Plan Review Notes For Permit 09060097 |
Permit Number |
09060097 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2009-09-30 13:48:02 | **PROVISOS** | | 1. NEED PRODUCT APPROVAL FOR PRE-ENGINEERED STAND ON | | SITE PRIOR TO INSPECTION. | | 2. NEED PROTECTION OF DUCT PENETRATIONS FOR EF-1 AND | | EF-3 DUCTS AT FLOOR OR SHAFT PENETRATIONS PER FBC-M | | 607.5.5 OR 607.5.6. | | 3. SUBMIT MANUFACTURER'S WIND RESISTANCE DATA FOR | | ROOFTOP UNITS PER FBC-M 301.12. | | 4. SUBMIT COOLING LOAD CALCULATIONS PER FBC-B | | 13-407.AB.1. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|