Date Text
2009-06-22 13:49:41 
  
 ** DENIED PLANS **
  
 *** IT IS IMPORTANT TO KNOW THAT THERE IS INFORMATION
 NOT YET SHOWN OR SUBMITTED FOR REVIEW OF MINIMUM CODE
 COMPLIANCE. THEREFORE THERE MAY VERY WELL BE NEW
 COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT BE MADE
 AT THIS TIME.
  
  
 1) NOTE: PLEASE BE SURE THE FOLLOWING ADDRESS WHICH HAS
 BEEN ASSIGNED IS NOTED ON TITLE BLOCKS ALONG WITH OTHER
 SUPPORTING DOCUMENTS SUCH AS ENERGY CALCULATIONS.
 8101 OKEECHOBEE BLVD.
 FBC 106.5
 FAC 61G1-16.004, 61G15-23.002
  
 2) NOTE: PLEASE SEE COMMENTS FROM OTHER TRADES AS WELL
 AS BUILDING REVIEW COMMENTS WHICH WILL BE FORTHCOMING.
 THE SUBMITTED PLANS CONTAIN WORK ON THREE SEPARATE
 PARCELS. IF THE THREE ARE NOT LEGALLY JOINED THEN IT IS
 NOT PERMITTED TO FEED LIGHTING FOR EXAMPLE LOCATED ON
 ANOTHER LEGAL PROPERTY FROM THE MAIN BUILDING. THIS MAY
 REQUIRE A UNITY OF TITLE OR ALL WORK ON OTHER PARCELS
 SHALL BE UNDER SEPARATE PERMITS AND REQUIRE ANY SITE
 ELECTRICAL SUCH AS SITE LIGHTING TO COME FROM MORE THAN
 ONE SERVICE.
 AS THE INTENT OF SCOPE OF WORK IS NOT YET KNOW SOME
 ASPECTS OF REVIEW WILL BE BASED ON THIS BEING ALL ONE
 LEGAL PROPERTY. SEE NOTES ON SITE LIGHTING WHICH WILL
 BE BELOW. IF UNDER SEPARATE PERMITS REVIEW FOR SOME OF
 THESE ITEMS MAY BE DISCARDED.
  
 3) NOTE: PLEASE BE SURE THE PLANS CONTAIN THE FOLLOWING
 CODES AT A MINIMUM. SOME ARE CURRENT AND OK ON
 ELECTRICAL PLANS HOWEVER SHEET A.1 CONTAINS REFERENCE
 TO THE 2002 NEC/ NFPA-70. PLEASE KNOW AS OF DECEMBER 8,
 2006 THE STATE OF FLORIDA ADOPTED THE 2005 NEC/NFPA-70.
 ANOTHER CODE WHICH NEEDS TO BE REFERENCE ON PLAN IS THE
 2003 NFPA-75.
 SEE NOTES BELOW WITH RESPECT TO IT ROOM AS NOTED ON
 PLANS.
 NFPA-75 2003 IS ADOPTED PER FAC 69A-3.012
 ALSO THERE ARE OTHER DESIGNS ON PLANS WITHOUT CODE
 REFERENCES SUCH AS THE GENERATOR. ( NFPA-110)
  
 2007 FBC W/ 2009 REVISIONS
 2002 NFPA-110
 2005 NFPA-70
 2006 NFPA-101
 2003 NFPA-75
 2002 NFPA-72
  
 ** THESE ARE CODES REQUIRED BY THE ELECTRICAL REVIEW AT
 THIS TIME. SOME ARE NOTED AS THEY EXIST ON PLANS.
  
  
 4) NOTE: LANDSCAPE ARCHITECT: PLEASE SEE FLORIDA
 STATUTES 481.319 FOR REQUIRED CERTIFICATE OF
 AUTHORIZATION. PLEASE CONFIRM WITH THE DEPARTMENT OF
 BUSINESS AND PROFESSIONAL REGULATION.
 ** PLEASE ALSO BE SURE TO COORDINATE ALL SITE LIGHTING
 WITH THE MEP DESIGN TEAM AND SEE COMMENTS ABOVE WITH
 RESPECT TO SEPARATE LEGAL PROPERTIES. THERE ARE
 CONFLICTS ON LANDSCAPE PLANS COMPARED TO ELECTRICAL
 SHEETS.
  
 5) NOTE: PLEASE SUBMIT A COMPLETE SET OF PLANS. THE
 PLANS MAKE NOTE AND REFERENCES TO FIRE ALARMS PLANS
 HOWEVER NO FA SHEETS COULD BE LOCATED IN THE SUBMITTED
 SETS. THE PLANS STATE FIRE ALARM SYSTEM BY OTHERS
 HOWEVER IF THE FA IS A REQUIRED SYSTEM THEN THE BASE
 DESIGN MUST BE SHOWN AT THIS TIME.
 PLEASE SEE FS 633 AS ALL BASE BUILDING PLANS SHOWING
 MINIMUM DESIGNS FOR FIRE AND LIFE SAFETY SHALL BE PART
 OF THE BASE BUILDING DESIGN INTENT.
  
 6) NOTE: AS NOTED FOR COMMENT #4 ABOVE, IF THERE IS A
 FIRE ALARM SYSTEM PLEASE BE SURE TO SEE FBC
 11-4.28.1,.2 AND .3 FOR MINIMUM HEIGHTS, LEVELS,
 LOCATIONS ETC FOR ADA COMPLIANCE.
  
 7) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE PROPOSED ATS. THE GENERATOR WILL BE
 UNDER A SEPARATE PERMIT HOWEVER IT IS VERY IMPORTANT TO
 SEE COMMENTS BELOW WITH RESPECT TO THE LOCATION OF THE
 UNIT AND THE NG LINE IN THE BUILDING.
 THE SPECS FOR THE ATS ARE REQUIRED AT THIS TIME AS IT
 NOTES BEING SERVICE ENTRANCE RATED AND ONE OF THE
 MAINS. THERE WILL BE COMMENTS BELOW WITH RESPECT TO
 FEEDERS AND SHUT DOWN OF POWER.
 ** IF A PRODUCT IS NOT KNOWN THEN PLEASE PROVIDE SPECS
 ON A CODE COMPLIANT ITEM AT THIS TIME. 110.3,90.7,
 230.70,71, ETC
 THE PRODUCT MAY ALWAYS BE REVISED AT A LATER DATE.
  
 8) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS IN
 COMPLIANCE WITH THE FBC CHAPTER 13. THE FOLLOWING WILL
 BE NOTED FOR EXAMPLES OF NONE COMPLIANCE AND IS **
 NOT** ALL POSSIBLE ITEMS. THE INPUT DATE REPORT WILL BE
 NOTED AS IDR.
 AS THE FIXTURE LEGEND IS NOT YET COMPLETE THERE ARE
 ITEMS WHICH CAN NOT BE CONFIRMED AS BEING CODE
 COMPLIANT AT THIS TIME.
 13-415.AB.5. PLEASE ALSO NOTE, IT IS NOT PERMITTED TO
 USE MORE THAN ONE METHOD FOR CALCULATIONS.
  
 FOR EXAMPLE: PLEASE COORDINATE ALL EXTERIOR LIGHTING ON
 PLANS WITH THE IDR. THE IDR ONLY INDICATES TWO TYPES OF
 FIXTURES. THIS IS NOT POSSIBLE WHEN THE PLANS CONTAIN
 MANY OTHER FIXTURES. WHERE ARE ALL THE SITE LIGHTING
 FIXTURES WHICH ARE SHOWN AS 400W MH?
  
 FOR EXAMPLE: PLEASE SEE INTERIOR LIGHTS ON THE PLANS
 ARE NOTED AS METHOD *B* YET A METHOD *A* FLA-COM WAS
 SUBMITTED. THERE IS A LARGE DESIGN INCONSISTENCY.
 THE TOTAL WATTAGE ON THE FLA-COM INTERIOR IS IN EXCESS
 OF 18,000 WATTS YET THE PLANS STATE THE TOTAL INTERIOR
 DESIGN WATTAGE IS LESS THAN 7000WATTS. HOW IS THIS
 POSSIBLE?
 THE PLANS CONTAIN FIXTURES AND WATTAGE TYPE NOT ON THE
 IDR. PLEASE BE SURE TO GO OVER PLANS FOR ALL FIXTURES.
 ANOTHER EXAMPLE ON THE INTERIOR LIGHTING IS THE *J*
 FIXTURE. THE PLANS AND THE FIXTURE LEGEND CONTAIN
 REFERENCES TO THE FUTURE FIXTURE HOWEVER THERE IS NO
 ALLOWANCE FIGURED INTO THE SPACE BY SPACE ON PLANS OR
 THE IDR OF THE FLA-COM REPORT.
  
 FOR EXAMPLE: PLEASE SEE THE NOTES BELOW FOR WATER
 HEATERS/ LOADS. THE EXAMPLE HOWEVER FOR CHAPTER 13
 COMPLIANCE IS THE FACT THE IDR IS COMPLETELY BLANK
 UNDER *PIPING*. THE BUILDING CONTAINS ELECTRICAL HWH
 WHICH THEN ALSO CONTAIN PIPING FOR HOT WATER. PLEASE
 SEE SECTION 13-411.AB.2.
  
 ** THESE ARE A FEW EXAMPLES ONLY. THERE ARE OTHERS,
 PLEASE GO OVER ALL COMPONENTS AND SEE POSSIBLE COMMENTS
 FROM OTHER TRADES FOR ITEMS SUCH AS ROOFING
 INSULATIONS.
  
 9) NOTE: PLEASE SUBMIT VOLTAGE DROP CALCULATIONS FOR
 WORST CASE FEEDERS AND WORST CASE BRANCH CIRCUITS.
 PLEASE SEE 13-413.AB.1.1, .1.2
  
 10) NOTE: PLEASE SEE NOTE #2 ON SHEET E3.03 WHICH
 STATES CONDUCTORS #10 AND SMALLER SHALL BE THHN AND
 LARGER THAN #1 TO BE THWN. PLEASE BE AWARE THAT THE
 SITE LIGHTING FOR EXAMPLE INDICATES CONDUCTORS TO BE
 #10. DEPENDING ON COMMENT #9 ABOVE THIS MAY CHANGE
 HOWEVER BASED ON NOTES AND PANEL SCHEDULE IF #10 AWG
 CONDUCTORS ARE INSTALLED TO SITE LIGHTING THE PLANS DO
 NOT STATE THEY NEED TO BE THWN.
 PLEASE SEE LISTING FOR THHN AND THWN. THE W IS FOR WET
 LOCATIONS, ALL UNDERGROUND PIPING AND WIRING TO SITE
 LIGHTING IS CONSIDERED A WET LOCATION. THIS IS VERY
 SPECIFIC IN THE NEC.
 THEREFORE ALL CONDUCTORS INCLUDING THOSE SMALL THAN #10
 IN WET LOCATIONS SHALL BE RATED AS SUCH. THWN IS ONLY
 ONE CHOICE.
 110.3, 300.5, 310.9, 310.8B ETC.
  
 11) NOTE: PLEASE SUBMIT PHOTO-METRICS SHOWING MINIMUM
 LEVELS FOR EGRESS AREAS UNDER NORMAL AND EMERGENCY
 CONDITIONS. PLEASE SEE NFPA-101 7.8.1.3 AS THE STAIR
 LEVELS NEED TO MEET 10FT CANDLES UNDER NORMAL AND IS
 PERMITTED DOWN TO 1FT CANDLE UNDER EMERGENCY
 CONDITIONS.
 PLEASE KNOW THAT ROOMS SUCH AS THE MAIN ELECTRICAL ROOM
 AND ELEVATOR EQUIPMENT ROOM SHALL CONTAIN BATTERY BACK
 UP FIXTURES OF SOME KIND. 700.12F, 700.16.
 THIS NEEDS TO COORDINATE WITH COMMENT #17 BELOW.
  
 12) NOTE: PLEASE SEE NEC AND FBC WHICH BOTH MAKE
 REFERENCE TO ASME-17 2004 FOR ELEVATOR CODES. THIS
 OFFICE DOES NOT REVIEW FOR CODE COMPLIANCE FOR ASME
 HOWEVER IT SHOULD BE NOTED THAT FOR INFORMATION THERE
 ARE SOME ITEMS ON PLANS WHICH DO NOT MEET MINIMUM ASME
 CODES. THERE WILL BE SOME ITEMS NOTED BELOW IN OTHER
 COMMENTS FOR NEC/ FBC REQUIREMENTS HOWEVER THESE ARE
 FOR INFORMATION ONLY.
 THE INTENT IS TO PROVIDE INFORMATION WHICH MAY HELP TO
 NOT DELAY THE PROJECT WHEN IT COMES TIME FOR ELEVATOR
 INSPECTIONS.
  
 ** PLEASE CHECK THE ELEVATOR PIT LIGHTING REQUIREMENTS,
 THE SINGLE FIXTURE SHOWN MOST LIKELY DOES NOT GIVE THE
 NEW LEVELS REQUIRED FOR FT CANDLES IN PIT. ( 10FT
 CANDLES MIN)
 ** PLEASE CHECK THE LIGHTING AT SILLS/LANDINGS IN
 HALLWAYS, 10FT CANDLES MINIMUM.
 ** PLEASE CHECK LIGHTING IN ELEVATOR EQUIPMENT ROOMS.
 19 FT CANDLES MINIMUM.
  
 13) NOTE: PLEASE COMPLETE PLANS FOR ALL CIRCUITING.
 THERE ARE SOME ITEMS ON PLANS WHICH DO NOT SHOW
 CIRCUITING AT THIS TIME. PLEASE SEE CORRIDOR #4, EXIT
 SIGN, PLEASE SEE LIGHTING IN ELEVATOR EQUIPMENT ROOM
 AND MAIN ELECTRICAL ROOM.
 PANELS SCHEDULE SHALL ALSO BE SPECIFIC. MAY NOTA STATE
 *LIGHTING OR RECEPTACLES* IN GENERAL. MAY USE ALPHA OR
 NUMERIC DESIGNATIONS. IT WOULD BE *LIGHTING
 101,102,103* ETC.
 408.4, 310.16, 220.12,220.42
 THESE ARE A FEW EXAMPLES
  
 14) NOTE: PLEASE SEE NEC 620.23 FOR REQUIRED DEDICATED
 CIRCUIT FOR ROOM LIGHTING.
  
 15) NOTE: PLEASE PROVIDE CLARITY FOR THE SYSTEM WHICH
 IS GOING TO FEED THE ELEVATOR EQUIPMENT ROOM. PER FBC
 3006.2 WHICH REQUIRES A DEDICATED SYSTEM. SHEET E1.02
 STATES TO SEE ME1.01 FOR UNIT TO BE FED FROM CONDENSING
 UNIT. HOWEVER ME1.01 SHOWS MORE THAN ONE CU.
 THE SYSTEM SHALL BE DEDICATED. PANEL SCHEDULE IS NOT
 SPECIFIC.
 408.4, 310.16, 220 ETC LOADS AND OTHER ITEMS NEED TO BE
 DETERMINED.
 FBC 106.1.1, 106.1.2 FOR CLARITY AND ADDITIONAL
 INFORMATION.
  
 16) NOTE: PLEASE SHOW A SYSTEM IN COMPLIANCE WITH FBC
 CHAPTER 13, 13-415.AB.1.1,.1.2, .1.3 AND .1.4. THE
 PLANS CONTAIN MANY NOTES THAT A SYSTEM NOTES AS TIMED
 SCHEDULING IS TO BE PROVIDED HOWEVER NO SYSTEM IS
 SHOWN.
 NEED TO SHOW SYSTEM.
 NEED TO SHOW ZONES FOR AREAS OVER SQ FT PERMITTED.
 NEED TO SHOW SYSTEM FOR EACH FLOOR AS THE CODE DOES NOT
 PERMIT A SINGLE CONTROL FEEDING MORE THAN ONE FLOOR.
 NEED TO SHOW LOCATIONS OF ALL OVER RIDES AND/OR
 ALTERNATE LOCATIONS MEETING EXCEPTIONS FOR PILOT
 LIGHTS.
 PLEASE BE SURE TO INCLUDE TIME FOR BACK UP OF EXTERIOR
 PROGRAMMING ON ASTRONOMICAL TIME CLOCK.
 SEE NOTES FOR OTHER FIXTURES WHICH PER PLANS ONLY SHOW
 A SINGLE POLE SWITCH FOR CONTROL. BREAK ROOM FOR
 EXAMPLE INDICATES SOME SORT OF FIXTURE YET NO CONTROLS
 FOR AUTOMATIC SHUT OFF AS REQUIRED PER
 13-415.AB.1.1,.1.3 AND *BREAK ROOMS* UNDER .1.2.
  
 ** THERE ARE SEVERAL ITEMS WHICH COULD NOT BE REVIEWED
 FOR CODE COMPLIANCE. SEE NOTES FOR FIXTURES ALSO.
  
 17) NOTE: PLEASE COORDINATE ALL FIXTURES ON PLANS AND
 COMPLETE A FIXTURE LEGEND SHOWING MINIMUM CODE
 COMPLIANCE AT THIS TIME.
 FOR EXAMPLE: SD FIXTURES ON PLANS YET NOTHING ON
 FIXTURE LEGEND.
 FOR EXAMPLE: FIXTURE DL IS NOTED AS BEING 208V, YET THE
 PLANS INDICATE THIS CIRCUITED TO A 277/480V PANEL.
 FOR EXAMPLE: ONE OF THE ITEMS WHICH IS CONFUSING IS THE
 *R* IN THE SMALL CIRCLE ON PLANS LOCATED AT MANY OF THE
 FIXTURES. THE SYMBOL LEGEND DOES NOT LIST THIS ITEM.
 THE *R* IS LOCATED NEXT TO NUMEROUS RECESSED TYPE
 FIXTURES SO ONE WOULD ASSUME THAT PERHAPS THIS WAS FOR
 RECESSED LIGHTS. HOWEVER PLEASE SEE THE BREAK ROOM FOR
 EXAMPLE AS ONE LOCATION WHICH INDICATES LIGHTING
 FIXTURES AS *R* WITH NO OTHER DESIGNATION. IS *R* A
 FIXTURE TYPE ? OR SOME OTHER DESIGNATION.
 REVIEW FOR ITEMS SUCH AS LIGHTING PERFORMANCE
 CALCULATIONS, REQUIRED CONTROLS, LOAD CALCULATIONS,
 CIRCUITING ETC CAN NOT BE DETERMINED AT THIS TIME.
  
 ** THERE ARE MORE ITEMS, PLEASE COMPLETE ALL FIXTURES
 AND COORDINATE ALL.
  
 18) NOTE: PLEASE EXPLAIN HOW THE POWER FROM THE
 GENERATOR WILL BE SHUT DOWN IN AN EMERGENCY. THE MAINS
 ARE TURNED OFF BY FIRE PERSONNEL, THE GENERATOR WILL
 AUTOMATICALLY TURN ON PLACING HOT 277/480V FEEDERS
 INSIDE THE BUILDING TO MANY PANELS.
 PLEASE KEEP IN MIND THAT ALL DISCONNECTING MEANS SHALL
 BE RATED FOR LOAD SERVED PER 230.76,230.79.
 PLEASE GO OVER LOCATION OF UNIT WITH ALL TRADES
 INCLUDING FIRE MARSHAL.
 PLEASE SEE 445.18, AS THE FUEL SOURCE SHALL BE SHUT
 DOWN AND IN CLOSE PROXIMITY TO THE MAIN ELECTRICAL
 ROOM. PLANS WOULD ALSO CONTAIN THE GAS LINE INSIDE THE
 BUILDING.
 THERE ARE SEVERAL ITEMS WHICH COULD CREATE A LIFE
 SAFETY AND FIRE HAZARD AS THE GENERATOR WOULD STILL RUN
 AFTER TURNING OFF MAINS.
 ** PLEASE CALL TO GO OVER AND PLEASE CONTACT THE FIRE
 MARSHAL.
 PLEASE SEE NFPA-110 FOR LOCATIONS PER CHAPTER 7.
 ** PLEASE SEE COMMENTS FROM OTHER TRADES WITH RESPECT
 TO THE 100KW GENERATOR SHOWN ON SOME PLANS HOWEVER NO
 SPECIFIC STRUCTURAL DETAILS ON ROOF LOADS ETC ARE
 SHOWN.
  
 19) NOTE: PLEASE BE SURE TO STATE ON PLANS THAT THE
 BACK UP SYSTEM PROVIDED IS AN * OPTIONAL STAND-BY
 SYSTEM* ONLY. 702, 700, 701
 FBC 106.1.1 FOR CLARITY AND INFORMATION ON PLANS.
  
 20) NOTE: PLEASE SEE FBC 1006.1.2 AND NFPA-101 7.8.1.2
 WHICH REQUIRES ALL OCCUPANCY SENSORS TO BE OF FAIL SAFE
 TYPE FOR ANY LIGHTING WHICH IS PART OF THE REQUIRED
 EGRESS.
 THE PLANS SHOW THAT LIGHTING IN AREAS SUCH AS STAIRS
 AND OTHER LOCATIONS MAY OR MAY NOT BE THROUGH THE
 LIGHTING CONTROL PANEL. WHAT IS THE DESIGN INTENT?
 PLEASE SEE 13-415.AB.1 FOR CHAPTER 13 COMPLIANCE AS
 WELL AS SECTIONS NOTED ABOVE.
 ARE THERE GOING TO BE PROPOSED NIGHT LIGHTS? IF SO
 PLEASE SHOW ON PLANS.
 PLEASE KEEP IN MIND NOT ALL FIXTURES WILL BE CONSIDERED
 NIGHT LIGHTS.
  
 21) NOTE: PLEASE SEE 2003 NFPA-75 AND 2005 NEC FOR IT
 ROOM. THIS REQUIRES SEPARATION FROM OTHER AREAS. PLANS
 SHOW FILE/STORAGE AREA AS PART OF THE SEPARATED AREA.
 PLEASE SEE NEC 645.4 FOR REQUIREMENTS OF AN IT ROOM. IF
 THIS IS INDEED AS IT ROOM AS DEFINED IN 645.4 AND
 NFPA-75 THEN ALL THE ITEMS IN 645.4 ( 1-5) MUST BE MET.
 FOR EXAMPLE: 645.10 FOR REQUIRED DISCONNECTING MEANS
 FOR ALL ELECTRICAL FEEDING EQUIPMENT ALONG WITH AIR
 CONDITIONING EQUIPMENT.
 IF THIS IS NOT GOING TO BE AN IT ROOM, THEN NO WIRING
 METHODS PER NEC 645 ARE PERMITTED IN THIS LOCATION.
 PLEASE PLACE NOTES ON PLANS ACCORDINGLY.
  
 22) NOTE: PLEASE SEE FBC 1020.1.1,.1.2 WHICH UNDER THE
 2004 FBC WAS SECTION 1019. OTHER SYSTEMS SUCH AS
 SECURITY SYSTEMS WHICH ARE NOTED ON PLANS ARE NOT
 PERMITTED IN THE STAIRWAYS.
 PLANS INDICATE RECEPTACLES ALONG WITH A NOTE #14 FOR
 SECURITY SYSTEM/OTHER DEVICES TO BE LOCATED IN STAIRS.
 THIS IS NOT PERMITTED.
 ONLY SYSTEMS PERTAINING TO THE STAIR AND EXIT ENCLOSURE
 WHICH ARE A REQUIRED SYSTEM.
  
 23) NOTE: NOTED, LOW VOLTAGE SYSTEMS SUCH AS PHONE,
 CATV, ACCESS CONTROLS ETC SHALL BE UNDER SEPARATE
 PERMIT(S) ALONG WITH THE SITE LIGHTING, GENERATOR AND
 OTHERS AS NOTED BY TRADES.
  
 24) NOTE: PLEASE SEE 250.6,250.24 ETC. THE RISER
 INDICATES *EQUIPMENT GROUNDING CONDUCTORS* BEFORE THE
 FIRST MEANS OF DISCONNECT. THIS IS NOT PERMITTED. AS
 THE FIRST MEANS OF DISCONNECT IS REQUIRED TO BE BONDED
 TO THE GROUNDED CONDUCTOR, AS SHOWN THIS WOULD PARALLEL
 THE NEUTRAL (GROUNDED ) CONDUCTOR THUS CREATING
 OBJECTIONABLE CURRENTS.
 PLEASE CALL TO GO OVER IF NEEDED.
  
 25) NOTE: PLEASE KNOW THAT SIGNED, DATED AND SEALED
 WIND LOAD CALCULATIONS WILL BE REQUIRED FOR SITE
 LIGHTING POLES. ALL CALCULATIONS SHALL INCLUDE THE EPA
 ( EFFECTIVE PROJECTED AREA) OF FIXTURES.
 * THIS MAY BE PART OF THE PERMIT FOR SITE LIGHTING.
  
 26) NOTE: PLEASE SHOW THE PHOTO-METRIC LEVELS FOR ALL
 AREAS SURROUNDING THE ATM ( AUTOMATED TELLER MACHINES)
 PER FS 655.962.
  
 27) NOTE: PLEASE BE SURE ALL CONTINUOUS LOADS ARE SHOWN
 PER 422.13. PLEASE SEE 2005 NEC HANDBOOK AS ELECTRIC
 STORAGE TYPE WATER HEATERS ARE NOW CONSIDERED
 CONTINUOUS LOADS. THESE SHALL BE FIGURED INTO SERVICES
 AND FEEDERS AT 125%.
  
 28) NOTE: PLEASE SEE 422.11, 422.13. SECTION 422.13
 REQUIRES THE MINIMUM OVER CURRENT PROTECTION TO BE
 FIGURED AT 125%. HOWEVER 422.11 REQUIRES THE MAXIMUM
 OVER CURRENT PROTECTION TO BE 150%.
 BASED ON THE PANEL SCHEDULES THE WATER HEATERS ARE BOTH
 SHOWN AS 4.5KW UNITS ON 277480V PANELS. THE OCP SHOWN
 IS TOO HIGH. THE 30AMP OCP WOULD BE OK IF THESE WERE ON
 A 208, OR 240V SYSTEM.
  
 29) NOTE: PLEASE KNOW: ANY AND ALL PRODUCT APPROVAL AND
 SPECS SHOULD CONTAIN *SHOP DRAWING* REVIEW STAMPS ON
 THE COVER SHEETS. THE PLANS AND DOCUMENTS ARE SCANNED
 FOR FILE STORAGE HOWEVER THE BACK OF SHEETS AND
 DOCUMENTS WHICH ARE ESSENTIALLY BLANK ARE NOT SCANNED.
 EVEN IF THESE BACK OF DOCUMENTS WERE SCANNED, THE STAMP
 AND SIGNATURE WOULD BE ON BLANK SHEETS.
 ** PRODUCT APPROVALS
 ** SPEC SHEETS
 ETC.
  
 30) NOTE: PER BUILDING OFFICIAL, ONE SET OR MORE OF
 SUBMITTED PLANS/DOCUMENTS MAY BE RETAINED BY THIS
 OFFICE.
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  