Plan Review Notes For Permit 09060089 |
Permit Number |
09060089 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-06-10 08:41:51 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2007 | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | 1. COMPLETE THE SAMPLE INSTALLATION SCHEDULE OR PROVIDE | | ALL INFORMATION TO SHOW CODE COMPLIANCE IN ANOTHER | | FORMAT, FBC*106, FBC R301, FBC1609. TWO SETS REQUIRED. | | THIS FORM IS AVAILABLE IN THE LOBBY OR ON THE INTERNET | | AT | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_ | | INSTALLATION.PDF | | | | THE ANCHOR SPACING FOR CLEAR PANELS STATES "NA"; THIS | | INFORMATION IS REQUIRED. | | | | 2. ACCORDION SHUTTERS, TOP CONNECTION, 10" SPACING | | SPECIFIED BUT THIS IS FOR 60PSF (9" REQUIRED FOR | | PRESSURE GREATER THAN 60PSF). | | | | 3. PLEASE CLARIFY EDGE DISTANCE. FOR INSTANCE, OPENING | | 18 STATES 3", BUT IF THE SUBSTRATE IS WOOD, 3" EDGE | | DISTANCE WOULD NOT ALLOW THE ANCHOR TO MEET THE MINIMUM | | EMBEDMENT REQUIREMENT. UNLESS PLYWOOD SUBSTRATE IS | | ALLOWED FOR THE SPECIFIED SHUTTER CONNECTION MOUNTING | | TYPE, 3/4" EDGE DISTANCE IS REQUIRED. | | | | | | |
|