Plan Review Notes For Permit 09060151 |
Permit Number |
09060151 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-07-06 16:46:21 | REVIEW #: 1ST | | ACTION: DENIED | | | | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | 1. PAGE M1 SHOWS TWO NEW SUPPLY DUCTS AND TWO NEW | | EXHAUST DUCTS ENTERING RESTROOMS FROM THE COMMON AREA | | CORRIDOR/ELEVATOR LOBBY AREA. ARCHITECTURAL PLANS | | INDICATE RATED WALLS AT THESE LOCATIONS. SHOW HOW DUCT | | PENETRATIONS OF THESE RATED ASSEMBLIES ARE TO BE | | PROTECTED IN ACCORDANCE WITH FBC-M 607.5. | | | | 2. PAGE M1 SHOWS 8" ROUND DUCT AT HEAT PUMP TIES INTO | | EXISTING SMOKE EVAC/FRESH AIR DUCT. FLOOR PLAN | | INDICATES THE 8" ROUND TIES IN AT THE SAME LOCATION OF | | AN EXISTING FIRE DAMPER, HALF WAY THROUGH A RATED WALL. | | PLEASE CLARIFY AND SHOW HOW REQUIRED FIRE RATINGS ARE | | TO BE MAINTAINED AT THIS LOCATION PER FBC-M 607.5. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|