Plan Review Notes
Plan Review Notes For Permit 09060146
Permit Number 09060146
Review Stop E
Sequence Number 1
Notes
Date Text
2009-06-18 08:35:31 
  
  
  
 ** DENIED PLANS *
  
 1) NOTE: THE ELECTRICAL PLANS NEED TO STATE THE
 FOLLOWING MINIMUM CODES.
 PLEASE BE SURE THE FOLLOWING ARE STATED ON ELECTRICAL
 PLANS.
 2007 FBC W/ 2009 AMENDMENTS.
 2006 NFPA-101 ( PLANS STATE 2007 FOR THIS CODE)
 2002 NFPA-72 (OK)
 2006 NFPA-1
 2005 NFPA-70 ( PLANS STATE 2007) PLEASE BE ADVISED EVEN
 ONCE THE CODE CHANGE GOES INTO AFFECT THE IT WILL BE
 THE 2008 NEC.
  
 PER: FBC CHAPTER 35, FS 553.73, FAC 69A-60.004, .003
  
 2) NOTE: PLEASE SEE 13-415.AB.5 AND 13-415.AB.5.1 FOR
 LIGHTING PERFORMANCE CALCULATIONS. THE SECTION WHICH
 USED TO ALLOW TRADE OFFS FOR OTHER AREAS IS NO LONGER
 IN THE CODE. THE ALLOWANCE FOR SCONCES, CHANDELIERS ETC
 ARE ALSO NOT IN THE CODE.
 PLANS SHOW CALCULATIONS FOR MOST AREAS HOWEVER SOME ARE
 IN QUESTION.
 FOR EXAMPLE: ROOM 631 MISSING FROM CALCULATIONS.
 FOR EXAMPLE: SQ FT FOR AREA629 EXCEED SQ FT ON PLANS.
  
 3) NOTE: PLEASE INCLUDE ALL DEVICE LOCATIONS, HEIGHTS,
 AND MINIMUM LEVELS PER FBC 11-4.28.1,.2 AND .3.
 THERE ARE SOME DEVICES ON PLANS HOWEVER NO DETAILS OR
 INFORMATION ON SYMBOL LEGEND.
  
 4) NOTE: PLEASE CLARIFY WHY PANEL 6-OHP IS SHOWN.
 FBC 106.1.1, 106.1.2 FOR ADDITIONAL INFORMATION.
 NEC 408,240,
  
  
  
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  