2009-07-20 07:30:19PB COMMUNITY BANK-NEW CORPORATE OFFICE AT OAKTON
 COMMONS
  
 1. ALL CONSTRUCTION, DEMOLITION AND RENOVATION TO
 COMPLY WITH NFPA 241.
  
 2. BUILDING ADRESS REQUIRED. BUILDING ADDRESS IS TO BE
 A MINIMUM OF AT LEAST 6" HIGH AND 1" WIDE THAT
 CONTRASTS TO THE BACKGROUND IT IS PLACED.
  
 3. SUITABLE ACCESS LANES AND RAODS SHALL BE PROVIDED
 DURING CONSTRUCTION.
  
 4. WET FIRE HYDRANTS ARE REQUIRED PRIOR, TO, DURING,
 AND AFTER CONSTRUCTION.
  
 5. SUITABLE EXITS ARE TO BE PROVIDED DURING
 CONSTRUCTION.
  
 6. ELECTRICAL EQUIPMENT SHOWN IN STAIRS NOT RELATED TO
 EMERGENCY EQUIPMENT IS NOT PERMITTED.
  
 7. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE ALARM
 SYSTEM.
  
 8. NO FIRE SPRINKLER DRAWINGS PROVIDED. PLEASE PROVIDE
 FIRE SPRINKLER SYSTEM DRAWINGS. SEPARATE SHOP DRAWINGS
 WILL BE REQUIRED PRIOR TO INSTALLATION.
  
 9. FIRE DAMPERS TO BE DROP TESTED AFTER INSTALLATION.
  
 10. TACTILE SIGNAGE REQUIRED AT EXIT DOORS.
  
 11. MANY KNOX-BOXES ARE SHOWN. USUALLY ONLY ONE
 KNOX-BOX IS REQUIRED.
  
 12. ANY ELECTRONIC LOCKING DEVICES SHALL COMPLY WITH
 SPECIAL LOCKING ARRANGEMENTS PER CHAPTER 7 OF THE
 FLORIDA FIRE PREVENTION CODE.
  
 13. A DIRECTIONAL EXIT SIGN APPEARS TO BE NEEDED AT
 INTERSECTION OF CORRIDOR 1 AND HALL 2.
  
 14. PLEASE PROVIDE FLAMESPREAD INFORMATION FOR FOLDING
 PARTITION.
  
 15. PLEASE PROVIDE PRESCRITPIVE STRENGTH REQUIREMENTS
 FOR HANDRAILS AND GUARDRAILS.
  
 16. LOCKING CAPS WILL BE REQUIRED FOR THE FIRE
 DEPARTMENT SPRINKLER CONNECTION. APPLICATIONS CAN BE
 OBTAINED FROM FIRE RESCUE.
  
 17. THE MONITORING OF THE FIRE SPRINKLER SYSTEM AND ANY
 FIRE ALARM EQUIPMENT SHALL BE PERFORMED BY A UL LISTED
 CENTRAL STATION APPROVED FOR CENTRAL STATION SERVICE.
  
 18. FIRE EXTINGUISHER TRAINING IS REQUIRED FOR
 DESIGNATED EMPLOYEES.
  
 19. SOFFITTS SHALL NOT INTERFERE WITH THE OPERATION OF
 ANY FIRE SPRIINKLER HEADS.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4724 PHONE
 804-4774 FAX