2009-06-22 11:14:53 | REVIEW #: 1ST |
| ACTION: DENIED |
| |
| FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS |
| FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| |
| 1. PG M1.01 AND M1.02: FILE ROOMS APPEAR TO BE |
| INCIDENTAL USE AREAS IN ACCORDANCE WITH FBC-B 508.2. IN |
| FULLY SPRINKLERED BUILDINGS, THIS ROOM REQUIRES SMOKE |
| PARTITIONS IN ACCORDANCE WITH 508.2.2.1. SHOW THE |
| TRANSFER AIR OPENING TO BE PROTECTED WITH SMOKE DAMPER |
| IN ACCORDANCE WITH FBC-710.7. NOTE: THIS CONDITION |
| WOULD APPLY TO ALL INCIDENTAL USE AREAS. |
| |
| 2. PAGE M1.01: EXHAUST DUCTS FOR EF-3 MISSING SIZE. |
| PROVIDE MISSING INFORMATION IN ACCORDANCE WITH FBC-M |
| 501.1. |
| |
| 3. M1.01: FLOOR PLAN SHOWS EF-3 WITH 500 CFM WHILE |
| EXHAUST GRILLS AND FAN SCHEDULE CALL FOR 400 CFM. |
| PLEASE COORDINATE NOTES AND PLANS IN ACCORDANCE WITH |
| FBC-M 501.1 AND FBC-B 106.1.1. |
| |
| 4. M1.01: RTU-2 AND RTU-3 SUPPLY RISERS SHOW DUCT SMOKE |
| DETECTORS ON ONE BRANCH ONLY. THIS LEAVES THE OTHER |
| BRANCH NOT COVERED BY DUCT SMOKE DETECTOR. THE |
| DETECTORS SHALL BE LOCATED TO SAMPLE THE ENTIRE AIRFLOW |
| IN ACCORDANCE WITH FBC-M 606.3. |
| |
| 5. M1.01: EF-1, EF-2 AND EF-3 ARE SHOWN WITH THE |
| EXHAUST DUCT ON THE DISCHARGE SIDE OF THE FAN LOCATED |
| IN THE RETURN AIR PLENUM CEILING. EXHAUST DUCTS UNDER |
| POSITIVE PRESSURE SHALL NOT BE LOCATED IN A PLENUM IN |
| ACCORDANCE WITH FBC-M 601.5. |
| |
| 6. M1.01: PROVIDE GRAVITY OPERATED OR MOTORIZED DAMPER |
| ON EXHAUST DUCTS TO SHUT WHEN SPACES ARE NOT IN USE PER |
| FBC-B 13-409.AB.3.3. |
| |
| 7. M2.01 CONTAINS MOUNTING DETAILS FOR RTUS, FANS AND |
| CURBS. THESE DETAILS ARE IN CONFLICT WITH CURB/UNIT |
| ATTACHMENT DETAILS ON PAGE S401. PLEASE COORDINATE |
| PLANS AND DETAILS AND DEMONSTRATE COMPLIANCE WITH FBC-M |
| 301.12. |
| |
| 8. M2.01: PLAN CONTAINS INSTALLATION DETAIL FOR FIRE |
| DAMPERS. NO PARTICULAR BRAND/MAKE OF FIRE DAMPER IS |
| SPECIFIED ON PLANS. FIRE DAMPERS SHALL BE INSTALLED IN |
| ACCORDANCE WITH THE MANUFACTURER???S INSTALLATION |
| INSTRUCTIONS AND LISTING PER FBC-M 607.2. |
| |
| 9. PROVIDE MANUFACTURER???S DATA SHOWING ALL OUTDOOR |
| APPLIANCES SUCH AS RTUS, EXHAUST FANS AND CONDENSING |
| UNITS ARE DESIGNED FOR WIND RESISTANCE IN ACCORDANCE |
| WITH FBC-M 301.12. SEE COMMENT ABOVE AS MANUFACTURERS |
| INSTALLATION DATA FOR WIND RESISTANCE MAY BE IN |
| CONFLICT WITH MECHANICAL AND STRUCTURAL DETAILS ON |
| PLANS. |
| |
| 10. ME1.01: PLAN SHOWS CONDENSING UNITS INSTALLED ON |
| ROOF STAND. NO DETAIL FOR THIS ROOF STAND COULD BE |
| FOUND FOR THIS STAND. IS THIS A SITE BUILT OR |
| PRE-ENGINEERED STAND? PROVIDE DETAIL FOR SITE BUILT |
| STAND OR PRODUCT APPROVAL FOR PRE-ENGINEERED STAND, |
| DEMONSTRATING COMPLIANCE WITH WIND RESISTANCE |
| REQUIREMENTS OF FBC-M 301.12. |
| |
| 11. P1.01 SHOWS CONDENSATE PUMPS OUTSIDE THE BUILDING |
| TO DISPOSE OF CONDENSATE FROM AC-1 AND AC-2. SHOW ON |
| PLANS WHERE THESE PUMPS WILL DISCHARGE THE CONDENSATE |
| PER FBC-M 307.2.1. ALSO, ELECTRICAL PLANS DO NOT SHOW |
| ANY POWER FOR THE PUMPS AT THE PROPOSED LOCATIONS. |
| PLEASE CLARIFY THE DESIGN INTENT FOR CONDENSATE |
| DISPOSAL FOR THESE UNITS. |
| |
| 12. PROVIDE DETAIL SHOWING EXTERIOR BLOCK WALL FINISH |
| ABOVE CEILING. NO SUCT DETAIL COULD BE FOUND IN |
| ARCHITECTURAL PLANS. THIS IS A PLENUM SPACE. WALL SHALL |
| BE INSULATED AND LINED WITH AN APPROVED AIR BARRIER IN |
| ACCORDANCE WITH FBC-M 603.8. |
| |