2009-06-05 15:41:17****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
  
 1. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED
 FAC9B72. LOCAL PRODUCT APPROVAL APPLICATION AVAILABLE
 AT WWW.FLORIDABUILDING.ORG OR HTTP://WWW.WPB.ORG/CONSTR
 UCTION/PDF/PRODUCT%20APPROVAL.PDF. PLEASE COMPLETE THE
 APPLICATION WITH ALL PERTINENT INFORMATION, INCLUDING
 HOW QUALITY ASSURANCE WILL BE ADDRESSED (A LETTER FROM
 THE ENGINEER STATING THAT SHE WILL DO AN INSPECTION IS
 ONE METHOD OF ADDRESSING QUALITY ASSURANCE).
  
 2. PROVIDE A CONTRACT FOR THIS JOB. VALUE IS TO INCLUDE
 LABOR AND MATERIALS. FBC*108.
  
 3. PLEASE CLARIFY DESIGN CRITERIA. IF THIS IS
 ASSOCIATED WITH THE MASTER PERMIT AS NOTED ON THE
 APPLICATION, AND WAS SHOWN ON THE PLANS FOR 08010413,
 THEN THE DESIGN CRITERIA SHOULD BE FBC2004 AND ASCE7-02
 AND REVIEW BY DESIGNER OF RECORD IS REQUIRED FBC*103.
 IF THIS IS A STAND-ALONE PERMIT INDEPENDENT OF
 08010413, THEN THE DESIGN CRITERIA IS FBC2007 WITH 2009
 SUPPLEMENTS AND ASCE7-05. ENGINEER HAS STATED FBC2004
 AND ASCE7-05 AS DESIGN CRITERIA; NOT CONSISTENT.
  
 4. IF ASCE7-05 IS USED AS DESIGN CRITERIA, PLEASE
 PROVIDE JUSTIFICATION FOR EXPOSURE B PRESSURES. THIS
 PARCEL APPEARS TO BE WITHIN 1500' OF EXPOSURE C
 ROUGHNESS CONDITIONS (INTRACOASTAL).
  
  
  
  
  
  