Plan Review Notes
Plan Review Notes For Permit 09060089
Permit Number 09060089
Review Stop B
Sequence Number 2
Notes
Date Text
2009-06-25 19:16:02****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 FROM PREVIOUS LIST:
  
 2. ACCORDION SHUTTERS, TOP CONNECTION, 10" SPACING
 SPECIFIED BUT THIS IS FOR 60PSF (9" REQUIRED FOR
 PRESSURE GREATER THAN 60PSF).
  
 ANCHOR SPACING REVISED TO STATE "NA". THIS INFORMATION
 IS REQUIRED.
  
 NEW COMMENT:
  
 1ST INSTALL SCHEDULE ANCHOR SPACING FOR CLEAR PANELS
 WAS BLANK. NOW IT STATES 6". -59PSF REQUIRES USE OF
 120MPH ROW (CANNOT USE -54, TOO LOW), BUT 47 HAS BEEN
 HIGHLIGHTED. 120 PSF REQUIRES 3.7" SPACING.
  
 SHUTTER MOUNTING CONNECTION TYPE STATES "NA;" THIS
 SHOULD SPECIFY ANCHOR DETAIL CORRELATING WITH ANCHOR
 CHARTS. IT APPEARS YOU ARE USING C2.
  
 IF YOU NEED ASSISTANCE WITH THE FORM, PLEASE HAVE THE
 QUALIFIER CONTACT ME TO SCHEDULE A MEETING.