2009-06-19 08:07:22 | |
| ** DENIED PLANS * |
| |
| 1) NOTE: THE VALUE FOR THE COMPLETE SCOPE OF WORK |
| INCLUDING DESIGN COST, LABOR MATERIALS ETC EVEN IF ANY |
| OF THESE ARE OWNER SUPPLIED SHALL BE INCLUDED. THE |
| VALUE ON APPLICATION IS LOW PER MINIMUM PER SQ FT COST |
| PER ICC TABLES. THIS IS ALSO A PROJECT WHICH HAS |
| ALREADY BEEN BUILT. 4X FEE HAS BEEN ADDED AND FEE WILL |
| INCREASE ONCE VALUE PER ICC TABLES HAVE BEEN ASSESSED. |
| FBC 108.3 |
| |
| 2) NOTE: SERVICE ENTRANCE CONDUCTORS DO NOT MEET |
| MINIMUM REQUIRED FOR SERVICER SHOWN. RISER SHOWS #2 |
| WITH A 200AMP MAIN AND A 60AMP MAIN. THE LOAD |
| CALCULATIONS ALONE EXCEED THE RATINGS. |
| PLEASE INCREASE SERVICE, METER CAN ETC. |
| 90.7,90.8,110.3,310.16,310.15B6, 220.87, 240.4 ETC |
| ** PLEASE ALSO EXPLAIN WHY THE LOAD CALCULATIONS STATE |
| LOAD FOR PANELS B AND C WHEN THERE IS ONLY A PANEL A |
| AND B IDENTIFIED. |
| |
| 3) NOTE: PLEASE SHOW THE NEW MAIN AIC RATINGS PER 110.9 |
| |
| 4) NOTE: PLEASE INCLUDE THE GROUNDING ELECTRODE SYSTEM |
| REQUIRED AT THE DETACHED STRUCTURE PER 250.50,250.32 |
| |
| 5) NOTE: PLEASE INCLUDE THE MEANS OF DISCONNECT PER |
| 225.31-225.39. |
| |
| 6) NOTE: PLEASE SHOW LOCATION OF SERVICE EQUIPMENT ON |
| PLANS ALONG WITH THE SERVICE EQUIPMENT ON THE DETACHED |
| STRUCTURE. |
| 240.24,110.26 |
| |
| 7) NOTE: PLANS NEED TO SHOW COMPLIANCE WITH 210.8A2 |
| |
| ** THIS APPEARS TO BE A BUILDING BEING SET UP FOR |
| LIVING AREA. PLEASE KNOW A HOLD WILL BE PLACED ON PCN |
| FOR NO LIVING SPACE AND SUBJECT TO FURTHER INSPECTIONS. |
| THIS IS THE THIRD BUILDING BEING CONSTRUCTED BY THIS |
| CONTRACTOR AS *AS-BUILT* FOR THIS SAME PURPOSE. |
| |
| |
| |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |