Plan Review Notes
Plan Review Notes For Permit 09060135
Permit Number 09060135
Review Stop E
Sequence Number 1
Notes
Date Text
2009-07-04 09:56:39 
  
 ** DENIED REVIEW **
  
 ** PLANS WERE STAMPED BY ELECTRICAL AND COMMENTS
 REDLINED HOWEVER HAVE BEEN VOIDED BASED ON BUILDING
 REVIEW COMMENTS. THE SHEET WHICH ELECTRICAL IS SHOWN
 WILL NEED TO BE UPDATED. PLEASE ADDRESS THE OTHER MINOR
 ELECTRICAL COMMENTS BELOW AT THE SAME TIME.
  
 1) NOTE: PLEASE BE SURE PLANS CONTAIN THE CODES UNDER
 ADOPTION BY THE STATE OF FLORIDA.
  
 ELECTRICAL SHALL CONTAIN:
 2005 NFPA-70
 2006 NFPA-101
  
 PLEASE SEE FAC 69A-60.004 AND 69A-3.012.
 FS 553.73 AND 2007 FBC WITH 2009 SUPPLEMENTS
  
 2) NOTE: THE SCOPE SHOWN INCLUDES ENCLOSING AREA TO BE
 PART OF A HABITABLE ROOM. PLEASE SEE 210.52 AS
 RECEPTACLES SPACING SHALL MEET REQUIRED SPACING WITHIN
 6FT OF A DOOR. THE FIXED GLASS PANELS ARE COUNTED AS
 WALL SPACE THEREFORE REQUIRING THE RECEPTACLE TO BE
 WITHIN 6FT OF DOOR OPENING.
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  