2009-07-13 10:35:18RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW CHECKLIST.
 2007 FL. RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 N1100.0 OF 2007 FLORIDA RESIDENTIAL CODE.
 NOTE: MAKE SURE ALL INFORMATION IS PROVIDED AND ALL
 SIGNATURES ARE PROVIDED.
  
 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. UPDATE VALUE TO INCLUDE ALL MATERIALS, LABOR,
 OVERHEAD AND PROFIT AND ALL PROFESSIONAL FEES AS
 REQUIRED BY SEC. 108.3 CITY AMENDMENTS TO FBC.
  
 3- PROVIDE PRODUCT APPROVALS AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) FLAT ROOF. AND, CLEARLY MARK SPECIFIC APPROVED
 ASSEMBLY AND BASE SHEET FASTENING OPTION. PROVIDE RAS
 117 CALCULATIONS FOR NAIL ENHANCING AT PERIMETER AND
 CORNER AREAS. IF PRODUCT APPROVAL SUBMITTED REQUIRES
 CALCULATIONS TO BE SIGNED AND SEALED, THEN PROVIDE
 SIGNED AND SEALED CALCULATIONS.
 NOTE: ACCORDING TO 2009 REVISIONS TO THE 2007 FLORIDA
 RESIDENTIAL CODE, THIS BUILDING IS LOCATED ON EXPOSURE
 "C". HAVE THIS IN CONSIDERATION WHEN PROVIDING THE RAS
 117 CALCULATIONS.
  
 B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. PROVIDE ONLY THE PRODUCT APPROVAL COVER
 PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR.
  
 C) SHUTTERS FOR WINDOWS. AND PROVIDE COMPLETE
 INSTALLATION SCHEDULE AND CLEARLY MARK SPECIFIC ANCHOR
 TYPE AND SPACING TO BE USED.
  
 4- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC.
  
 5- ACCORDING TO 2009 REVISIONS TO THE 2007 FLORIDA
 RESIDENTIAL CODE, THIS BUILDING IS LOCATED ON EXPOSURE
 "C", NOT "B". REVISE PLANS DESIGN CRITERIA AND WINDOWS/
 DOORS DESIGN PRESSURES AS REQUIRED.
  
 6- INFORMATION ON ARCHITECT'S LETTER PROVIDED DOESN'T
 MATCH INFORMATION SHOWN ON PLANS. REVISE AS REQUIRED TO
 MATCH.
 NOTE: LETTER IS NOT REQUIRED. PLANS SHALL BE OF
 SUFFICIENT CLARITY TO PROVIDE ALL THE INFORMATION.
  
 7- PLANS TO SHOW MINIMUM STUCCO THICKNESS AS REQUIRED
 BY TABLE R702.1(1) OF 2007 FLORIDA RESIDENTIAL CODE.
  
 8- PLANS TO SPECIFY TWO LAYERS OF WATER RESISTANT
 BARRIERS AS REQUIRED BY SEC. R703.6.3 OF 2007 FLORIDA
 RESIDENTIAL CODE FOR STUCCO ON FRAMED CONSTRUCTION.
  
 9- WALLS SECTION SPECIFIES T-111 WHILE ELEVATIONS
 SPECIFY STUCCO FINISH. CLARIFY AS REQUIRED TO MATCH.
  
 10- PROVIDE ROOF CROSS VENTILATION AS REQUIRED BY SEC.
 R806.1 OF 2007 FLORIDA RESIDENTIAL CODE. VENTILATION
 SPECIFIED ON WALL SECTION DOESN'T PROVIDE CROSS
 VENTILATION. REVISE AS REQUIRED.
  
 11- SPECIFY HOW LONG ARE THE 1/2" ANCHORS BOLTS
 SPECIFIED ON WALL SECTION TO VERIFY COMPLIANCE WITH
 UPLIFT LOADS OF SEC. R301 OF 2007 FLORIDA RESIDENTIAL
 CODE.
  
 12- REVISE ROOF SHEATHING SPECIFICATIONS SHOWN ON WALL
 SECTION TO COMPLY WITH SEC. R803.2.3.1 OF 2007 FLORIDA
 RESIDENTIAL CODE. NEED TO SPECIFY RING SHANK NAILS IN
 ALL ZONES.
  
 13- WALL SECTION IS MISSING SPECIFICATIONS FOR WALL
 INSULATION.
 NOTE: COORDINATE WITH THE ENERGY CALCULATIONS.
  
 14- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED
 BY SEC. 713.13 FLORIDA STATUTE.
  
 15- SURVEY SUBMITTED NEEDS SURVEYOR'S ORIGINAL
 SIGNATURE (NOT COPY OR RUBBER STAMP SIGNATURE) AS
 REQUIRED BY CHAPTER 472 FLORIDA STATUTE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712