Plan Review Notes
Plan Review Notes For Permit 09060097
Permit Number 09060097
Review Stop B
Sequence Number 1
Notes
Date Text
2009-06-26 17:57:58****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. IT APPEARS THAT THIS PARCEL MAY BE LOCATED IN A HIGH
 HAZARD FLOOD ZONE. THE STRUCTURE IS TO COMPLY WITH WPB
 ADMIN CODE 94-546(B). PLEASE NOTE FINISHED FLOOR
 ELEVATION, MINIMUM 6" ABOVE BASE FLOOD, ON THE PLAN AND
 PROVIDE THE FLOOD ELEVATION CERTIFICATE. A FORM BOARD
 ELEVATION CERTIFICATE AS WELL AS A FINAL ELEVATION
 CERTIFICATE WILL BE REQUIRED.
  
 2. IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY PRIOR
 TO PERMIT ISSUANCE, 2300 N JOG RD. PLEASE CALL
 561-233-5025 FOR MORE INFORMATION. THE PLANS MUST BE
 STAMPED AND THE RECEIPT IS TO BE INCLUDED WITH THE
 PERMIT APPLICATION.
  
 3. RADON FEES DUE, FS*553.721. SEE ATTACHED.
  
 4. FIRE SPRINKLER PLANS REQUIRED IF SPRINKLERS ARE
 REQUIRED FOR CODE COMPLIANCE, FBC*106.3.5.1.1(5),
 FS553.79 (2). SOME SHEETS REFER TO ATTACHED FIRE
 SPRINKLER/FIRE ALARM PLANS, BUT THEY WERE NOT INCLUDED.
  
 5. PLEASE SEE ZONING COMMENTS AND CLARIFY LOCATION OF
 PARCEL LINES. PLEASE CLARIFY LOCATION OF IMPROVEMENTS
 IN RELATION TO THE LEGAL RECORDED LOT LINES/PLAT. THE
 TRACTS SHOWN ON THE PLAN ARE NOT CONSISTENT WITH COUNTY
 RECORDS. WWW.PBCGOV.COM/PAPA, WWW.PBCOUNTYCLERK.COM
  
 6. AREA INCREASE CALCULATIONS ARE TO BE INCLUDED ON THE
 PLAN TO SHOW COMPLIANCE WITH FBC TABLE 503, SHEET A1.
  
 7. STORAGE AREAS AND A CONFERENCE ROOM (ASSEMBLY) ARE
 SHOWN. PLEASE INCLUDE THESE AREAS IN THE AREA
 CALCULATIONS, SHEET A1, FBC508.1. ANY ACCESSORY OR
 INCIDENTAL USE AREAS ARE TO BE NOTED AS SUCH WITH
 APPROPRIATE FIRE RESISTIVE SEPARATIONS NOTED ON THE
 PLAN (BOTH HORIZONTAL AND VERTICAL), FBC TABLE 508.2,
 FBC 508.3.1.
  
 8. STAIR CONSTRUCTION TO COMPLY WITH FBC1020.1. FIRE
 RATING FOR FIRE BARRIER NOT SHOWN, A1, WALL SYMBOLS.
 SPECIFY FIRE RESISTIVE RATING AND PROVIDE A DETAIL,
 FBC703.2.
  
 9. STAIR CONSTRUCTION TO COMPLY WITH FBC1020.1.4,
 PLEASE NOTE REQUIRED FIRE RESISTANCE ON WALLS WITHIN
 10FT AS WELL AS OPENINGS WITHIN THE 10FT. PROVIDE
 PRODUCT APPROVAL FOR THE FIRE RATED WINDOW AND IMPACT
 PROTECTION, FAC9B72.
  
 10. A1, PLEASE REVISE OCCUPANT LOAD, TAKING INTO
 ACCOUNT CONFERENCE ROOM AREA, SEE FBC TABLE 1004.1.1.
  
 11. THE FILE STORAGE/IT AREA IS NOTED AS A FIRE PROOF
 AREA, BUT FIRE RESISTANCE IS NOT SPECIFIED ON THE PLAN,
 SEE A1, WALL SYMBOLS. SEE OTHER COMMENTS REGARDING
 OCCUPANCY CLASSIFICATION AND REQUIRED SEPARATIONS. SHOW
 ALL REQUIRED FIRE RATINGS ON THE PLAN, BOTH HORIZONTAL
 AND VERTICAL, FBC 7.
  
 12. SHOW MANEUVERING CLEARANCE, PULL SIDE, ON THE
 FOLLOWING DOORS PER FBC FIGURE 11-25:
  
 EXEC. OFFICE 10, SOUTHEAST CORNER
 CEO OFFICE 5, NORTH DOOR
  
 13. TR 5, CEO OFFICE 5, IS TO BE ADAPTABLE,
 FBC11-4.1.3(11). SHOW BLOCKING FOR FUTURE GRAB BARS,
 TURNING RADIUS.
  
 14. JANITOR'S CLOSET SHALL BE CONSTRUCTED SO THAT
 EMPLOYEES WITH DISABILITIES CAN APPROACH, ENTER, AND
 EXIT THE AREA FBC11-4.1(3).
  
 15. STAIRS, SHOW PROTECTION FROM OVERHEAD HAZARDS, FBC
 FIGURE 11-8 (C1).
  
 16. PROVIDE A DETAIL FOR THE ACCESSIBLE PARKING SPACE,
 INCLUDING ACCESS AISLE. PLEASE INCLUDE SLOPE AND CROSS
 SLOPE. FBC FIGURE 11-10.
  
 17. TR2, 2ND FLOOR, CLEAR FLOOR SPACE FOR THE LAV
 CANNOT ENCROACH INTO THE REQUIRED CLEAR FLOOR SPACE FOR
 THE WATER CLOSET. FBC FIGURE 11-30E.
  
 18. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED
 FOR THE ROOF HATCH, FAC9B72. SEE ALSO DCA DECLARATORY
 STATEMENT CONFIRMING THIS REQUIREMENT. THIS MAY BE A
 PROVISO ITEM UPON REQUEST BUT MUST BE PROVIDED PRIOR TO
 INSTALLATION.
  
 19. A3 SHOWS A BACKUP GENERATOR ON THE ROOF, S103 DOES
 NOT APPEAR TO INCLUDE THE GENERATOR. PLEASE ADDRES,
 FBC16.
  
 20. FBC13-103.1.1.1, DESIGN PROFESSIONALS RESPONSIBLE
 UNDER FLORIDA LAW FOR THE DESIGN OF THE BUILDING SHELL,
 SHALL CERTIFY COMPLIANCE OF THOSE BUILDING SYSTEMS WITH
 THE CODE BY SIGNING AND PROVIDING THEIR PROFESSIONAL
 REGISTRATION NUMBER ON THE ENERGY CODE FORM PROVIDED AS
 PART OF THE PLANS AND SPECIFICATIONS TO THE BUILDING
 DEPARTMENT.
  
 21. FOR THE MODIFIED ROOF SYSTEM, PLEASE INDICATE WHICH
 APPROVED ASSEMBLY WILL BE INSTALLED, FASTENER SELECTED,
 AND ENHANCED FASTENING SPECIFICATION IN ACCORDANCE WITH
 RAS117 (PREPARED BY AN ARCHITECT, ENGINEER, OR
 REGISTERED ROOF CONSULTANT); SEE GENERAL LIMITATION #7
 ON THE NOA. THIS CAN BE A PROVISO ITEM, TO BE PROVIDED
 AT TIME OF ROOF PERMIT SUBMITTAL.
  
 22. FOR THE ROOF TILE, PLEASE INDICATE METHOD OF
 ATTACHMENT. IF FOAM ADHESIVE IS PROPOSED, PLEASE
 PROVIDE PRODUCT APPROVAL FAC9B72. THIS CAN BE A PROVISO
 ITEM, TO BE PROVIDED AT TIME OF ROOF PERMIT SUBMITTAL.
  
 23. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS
 FS471. PLEASE SUBMIT TWO ORIGINAL SOILS REPORTS.
  
 24. ENERGY CALC SHOWS A BUILT UP ROOF, R19. PLEASE
 PROVIDE CLARIFICATION. A3 SHOWS 2" INSULATION BOARD;
 PROVIDE SPEC SHEETS FOR THE INSULATION TO SHOW THAT IT
 MEETS THE MINIMUM R19 REQUIREMENT.
  