Plan Review Notes
Plan Review Notes For Permit 09060097
Permit Number 09060097
Review Stop P
Sequence Number 1
Notes
Date Text
2009-06-29 09:20:28DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 11
 FBC-2007 FUEL GAS
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL SHEETS SIGNED & SEALED BY MICHAEL SIPULA. THE
 PRINTED NAME OF THE PERSON SEALING THE DOCUMENT IS
 REQUIRED IN THE TITLE BLOCK OF EACH SHEET. FAC
 61G1-16.004(6) & FS 481.2055.
  
 2. SHT A.1 TOILET ROOM 5 SHALL BE ADAPTABLE. PLEASE
 INDICATE ON PLANS. SECTION 11-4.1.3(11).
  
 3. SHT A.1 THE SINKS IN THE BREAK ROOM & THE CEO BAR
 SHALL BE ACCESSIBLE. SECTION 11-4.24. PLEASE SUBMIT A
 DETAIL SHOWING COMPLIANCE WITH ALL SUBSECTIONS.
  
 4. SHT A.1 SHOW THE CLEAR FLOOR SPACE FOR THE WATER
 CLOSET AND LAV IN THE ACCESSIBLE STALLS. THE LAV CAN
 NOT BE IN THE CLEAR FLOOR SPACE OF THE WATER CLOSET.
 SEE FIGURE 11-30E.
  
 5. PLEASE SHOW COMPLIANCE FOR THE FOLLOWING:
 ___W/C'S
 A. 11-4.16.3 HEIGHT
 B. 11-4/16/5 FLUSH CONTROLS (SHT A.8 DETAILS C & D SHOW
 THE FLUSH CONTROLS ON THE WRONG SIDE).
 ___LAVS
 A. 11-4.19.2 CLEARANCES
 B. 11-4.19.3 CLEAR FLOOR SPACE (TR/1 & TR/2)
 C. 11-4.19.4 EXPOSED PIPES & SURFACES
 D. 11-4.19.5 FAUCETS
  
 6. SHT A.8 THE ACCESSIBLE STALL IN TR/2 2ND FLOOR
 LOBBY/TOILET AREA DOES NOT COMPLY WITH SECTION
 11-4.17.3 OR FIGURE 30E. THE LAV CAN NOT BE IN THE 5FT
 WIDE CLEAR FLOOR SPACE.
  
 SHT A.8 PLEASE SHOW THE ACCESSIBLE W/C'S TO BE 18
 INCHES OFF THE WALL TO THE CENTERLINE OF THE FIXTURE.
 FIGURE 30E. LAVS TO BE MINIMUM 15 INCHES OFF THE WALL
 TO THE CENTERLINE OF THE FIXTURE TO BE CENTERED ON THE
 30 INCH DIMENSION OF THE CLEAR FLOOR SPACE. 11-4.19.3.
  
 7. SHTS P1.01 & P2.01 FLOOR DRAINS ARE NOT APPROVED
 INDIRECT WASTE RECEPTORS. A FLOOR SINK OR HUB DRAIN IS
 REQUIRED. SECTIONS 802.3 & 802.3.2.
  
  
 8. SEPARATE GAS PERMIT REQUIRED. SUBMIT THE FOLLOWING
 REQUIRED INFORMATION:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2007 RESIDENTIAL OR
 2007 FUEL GAS CODE. - THE CORRESPONDING LENGHTS SHALL
 BE INDICATED TO VERIFY DISTANCE TO THE MOST REMOTE
 OUTLET.
  
 B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2007 FUEL GAS CODE SEC 402.2 & RESIDENTIAL CODE
 SEC. G2413.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  