Plan Review Notes
Plan Review Notes For Permit 09060151
Permit Number 09060151
Review Stop E
Sequence Number 1
Notes
Date Text
2009-06-18 11:56:47 
 ** DENIED PLANS *
  
 1) NOTE: THE ELECTRICAL PLANS NEED TO STATE THE
 FOLLOWING MINIMUM CODES.
 PLEASE BE SURE THE FOLLOWING ARE STATED ON ELECTRICAL
 PLANS.
 2007 FBC W/ 2009 AMENDMENTS.
 2006 NFPA-101 ( PLANS STATE 2007 FOR THIS CODE)
 2002 NFPA-72 (OK)
 2006 NFPA-1
 2005 NFPA-70 ( PLANS STATE 2007) PLEASE BE ADVISED EVEN
 ONCE THE CODE CHANGE GOES INTO AFFECT THE IT WILL BE
 THE 2008 NEC.
  
 PER: FBC CHAPTER 35, FS 553.73, FAC 69A-60.004, .003
  
 2) NOTE: PLEASE SEE 13-415.AB.5 AND 13-415.AB.5.1 FOR
 LIGHTING PERFORMANCE CALCULATIONS. THE SECTION WHICH
 USED TO ALLOW TRADE OFFS FOR OTHER AREAS IS NO LONGER
 IN THE CODE. THE ALLOWANCE FOR SCONCES, CHANDELIERS ETC
 ARE ALSO NOT IN THE CODE.
 PLANS SHOW THE ADDITIONAL FUTURE PENDANT FIXTURES
 HOWEVER NO ALLOWANCES ARE SHOWN.
  
 3) NOTE: PLEASE INCLUDE ALL DEVICE LOCATIONS, HEIGHTS,
 AND MINIMUM LEVELS PER FBC 11-4.28.1,.2 AND .3.
 THERE ARE SOME DEVICES ON PLANS HOWEVER NO DETAILS OR
 INFORMATION ON SYMBOL LEGEND.
  
 4) NOTE: PLEASE SHOW LIGHTING FOR BATHROOMS PER
 NFPA-101 7.8, 7.9.2.1,.2.2. NO BATTERY BACK UP FIXTURES
 SHOWN FOR MINIMUM EGRESS LIGHTING.
 ** PLEASE KEEP IN MIND THE BUILDING SHALL NOT BE
 OCCUPIED UNDER EMERGENCY POWER. IF OCCUPIED UNDER
 EMERGENCY POWER IF THE GENERATOR BREAKER IS TRIPPED OR
 LOST THEN NO EGRESS LIGHTING WOULD BE PROVIDED. THIS
 COULD LEAVE LIFE SAFETY EGRESS AREAS IN TOTAL DARKNESS.
 PLEASE BE SURE TO GO OVER THIS WITH BUILDING
 OWNER/MANAGEMENT.
 OBTAIN IN WRITING THAT BUILDING SHALL NOT BE OCCUPIED
 UNDER EMERGENCY POWER.
  
  
  
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  