2009-07-04 09:56:39 | |
| |
| ** DENIED REVIEW ** |
| |
| ** PLANS WERE STAMPED BY ELECTRICAL AND COMMENTS |
| REDLINED HOWEVER HAVE BEEN VOIDED BASED ON BUILDING |
| REVIEW COMMENTS. THE SHEET WHICH ELECTRICAL IS SHOWN |
| WILL NEED TO BE UPDATED. PLEASE ADDRESS THE OTHER MINOR |
| ELECTRICAL COMMENTS BELOW AT THE SAME TIME. |
| |
| 1) NOTE: PLEASE BE SURE PLANS CONTAIN THE CODES UNDER |
| ADOPTION BY THE STATE OF FLORIDA. |
| |
| ELECTRICAL SHALL CONTAIN: |
| 2005 NFPA-70 |
| 2006 NFPA-101 |
| |
| PLEASE SEE FAC 69A-60.004 AND 69A-3.012. |
| FS 553.73 AND 2007 FBC WITH 2009 SUPPLEMENTS |
| |
| 2) NOTE: THE SCOPE SHOWN INCLUDES ENCLOSING AREA TO BE |
| PART OF A HABITABLE ROOM. PLEASE SEE 210.52 AS |
| RECEPTACLES SPACING SHALL MEET REQUIRED SPACING WITHIN |
| 6FT OF A DOOR. THE FIXED GLASS PANELS ARE COUNTED AS |
| WALL SPACE THEREFORE REQUIRING THE RECEPTACLE TO BE |
| WITHIN 6FT OF DOOR OPENING. |
| |
| |
| |
| ** IMPORTANT ** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |