Plan Review Notes
Plan Review Notes For Permit 09060145
Permit Number 09060145
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-06-22 14:00:57*****PROVISO*****
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 2. ON SHEET A3.1, GENERAL NOTE #8 AND #9 REFERENCES
 FLORIDA FIRE PREVENTION CODE - 2004 EDITION. CORRELATE
 TO CURRENT EDITION AS CORRECTLY SHOWN ON SHEET T UNDER
 CODES.
  
 3. ON SHEET A3.1, AS PER BUILDING EXAMINER'S
 RED-LINING, THE NEW FIRE RATED DOOR (DOOR A) SHALL BE
 45 MINUTES.
  
 4. WILL THE SCOPE OF WORK HAVE CAUSE FOR THE SPRINKLER
 HEADS TO BE REMODELED IN ANY MANNER? IF SO, PROVIDE A
 LAYOUT OF THE FIRE SPRINKLER. (THEY MAY BE SHOWN ON
 SHEET A2.1, REFLECTED CEILING PLAN).
  
  
 THE APPROPIATE PLAN SHEET(S) TO BE FIRE-STAMPED WHEN
 THE ABOVE AS WELL AS OTHER PLAN EXAMINER(S)' COMMENTS
 HAVE BEEN ADDRESSED
  
  