Plan Review Notes
Plan Review Notes For Permit 09060151
Permit Number 09060151
Review Stop M
Sequence Number 1
Notes
Date Text
2009-07-06 16:46:21REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE M1 SHOWS TWO NEW SUPPLY DUCTS AND TWO NEW
 EXHAUST DUCTS ENTERING RESTROOMS FROM THE COMMON AREA
 CORRIDOR/ELEVATOR LOBBY AREA. ARCHITECTURAL PLANS
 INDICATE RATED WALLS AT THESE LOCATIONS. SHOW HOW DUCT
 PENETRATIONS OF THESE RATED ASSEMBLIES ARE TO BE
 PROTECTED IN ACCORDANCE WITH FBC-M 607.5.
  
 2. PAGE M1 SHOWS 8" ROUND DUCT AT HEAT PUMP TIES INTO
 EXISTING SMOKE EVAC/FRESH AIR DUCT. FLOOR PLAN
 INDICATES THE 8" ROUND TIES IN AT THE SAME LOCATION OF
 AN EXISTING FIRE DAMPER, HALF WAY THROUGH A RATED WALL.
 PLEASE CLARIFY AND SHOW HOW REQUIRED FIRE RATINGS ARE
 TO BE MAINTAINED AT THIS LOCATION PER FBC-M 607.5.
  