Date |
Text |
2009-06-29 09:20:28 | DENIED |
| REFERENCE: |
| FBC-2007 PLUMBING |
| FBC-2007 CHAPTER 11 |
| FBC-2007 FUEL GAS |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| 1. ALL SHEETS SIGNED & SEALED BY MICHAEL SIPULA. THE |
| PRINTED NAME OF THE PERSON SEALING THE DOCUMENT IS |
| REQUIRED IN THE TITLE BLOCK OF EACH SHEET. FAC |
| 61G1-16.004(6) & FS 481.2055. |
| |
| 2. SHT A.1 TOILET ROOM 5 SHALL BE ADAPTABLE. PLEASE |
| INDICATE ON PLANS. SECTION 11-4.1.3(11). |
| |
| 3. SHT A.1 THE SINKS IN THE BREAK ROOM & THE CEO BAR |
| SHALL BE ACCESSIBLE. SECTION 11-4.24. PLEASE SUBMIT A |
| DETAIL SHOWING COMPLIANCE WITH ALL SUBSECTIONS. |
| |
| 4. SHT A.1 SHOW THE CLEAR FLOOR SPACE FOR THE WATER |
| CLOSET AND LAV IN THE ACCESSIBLE STALLS. THE LAV CAN |
| NOT BE IN THE CLEAR FLOOR SPACE OF THE WATER CLOSET. |
| SEE FIGURE 11-30E. |
| |
| 5. PLEASE SHOW COMPLIANCE FOR THE FOLLOWING: |
| ___W/C'S |
| A. 11-4.16.3 HEIGHT |
| B. 11-4/16/5 FLUSH CONTROLS (SHT A.8 DETAILS C & D SHOW |
| THE FLUSH CONTROLS ON THE WRONG SIDE). |
| ___LAVS |
| A. 11-4.19.2 CLEARANCES |
| B. 11-4.19.3 CLEAR FLOOR SPACE (TR/1 & TR/2) |
| C. 11-4.19.4 EXPOSED PIPES & SURFACES |
| D. 11-4.19.5 FAUCETS |
| |
| 6. SHT A.8 THE ACCESSIBLE STALL IN TR/2 2ND FLOOR |
| LOBBY/TOILET AREA DOES NOT COMPLY WITH SECTION |
| 11-4.17.3 OR FIGURE 30E. THE LAV CAN NOT BE IN THE 5FT |
| WIDE CLEAR FLOOR SPACE. |
| |
| SHT A.8 PLEASE SHOW THE ACCESSIBLE W/C'S TO BE 18 |
| INCHES OFF THE WALL TO THE CENTERLINE OF THE FIXTURE. |
| FIGURE 30E. LAVS TO BE MINIMUM 15 INCHES OFF THE WALL |
| TO THE CENTERLINE OF THE FIXTURE TO BE CENTERED ON THE |
| 30 INCH DIMENSION OF THE CLEAR FLOOR SPACE. 11-4.19.3. |
| |
| 7. SHTS P1.01 & P2.01 FLOOR DRAINS ARE NOT APPROVED |
| INDIRECT WASTE RECEPTORS. A FLOOR SINK OR HUB DRAIN IS |
| REQUIRED. SECTIONS 802.3 & 802.3.2. |
| |
| |
| 8. SEPARATE GAS PERMIT REQUIRED. SUBMIT THE FOLLOWING |
| REQUIRED INFORMATION: |
| |
| A. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2007 RESIDENTIAL OR |
| 2007 FUEL GAS CODE. - THE CORRESPONDING LENGHTS SHALL |
| BE INDICATED TO VERIFY DISTANCE TO THE MOST REMOTE |
| OUTLET. |
| |
| B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2007 FUEL GAS CODE SEC 402.2 & RESIDENTIAL CODE |
| SEC. G2413.2. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |