2009-06-18 11:56:47 | |
| ** DENIED PLANS * |
| |
| 1) NOTE: THE ELECTRICAL PLANS NEED TO STATE THE |
| FOLLOWING MINIMUM CODES. |
| PLEASE BE SURE THE FOLLOWING ARE STATED ON ELECTRICAL |
| PLANS. |
| 2007 FBC W/ 2009 AMENDMENTS. |
| 2006 NFPA-101 ( PLANS STATE 2007 FOR THIS CODE) |
| 2002 NFPA-72 (OK) |
| 2006 NFPA-1 |
| 2005 NFPA-70 ( PLANS STATE 2007) PLEASE BE ADVISED EVEN |
| ONCE THE CODE CHANGE GOES INTO AFFECT THE IT WILL BE |
| THE 2008 NEC. |
| |
| PER: FBC CHAPTER 35, FS 553.73, FAC 69A-60.004, .003 |
| |
| 2) NOTE: PLEASE SEE 13-415.AB.5 AND 13-415.AB.5.1 FOR |
| LIGHTING PERFORMANCE CALCULATIONS. THE SECTION WHICH |
| USED TO ALLOW TRADE OFFS FOR OTHER AREAS IS NO LONGER |
| IN THE CODE. THE ALLOWANCE FOR SCONCES, CHANDELIERS ETC |
| ARE ALSO NOT IN THE CODE. |
| PLANS SHOW THE ADDITIONAL FUTURE PENDANT FIXTURES |
| HOWEVER NO ALLOWANCES ARE SHOWN. |
| |
| 3) NOTE: PLEASE INCLUDE ALL DEVICE LOCATIONS, HEIGHTS, |
| AND MINIMUM LEVELS PER FBC 11-4.28.1,.2 AND .3. |
| THERE ARE SOME DEVICES ON PLANS HOWEVER NO DETAILS OR |
| INFORMATION ON SYMBOL LEGEND. |
| |
| 4) NOTE: PLEASE SHOW LIGHTING FOR BATHROOMS PER |
| NFPA-101 7.8, 7.9.2.1,.2.2. NO BATTERY BACK UP FIXTURES |
| SHOWN FOR MINIMUM EGRESS LIGHTING. |
| ** PLEASE KEEP IN MIND THE BUILDING SHALL NOT BE |
| OCCUPIED UNDER EMERGENCY POWER. IF OCCUPIED UNDER |
| EMERGENCY POWER IF THE GENERATOR BREAKER IS TRIPPED OR |
| LOST THEN NO EGRESS LIGHTING WOULD BE PROVIDED. THIS |
| COULD LEAVE LIFE SAFETY EGRESS AREAS IN TOTAL DARKNESS. |
| PLEASE BE SURE TO GO OVER THIS WITH BUILDING |
| OWNER/MANAGEMENT. |
| OBTAIN IN WRITING THAT BUILDING SHALL NOT BE OCCUPIED |
| UNDER EMERGENCY POWER. |
| |
| |
| |
| |
| |
| |
| ** IMPORTANT ** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |