Plan Review Notes
Plan Review Notes For Permit 09060097
Permit Number 09060097
Review Stop M
Sequence Number 2
Notes
Date Text
2009-09-30 13:48:02**PROVISOS**
 1. NEED PRODUCT APPROVAL FOR PRE-ENGINEERED STAND ON
 SITE PRIOR TO INSPECTION.
 2. NEED PROTECTION OF DUCT PENETRATIONS FOR EF-1 AND
 EF-3 DUCTS AT FLOOR OR SHAFT PENETRATIONS PER FBC-M
 607.5.5 OR 607.5.6.
 3. SUBMIT MANUFACTURER'S WIND RESISTANCE DATA FOR
 ROOFTOP UNITS PER FBC-M 301.12.
 4. SUBMIT COOLING LOAD CALCULATIONS PER FBC-B
 13-407.AB.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]