AND DO
 NOT SERVE MORE THAN
 20 PEOPLE SHALL BE PERMITTED TO HAVE A MINIMUM CLEAR
 WIDTH OF 22 INCHES (559 MM), MINIMUM TREAD DEPTH OF 10
 INCHES (254 MM), MAXIMUM RISER HEIGHT OF 9 INCHES (229
 MM), MINIMUM
 HEADROOM OF 6 FEET 8 INCHES (2032 MM), AND A MAXIMUM
 HEIGHT BETWEEN LANDINGS OF 12 FEET (36 576 MM).
  
 2B ) GAURDRAILS: 1012.1 WHERE REQUIRED.
 GUARDS SHALL BE LOCATED ALONG OPEN-SIDED WALKING
 SURFACES, INDUSTRIAL EQUIPMENT PLATFORMS, LANDINGS
 WHICH ARE LOCATED MORE THAN 30 INCHES (762 MM) ABOVE
 THE FLOOR OR GRADE BELOW.
 GUARDS SHALL BE ADEQUATE IN STRENGTH AND ATTACHMENT IN
 ACCORDANCE WITH SECTION 1607.7.
  
 2C ) GUARD 1012.3 OPENING LIMITATIONS. EXCEPTIONS:
 2. AT ELEVATED WALKING SURFACES FOR ACCESS TO AND USE
 OF ELECTRICAL, MECHANICAL OR PLUMBING SYSTEMS OR
 EQUIPMENT, GUARDS SHALL HAVE BALUSTERS OR BE OF SOLID
 MATERIALS SUCH THAT A SPHERE WITH A DIAMETER OF 21
 INCHES (533 MM) CANNOT PASS THROUGH ANY OPENING.
 3.IN AREAS WHICH ARE NOT OPEN TO THE PUBLIC WITHIN
 OCCUPANCIES IN GROUP I-3, F, H OR S, BALUSTERS,
 HORIZONTAL INTERMEDIATE RAILS OR OTHER CONSTRUCTION
 SHALL NOT PERMIT A SPHERE WITH A
 DIAMETER OF 21 INCHES (533 MM) TO PASS THROUGH ANY
 OPENING.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved