Plan Review Notes
Plan Review Notes For Permit 09060097
Permit Number 09060097
Review Stop M
Sequence Number 1
Notes
Date Text
2009-06-22 11:14:53REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PG M1.01 AND M1.02: FILE ROOMS APPEAR TO BE
 INCIDENTAL USE AREAS IN ACCORDANCE WITH FBC-B 508.2. IN
 FULLY SPRINKLERED BUILDINGS, THIS ROOM REQUIRES SMOKE
 PARTITIONS IN ACCORDANCE WITH 508.2.2.1. SHOW THE
 TRANSFER AIR OPENING TO BE PROTECTED WITH SMOKE DAMPER
 IN ACCORDANCE WITH FBC-710.7. NOTE: THIS CONDITION
 WOULD APPLY TO ALL INCIDENTAL USE AREAS.
  
 2. PAGE M1.01: EXHAUST DUCTS FOR EF-3 MISSING SIZE.
 PROVIDE MISSING INFORMATION IN ACCORDANCE WITH FBC-M
 501.1.
  
 3. M1.01: FLOOR PLAN SHOWS EF-3 WITH 500 CFM WHILE
 EXHAUST GRILLS AND FAN SCHEDULE CALL FOR 400 CFM.
 PLEASE COORDINATE NOTES AND PLANS IN ACCORDANCE WITH
 FBC-M 501.1 AND FBC-B 106.1.1.
  
 4. M1.01: RTU-2 AND RTU-3 SUPPLY RISERS SHOW DUCT SMOKE
 DETECTORS ON ONE BRANCH ONLY. THIS LEAVES THE OTHER
 BRANCH NOT COVERED BY DUCT SMOKE DETECTOR. THE
 DETECTORS SHALL BE LOCATED TO SAMPLE THE ENTIRE AIRFLOW
 IN ACCORDANCE WITH FBC-M 606.3.
  
 5. M1.01: EF-1, EF-2 AND EF-3 ARE SHOWN WITH THE
 EXHAUST DUCT ON THE DISCHARGE SIDE OF THE FAN LOCATED
 IN THE RETURN AIR PLENUM CEILING. EXHAUST DUCTS UNDER
 POSITIVE PRESSURE SHALL NOT BE LOCATED IN A PLENUM IN
 ACCORDANCE WITH FBC-M 601.5.
  
 6. M1.01: PROVIDE GRAVITY OPERATED OR MOTORIZED DAMPER
 ON EXHAUST DUCTS TO SHUT WHEN SPACES ARE NOT IN USE PER
 FBC-B 13-409.AB.3.3.
  
 7. M2.01 CONTAINS MOUNTING DETAILS FOR RTUS, FANS AND
 CURBS. THESE DETAILS ARE IN CONFLICT WITH CURB/UNIT
 ATTACHMENT DETAILS ON PAGE S401. PLEASE COORDINATE
 PLANS AND DETAILS AND DEMONSTRATE COMPLIANCE WITH FBC-M
 301.12.
  
 8. M2.01: PLAN CONTAINS INSTALLATION DETAIL FOR FIRE
 DAMPERS. NO PARTICULAR BRAND/MAKE OF FIRE DAMPER IS
 SPECIFIED ON PLANS. FIRE DAMPERS SHALL BE INSTALLED IN
 ACCORDANCE WITH THE MANUFACTURER???S INSTALLATION
 INSTRUCTIONS AND LISTING PER FBC-M 607.2.
  
 9. PROVIDE MANUFACTURER???S DATA SHOWING ALL OUTDOOR
 APPLIANCES SUCH AS RTUS, EXHAUST FANS AND CONDENSING
 UNITS ARE DESIGNED FOR WIND RESISTANCE IN ACCORDANCE
 WITH FBC-M 301.12. SEE COMMENT ABOVE AS MANUFACTURERS
 INSTALLATION DATA FOR WIND RESISTANCE MAY BE IN
 CONFLICT WITH MECHANICAL AND STRUCTURAL DETAILS ON
 PLANS.
  
 10. ME1.01: PLAN SHOWS CONDENSING UNITS INSTALLED ON
 ROOF STAND. NO DETAIL FOR THIS ROOF STAND COULD BE
 FOUND FOR THIS STAND. IS THIS A SITE BUILT OR
 PRE-ENGINEERED STAND? PROVIDE DETAIL FOR SITE BUILT
 STAND OR PRODUCT APPROVAL FOR PRE-ENGINEERED STAND,
 DEMONSTRATING COMPLIANCE WITH WIND RESISTANCE
 REQUIREMENTS OF FBC-M 301.12.
  
 11. P1.01 SHOWS CONDENSATE PUMPS OUTSIDE THE BUILDING
 TO DISPOSE OF CONDENSATE FROM AC-1 AND AC-2. SHOW ON
 PLANS WHERE THESE PUMPS WILL DISCHARGE THE CONDENSATE
 PER FBC-M 307.2.1. ALSO, ELECTRICAL PLANS DO NOT SHOW
 ANY POWER FOR THE PUMPS AT THE PROPOSED LOCATIONS.
 PLEASE CLARIFY THE DESIGN INTENT FOR CONDENSATE
 DISPOSAL FOR THESE UNITS.
  
 12. PROVIDE DETAIL SHOWING EXTERIOR BLOCK WALL FINISH
 ABOVE CEILING. NO SUCT DETAIL COULD BE FOUND IN
 ARCHITECTURAL PLANS. THIS IS A PLENUM SPACE. WALL SHALL
 BE INSULATED AND LINED WITH AN APPROVED AIR BARRIER IN
 ACCORDANCE WITH FBC-M 603.8.
  