Plan Review Notes For Permit 09060089 |
Permit Number |
09060089 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2009-06-25 19:16:02 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2007 | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | FROM PREVIOUS LIST: | | | | 2. ACCORDION SHUTTERS, TOP CONNECTION, 10" SPACING | | SPECIFIED BUT THIS IS FOR 60PSF (9" REQUIRED FOR | | PRESSURE GREATER THAN 60PSF). | | | | ANCHOR SPACING REVISED TO STATE "NA". THIS INFORMATION | | IS REQUIRED. | | | | NEW COMMENT: | | | | 1ST INSTALL SCHEDULE ANCHOR SPACING FOR CLEAR PANELS | | WAS BLANK. NOW IT STATES 6". -59PSF REQUIRES USE OF | | 120MPH ROW (CANNOT USE -54, TOO LOW), BUT 47 HAS BEEN | | HIGHLIGHTED. 120 PSF REQUIRES 3.7" SPACING. | | | | SHUTTER MOUNTING CONNECTION TYPE STATES "NA;" THIS | | SHOULD SPECIFY ANCHOR DETAIL CORRELATING WITH ANCHOR | | CHARTS. IT APPEARS YOU ARE USING C2. | | | | IF YOU NEED ASSISTANCE WITH THE FORM, PLEASE HAVE THE | | QUALIFIER CONTACT ME TO SCHEDULE A MEETING. |
|