2009-06-22 13:49:41 | |
| |
| ** DENIED PLANS ** |
| |
| *** IT IS IMPORTANT TO KNOW THAT THERE IS INFORMATION |
| NOT YET SHOWN OR SUBMITTED FOR REVIEW OF MINIMUM CODE |
| COMPLIANCE. THEREFORE THERE MAY VERY WELL BE NEW |
| COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT BE MADE |
| AT THIS TIME. |
| |
| |
| 1) NOTE: PLEASE BE SURE THE FOLLOWING ADDRESS WHICH HAS |
| BEEN ASSIGNED IS NOTED ON TITLE BLOCKS ALONG WITH OTHER |
| SUPPORTING DOCUMENTS SUCH AS ENERGY CALCULATIONS. |
| 8101 OKEECHOBEE BLVD. |
| FBC 106.5 |
| FAC 61G1-16.004, 61G15-23.002 |
| |
| 2) NOTE: PLEASE SEE COMMENTS FROM OTHER TRADES AS WELL |
| AS BUILDING REVIEW COMMENTS WHICH WILL BE FORTHCOMING. |
| THE SUBMITTED PLANS CONTAIN WORK ON THREE SEPARATE |
| PARCELS. IF THE THREE ARE NOT LEGALLY JOINED THEN IT IS |
| NOT PERMITTED TO FEED LIGHTING FOR EXAMPLE LOCATED ON |
| ANOTHER LEGAL PROPERTY FROM THE MAIN BUILDING. THIS MAY |
| REQUIRE A UNITY OF TITLE OR ALL WORK ON OTHER PARCELS |
| SHALL BE UNDER SEPARATE PERMITS AND REQUIRE ANY SITE |
| ELECTRICAL SUCH AS SITE LIGHTING TO COME FROM MORE THAN |
| ONE SERVICE. |
| AS THE INTENT OF SCOPE OF WORK IS NOT YET KNOW SOME |
| ASPECTS OF REVIEW WILL BE BASED ON THIS BEING ALL ONE |
| LEGAL PROPERTY. SEE NOTES ON SITE LIGHTING WHICH WILL |
| BE BELOW. IF UNDER SEPARATE PERMITS REVIEW FOR SOME OF |
| THESE ITEMS MAY BE DISCARDED. |
| |
| 3) NOTE: PLEASE BE SURE THE PLANS CONTAIN THE FOLLOWING |
| CODES AT A MINIMUM. SOME ARE CURRENT AND OK ON |
| ELECTRICAL PLANS HOWEVER SHEET A.1 CONTAINS REFERENCE |
| TO THE 2002 NEC/ NFPA-70. PLEASE KNOW AS OF DECEMBER 8, |
| 2006 THE STATE OF FLORIDA ADOPTED THE 2005 NEC/NFPA-70. |
| ANOTHER CODE WHICH NEEDS TO BE REFERENCE ON PLAN IS THE |
| 2003 NFPA-75. |
| SEE NOTES BELOW WITH RESPECT TO IT ROOM AS NOTED ON |
| PLANS. |
| NFPA-75 2003 IS ADOPTED PER FAC 69A-3.012 |
| ALSO THERE ARE OTHER DESIGNS ON PLANS WITHOUT CODE |
| REFERENCES SUCH AS THE GENERATOR. ( NFPA-110) |
| |
| 2007 FBC W/ 2009 REVISIONS |
| 2002 NFPA-110 |
| 2005 NFPA-70 |
| 2006 NFPA-101 |
| 2003 NFPA-75 |
| 2002 NFPA-72 |
| |
| ** THESE ARE CODES REQUIRED BY THE ELECTRICAL REVIEW AT |
| THIS TIME. SOME ARE NOTED AS THEY EXIST ON PLANS. |
| |
| |
| 4) NOTE: LANDSCAPE ARCHITECT: PLEASE SEE FLORIDA |
| STATUTES 481.319 FOR REQUIRED CERTIFICATE OF |
| AUTHORIZATION. PLEASE CONFIRM WITH THE DEPARTMENT OF |
| BUSINESS AND PROFESSIONAL REGULATION. |
| ** PLEASE ALSO BE SURE TO COORDINATE ALL SITE LIGHTING |
| WITH THE MEP DESIGN TEAM AND SEE COMMENTS ABOVE WITH |
| RESPECT TO SEPARATE LEGAL PROPERTIES. THERE ARE |
| CONFLICTS ON LANDSCAPE PLANS COMPARED TO ELECTRICAL |
| SHEETS. |
| |
| 5) NOTE: PLEASE SUBMIT A COMPLETE SET OF PLANS. THE |
| PLANS MAKE NOTE AND REFERENCES TO FIRE ALARMS PLANS |
| HOWEVER NO FA SHEETS COULD BE LOCATED IN THE SUBMITTED |
| SETS. THE PLANS STATE FIRE ALARM SYSTEM BY OTHERS |
| HOWEVER IF THE FA IS A REQUIRED SYSTEM THEN THE BASE |
| DESIGN MUST BE SHOWN AT THIS TIME. |
| PLEASE SEE FS 633 AS ALL BASE BUILDING PLANS SHOWING |
| MINIMUM DESIGNS FOR FIRE AND LIFE SAFETY SHALL BE PART |
| OF THE BASE BUILDING DESIGN INTENT. |
| |
| 6) NOTE: AS NOTED FOR COMMENT #4 ABOVE, IF THERE IS A |
| FIRE ALARM SYSTEM PLEASE BE SURE TO SEE FBC |
| 11-4.28.1,.2 AND .3 FOR MINIMUM HEIGHTS, LEVELS, |
| LOCATIONS ETC FOR ADA COMPLIANCE. |
| |
| 7) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT |
| SHEETS FOR THE PROPOSED ATS. THE GENERATOR WILL BE |
| UNDER A SEPARATE PERMIT HOWEVER IT IS VERY IMPORTANT TO |
| SEE COMMENTS BELOW WITH RESPECT TO THE LOCATION OF THE |
| UNIT AND THE NG LINE IN THE BUILDING. |
| THE SPECS FOR THE ATS ARE REQUIRED AT THIS TIME AS IT |
| NOTES BEING SERVICE ENTRANCE RATED AND ONE OF THE |
| MAINS. THERE WILL BE COMMENTS BELOW WITH RESPECT TO |
| FEEDERS AND SHUT DOWN OF POWER. |
| ** IF A PRODUCT IS NOT KNOWN THEN PLEASE PROVIDE SPECS |
| ON A CODE COMPLIANT ITEM AT THIS TIME. 110.3,90.7, |
| 230.70,71, ETC |
| THE PRODUCT MAY ALWAYS BE REVISED AT A LATER DATE. |
| |
| 8) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS IN |
| COMPLIANCE WITH THE FBC CHAPTER 13. THE FOLLOWING WILL |
| BE NOTED FOR EXAMPLES OF NONE COMPLIANCE AND IS ** |
| NOT** ALL POSSIBLE ITEMS. THE INPUT DATE REPORT WILL BE |
| NOTED AS IDR. |
| AS THE FIXTURE LEGEND IS NOT YET COMPLETE THERE ARE |
| ITEMS WHICH CAN NOT BE CONFIRMED AS BEING CODE |
| COMPLIANT AT THIS TIME. |
| 13-415.AB.5. PLEASE ALSO NOTE, IT IS NOT PERMITTED TO |
| USE MORE THAN ONE METHOD FOR CALCULATIONS. |
| |
| FOR EXAMPLE: PLEASE COORDINATE ALL EXTERIOR LIGHTING ON |
| PLANS WITH THE IDR. THE IDR ONLY INDICATES TWO TYPES OF |
| FIXTURES. THIS IS NOT POSSIBLE WHEN THE PLANS CONTAIN |
| MANY OTHER FIXTURES. WHERE ARE ALL THE SITE LIGHTING |
| FIXTURES WHICH ARE SHOWN AS 400W MH? |
| |
| FOR EXAMPLE: PLEASE SEE INTERIOR LIGHTS ON THE PLANS |
| ARE NOTED AS METHOD *B* YET A METHOD *A* FLA-COM WAS |
| SUBMITTED. THERE IS A LARGE DESIGN INCONSISTENCY. |
| THE TOTAL WATTAGE ON THE FLA-COM INTERIOR IS IN EXCESS |
| OF 18,000 WATTS YET THE PLANS STATE THE TOTAL INTERIOR |
| DESIGN WATTAGE IS LESS THAN 7000WATTS. HOW IS THIS |
| POSSIBLE? |
| THE PLANS CONTAIN FIXTURES AND WATTAGE TYPE NOT ON THE |
| IDR. PLEASE BE SURE TO GO OVER PLANS FOR ALL FIXTURES. |
| ANOTHER EXAMPLE ON THE INTERIOR LIGHTING IS THE *J* |
| FIXTURE. THE PLANS AND THE FIXTURE LEGEND CONTAIN |
| REFERENCES TO THE FUTURE FIXTURE HOWEVER THERE IS NO |
| ALLOWANCE FIGURED INTO THE SPACE BY SPACE ON PLANS OR |
| THE IDR OF THE FLA-COM REPORT. |
| |
| FOR EXAMPLE: PLEASE SEE THE NOTES BELOW FOR WATER |
| HEATERS/ LOADS. THE EXAMPLE HOWEVER FOR CHAPTER 13 |
| COMPLIANCE IS THE FACT THE IDR IS COMPLETELY BLANK |
| UNDER *PIPING*. THE BUILDING CONTAINS ELECTRICAL HWH |
| WHICH THEN ALSO CONTAIN PIPING FOR HOT WATER. PLEASE |
| SEE SECTION 13-411.AB.2. |
| |
| ** THESE ARE A FEW EXAMPLES ONLY. THERE ARE OTHERS, |
| PLEASE GO OVER ALL COMPONENTS AND SEE POSSIBLE COMMENTS |
| FROM OTHER TRADES FOR ITEMS SUCH AS ROOFING |
| INSULATIONS. |
| |
| 9) NOTE: PLEASE SUBMIT VOLTAGE DROP CALCULATIONS FOR |
| WORST CASE FEEDERS AND WORST CASE BRANCH CIRCUITS. |
| PLEASE SEE 13-413.AB.1.1, .1.2 |
| |
| 10) NOTE: PLEASE SEE NOTE #2 ON SHEET E3.03 WHICH |
| STATES CONDUCTORS #10 AND SMALLER SHALL BE THHN AND |
| LARGER THAN #1 TO BE THWN. PLEASE BE AWARE THAT THE |
| SITE LIGHTING FOR EXAMPLE INDICATES CONDUCTORS TO BE |
| #10. DEPENDING ON COMMENT #9 ABOVE THIS MAY CHANGE |
| HOWEVER BASED ON NOTES AND PANEL SCHEDULE IF #10 AWG |
| CONDUCTORS ARE INSTALLED TO SITE LIGHTING THE PLANS DO |
| NOT STATE THEY NEED TO BE THWN. |
| PLEASE SEE LISTING FOR THHN AND THWN. THE W IS FOR WET |
| LOCATIONS, ALL UNDERGROUND PIPING AND WIRING TO SITE |
| LIGHTING IS CONSIDERED A WET LOCATION. THIS IS VERY |
| SPECIFIC IN THE NEC. |
| THEREFORE ALL CONDUCTORS INCLUDING THOSE SMALL THAN #10 |
| IN WET LOCATIONS SHALL BE RATED AS SUCH. THWN IS ONLY |
| ONE CHOICE. |
| 110.3, 300.5, 310.9, 310.8B ETC. |
| |
| 11) NOTE: PLEASE SUBMIT PHOTO-METRICS SHOWING MINIMUM |
| LEVELS FOR EGRESS AREAS UNDER NORMAL AND EMERGENCY |
| CONDITIONS. PLEASE SEE NFPA-101 7.8.1.3 AS THE STAIR |
| LEVELS NEED TO MEET 10FT CANDLES UNDER NORMAL AND IS |
| PERMITTED DOWN TO 1FT CANDLE UNDER EMERGENCY |
| CONDITIONS. |
| PLEASE KNOW THAT ROOMS SUCH AS THE MAIN ELECTRICAL ROOM |
| AND ELEVATOR EQUIPMENT ROOM SHALL CONTAIN BATTERY BACK |
| UP FIXTURES OF SOME KIND. 700.12F, 700.16. |
| THIS NEEDS TO COORDINATE WITH COMMENT #17 BELOW. |
| |
| 12) NOTE: PLEASE SEE NEC AND FBC WHICH BOTH MAKE |
| REFERENCE TO ASME-17 2004 FOR ELEVATOR CODES. THIS |
| OFFICE DOES NOT REVIEW FOR CODE COMPLIANCE FOR ASME |
| HOWEVER IT SHOULD BE NOTED THAT FOR INFORMATION THERE |
| ARE SOME ITEMS ON PLANS WHICH DO NOT MEET MINIMUM ASME |
| CODES. THERE WILL BE SOME ITEMS NOTED BELOW IN OTHER |
| COMMENTS FOR NEC/ FBC REQUIREMENTS HOWEVER THESE ARE |
| FOR INFORMATION ONLY. |
| THE INTENT IS TO PROVIDE INFORMATION WHICH MAY HELP TO |
| NOT DELAY THE PROJECT WHEN IT COMES TIME FOR ELEVATOR |
| INSPECTIONS. |
| |
| ** PLEASE CHECK THE ELEVATOR PIT LIGHTING REQUIREMENTS, |
| THE SINGLE FIXTURE SHOWN MOST LIKELY DOES NOT GIVE THE |
| NEW LEVELS REQUIRED FOR FT CANDLES IN PIT. ( 10FT |
| CANDLES MIN) |
| ** PLEASE CHECK THE LIGHTING AT SILLS/LANDINGS IN |
| HALLWAYS, 10FT CANDLES MINIMUM. |
| ** PLEASE CHECK LIGHTING IN ELEVATOR EQUIPMENT ROOMS. |
| 19 FT CANDLES MINIMUM. |
| |
| 13) NOTE: PLEASE COMPLETE PLANS FOR ALL CIRCUITING. |
| THERE ARE SOME ITEMS ON PLANS WHICH DO NOT SHOW |
| CIRCUITING AT THIS TIME. PLEASE SEE CORRIDOR #4, EXIT |
| SIGN, PLEASE SEE LIGHTING IN ELEVATOR EQUIPMENT ROOM |
| AND MAIN ELECTRICAL ROOM. |
| PANELS SCHEDULE SHALL ALSO BE SPECIFIC. MAY NOTA STATE |
| *LIGHTING OR RECEPTACLES* IN GENERAL. MAY USE ALPHA OR |
| NUMERIC DESIGNATIONS. IT WOULD BE *LIGHTING |
| 101,102,103* ETC. |
| 408.4, 310.16, 220.12,220.42 |
| THESE ARE A FEW EXAMPLES |
| |
| 14) NOTE: PLEASE SEE NEC 620.23 FOR REQUIRED DEDICATED |
| CIRCUIT FOR ROOM LIGHTING. |
| |
| 15) NOTE: PLEASE PROVIDE CLARITY FOR THE SYSTEM WHICH |
| IS GOING TO FEED THE ELEVATOR EQUIPMENT ROOM. PER FBC |
| 3006.2 WHICH REQUIRES A DEDICATED SYSTEM. SHEET E1.02 |
| STATES TO SEE ME1.01 FOR UNIT TO BE FED FROM CONDENSING |
| UNIT. HOWEVER ME1.01 SHOWS MORE THAN ONE CU. |
| THE SYSTEM SHALL BE DEDICATED. PANEL SCHEDULE IS NOT |
| SPECIFIC. |
| 408.4, 310.16, 220 ETC LOADS AND OTHER ITEMS NEED TO BE |
| DETERMINED. |
| FBC 106.1.1, 106.1.2 FOR CLARITY AND ADDITIONAL |
| INFORMATION. |
| |
| 16) NOTE: PLEASE SHOW A SYSTEM IN COMPLIANCE WITH FBC |
| CHAPTER 13, 13-415.AB.1.1,.1.2, .1.3 AND .1.4. THE |
| PLANS CONTAIN MANY NOTES THAT A SYSTEM NOTES AS TIMED |
| SCHEDULING IS TO BE PROVIDED HOWEVER NO SYSTEM IS |
| SHOWN. |
| NEED TO SHOW SYSTEM. |
| NEED TO SHOW ZONES FOR AREAS OVER SQ FT PERMITTED. |
| NEED TO SHOW SYSTEM FOR EACH FLOOR AS THE CODE DOES NOT |
| PERMIT A SINGLE CONTROL FEEDING MORE THAN ONE FLOOR. |
| NEED TO SHOW LOCATIONS OF ALL OVER RIDES AND/OR |
| ALTERNATE LOCATIONS MEETING EXCEPTIONS FOR PILOT |
| LIGHTS. |
| PLEASE BE SURE TO INCLUDE TIME FOR BACK UP OF EXTERIOR |
| PROGRAMMING ON ASTRONOMICAL TIME CLOCK. |
| SEE NOTES FOR OTHER FIXTURES WHICH PER PLANS ONLY SHOW |
| A SINGLE POLE SWITCH FOR CONTROL. BREAK ROOM FOR |
| EXAMPLE INDICATES SOME SORT OF FIXTURE YET NO CONTROLS |
| FOR AUTOMATIC SHUT OFF AS REQUIRED PER |
| 13-415.AB.1.1,.1.3 AND *BREAK ROOMS* UNDER .1.2. |
| |
| ** THERE ARE SEVERAL ITEMS WHICH COULD NOT BE REVIEWED |
| FOR CODE COMPLIANCE. SEE NOTES FOR FIXTURES ALSO. |
| |
| 17) NOTE: PLEASE COORDINATE ALL FIXTURES ON PLANS AND |
| COMPLETE A FIXTURE LEGEND SHOWING MINIMUM CODE |
| COMPLIANCE AT THIS TIME. |
| FOR EXAMPLE: SD FIXTURES ON PLANS YET NOTHING ON |
| FIXTURE LEGEND. |
| FOR EXAMPLE: FIXTURE DL IS NOTED AS BEING 208V, YET THE |
| PLANS INDICATE THIS CIRCUITED TO A 277/480V PANEL. |
| FOR EXAMPLE: ONE OF THE ITEMS WHICH IS CONFUSING IS THE |
| *R* IN THE SMALL CIRCLE ON PLANS LOCATED AT MANY OF THE |
| FIXTURES. THE SYMBOL LEGEND DOES NOT LIST THIS ITEM. |
| THE *R* IS LOCATED NEXT TO NUMEROUS RECESSED TYPE |
| FIXTURES SO ONE WOULD ASSUME THAT PERHAPS THIS WAS FOR |
| RECESSED LIGHTS. HOWEVER PLEASE SEE THE BREAK ROOM FOR |
| EXAMPLE AS ONE LOCATION WHICH INDICATES LIGHTING |
| FIXTURES AS *R* WITH NO OTHER DESIGNATION. IS *R* A |
| FIXTURE TYPE ? OR SOME OTHER DESIGNATION. |
| REVIEW FOR ITEMS SUCH AS LIGHTING PERFORMANCE |
| CALCULATIONS, REQUIRED CONTROLS, LOAD CALCULATIONS, |
| CIRCUITING ETC CAN NOT BE DETERMINED AT THIS TIME. |
| |
| ** THERE ARE MORE ITEMS, PLEASE COMPLETE ALL FIXTURES |
| AND COORDINATE ALL. |
| |
| 18) NOTE: PLEASE EXPLAIN HOW THE POWER FROM THE |
| GENERATOR WILL BE SHUT DOWN IN AN EMERGENCY. THE MAINS |
| ARE TURNED OFF BY FIRE PERSONNEL, THE GENERATOR WILL |
| AUTOMATICALLY TURN ON PLACING HOT 277/480V FEEDERS |
| INSIDE THE BUILDING TO MANY PANELS. |
| PLEASE KEEP IN MIND THAT ALL DISCONNECTING MEANS SHALL |
| BE RATED FOR LOAD SERVED PER 230.76,230.79. |
| PLEASE GO OVER LOCATION OF UNIT WITH ALL TRADES |
| INCLUDING FIRE MARSHAL. |
| PLEASE SEE 445.18, AS THE FUEL SOURCE SHALL BE SHUT |
| DOWN AND IN CLOSE PROXIMITY TO THE MAIN ELECTRICAL |
| ROOM. PLANS WOULD ALSO CONTAIN THE GAS LINE INSIDE THE |
| BUILDING. |
| THERE ARE SEVERAL ITEMS WHICH COULD CREATE A LIFE |
| SAFETY AND FIRE HAZARD AS THE GENERATOR WOULD STILL RUN |
| AFTER TURNING OFF MAINS. |
| ** PLEASE CALL TO GO OVER AND PLEASE CONTACT THE FIRE |
| MARSHAL. |
| PLEASE SEE NFPA-110 FOR LOCATIONS PER CHAPTER 7. |
| ** PLEASE SEE COMMENTS FROM OTHER TRADES WITH RESPECT |
| TO THE 100KW GENERATOR SHOWN ON SOME PLANS HOWEVER NO |
| SPECIFIC STRUCTURAL DETAILS ON ROOF LOADS ETC ARE |
| SHOWN. |
| |
| 19) NOTE: PLEASE BE SURE TO STATE ON PLANS THAT THE |
| BACK UP SYSTEM PROVIDED IS AN * OPTIONAL STAND-BY |
| SYSTEM* ONLY. 702, 700, 701 |
| FBC 106.1.1 FOR CLARITY AND INFORMATION ON PLANS. |
| |
| 20) NOTE: PLEASE SEE FBC 1006.1.2 AND NFPA-101 7.8.1.2 |
| WHICH REQUIRES ALL OCCUPANCY SENSORS TO BE OF FAIL SAFE |
| TYPE FOR ANY LIGHTING WHICH IS PART OF THE REQUIRED |
| EGRESS. |
| THE PLANS SHOW THAT LIGHTING IN AREAS SUCH AS STAIRS |
| AND OTHER LOCATIONS MAY OR MAY NOT BE THROUGH THE |
| LIGHTING CONTROL PANEL. WHAT IS THE DESIGN INTENT? |
| PLEASE SEE 13-415.AB.1 FOR CHAPTER 13 COMPLIANCE AS |
| WELL AS SECTIONS NOTED ABOVE. |
| ARE THERE GOING TO BE PROPOSED NIGHT LIGHTS? IF SO |
| PLEASE SHOW ON PLANS. |
| PLEASE KEEP IN MIND NOT ALL FIXTURES WILL BE CONSIDERED |
| NIGHT LIGHTS. |
| |
| 21) NOTE: PLEASE SEE 2003 NFPA-75 AND 2005 NEC FOR IT |
| ROOM. THIS REQUIRES SEPARATION FROM OTHER AREAS. PLANS |
| SHOW FILE/STORAGE AREA AS PART OF THE SEPARATED AREA. |
| PLEASE SEE NEC 645.4 FOR REQUIREMENTS OF AN IT ROOM. IF |
| THIS IS INDEED AS IT ROOM AS DEFINED IN 645.4 AND |
| NFPA-75 THEN ALL THE ITEMS IN 645.4 ( 1-5) MUST BE MET. |
| FOR EXAMPLE: 645.10 FOR REQUIRED DISCONNECTING MEANS |
| FOR ALL ELECTRICAL FEEDING EQUIPMENT ALONG WITH AIR |
| CONDITIONING EQUIPMENT. |
| IF THIS IS NOT GOING TO BE AN IT ROOM, THEN NO WIRING |
| METHODS PER NEC 645 ARE PERMITTED IN THIS LOCATION. |
| PLEASE PLACE NOTES ON PLANS ACCORDINGLY. |
| |
| 22) NOTE: PLEASE SEE FBC 1020.1.1,.1.2 WHICH UNDER THE |
| 2004 FBC WAS SECTION 1019. OTHER SYSTEMS SUCH AS |
| SECURITY SYSTEMS WHICH ARE NOTED ON PLANS ARE NOT |
| PERMITTED IN THE STAIRWAYS. |
| PLANS INDICATE RECEPTACLES ALONG WITH A NOTE #14 FOR |
| SECURITY SYSTEM/OTHER DEVICES TO BE LOCATED IN STAIRS. |
| THIS IS NOT PERMITTED. |
| ONLY SYSTEMS PERTAINING TO THE STAIR AND EXIT ENCLOSURE |
| WHICH ARE A REQUIRED SYSTEM. |
| |
| 23) NOTE: NOTED, LOW VOLTAGE SYSTEMS SUCH AS PHONE, |
| CATV, ACCESS CONTROLS ETC SHALL BE UNDER SEPARATE |
| PERMIT(S) ALONG WITH THE SITE LIGHTING, GENERATOR AND |
| OTHERS AS NOTED BY TRADES. |
| |
| 24) NOTE: PLEASE SEE 250.6,250.24 ETC. THE RISER |
| INDICATES *EQUIPMENT GROUNDING CONDUCTORS* BEFORE THE |
| FIRST MEANS OF DISCONNECT. THIS IS NOT PERMITTED. AS |
| THE FIRST MEANS OF DISCONNECT IS REQUIRED TO BE BONDED |
| TO THE GROUNDED CONDUCTOR, AS SHOWN THIS WOULD PARALLEL |
| THE NEUTRAL (GROUNDED ) CONDUCTOR THUS CREATING |
| OBJECTIONABLE CURRENTS. |
| PLEASE CALL TO GO OVER IF NEEDED. |
| |
| 25) NOTE: PLEASE KNOW THAT SIGNED, DATED AND SEALED |
| WIND LOAD CALCULATIONS WILL BE REQUIRED FOR SITE |
| LIGHTING POLES. ALL CALCULATIONS SHALL INCLUDE THE EPA |
| ( EFFECTIVE PROJECTED AREA) OF FIXTURES. |
| * THIS MAY BE PART OF THE PERMIT FOR SITE LIGHTING. |
| |
| 26) NOTE: PLEASE SHOW THE PHOTO-METRIC LEVELS FOR ALL |
| AREAS SURROUNDING THE ATM ( AUTOMATED TELLER MACHINES) |
| PER FS 655.962. |
| |
| 27) NOTE: PLEASE BE SURE ALL CONTINUOUS LOADS ARE SHOWN |
| PER 422.13. PLEASE SEE 2005 NEC HANDBOOK AS ELECTRIC |
| STORAGE TYPE WATER HEATERS ARE NOW CONSIDERED |
| CONTINUOUS LOADS. THESE SHALL BE FIGURED INTO SERVICES |
| AND FEEDERS AT 125%. |
| |
| 28) NOTE: PLEASE SEE 422.11, 422.13. SECTION 422.13 |
| REQUIRES THE MINIMUM OVER CURRENT PROTECTION TO BE |
| FIGURED AT 125%. HOWEVER 422.11 REQUIRES THE MAXIMUM |
| OVER CURRENT PROTECTION TO BE 150%. |
| BASED ON THE PANEL SCHEDULES THE WATER HEATERS ARE BOTH |
| SHOWN AS 4.5KW UNITS ON 277480V PANELS. THE OCP SHOWN |
| IS TOO HIGH. THE 30AMP OCP WOULD BE OK IF THESE WERE ON |
| A 208, OR 240V SYSTEM. |
| |
| 29) NOTE: PLEASE KNOW: ANY AND ALL PRODUCT APPROVAL AND |
| SPECS SHOULD CONTAIN *SHOP DRAWING* REVIEW STAMPS ON |
| THE COVER SHEETS. THE PLANS AND DOCUMENTS ARE SCANNED |
| FOR FILE STORAGE HOWEVER THE BACK OF SHEETS AND |
| DOCUMENTS WHICH ARE ESSENTIALLY BLANK ARE NOT SCANNED. |
| EVEN IF THESE BACK OF DOCUMENTS WERE SCANNED, THE STAMP |
| AND SIGNATURE WOULD BE ON BLANK SHEETS. |
| ** PRODUCT APPROVALS |
| ** SPEC SHEETS |
| ETC. |
| |
| 30) NOTE: PER BUILDING OFFICIAL, ONE SET OR MORE OF |
| SUBMITTED PLANS/DOCUMENTS MAY BE RETAINED BY THIS |
| OFFICE. |
| |
| |
| ** IMPORTANT ** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |