2009-06-10 16:46:07 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2007 | | FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING | | CODE | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007 | | FAC FLORIDA ADMINISTRATIVE CODE | | FS FLORIDA STATUTE | | | | 1. FBC3202.3.1, PROVIDE A SITE PLAN AND SHOW AWNING IN | | RELATION TO PROPERTY LINE AND SIDEWALK. | | | | FOR YOUR CONVENIENCE: | | | | 3202.3 ENCROACHMENTS 8 FEET OR MORE ABOVE GRADE. | | ENCROACHMENTS 8 FEET (2438 MM) OR MORE ABOVE GRADE | | SHALL COMPLY WITH SECTIONS 3202.3.1 THROUGH 3202.3.4. | | | | 3202.3.1 AWNINGS, CANOPIES, MARQUEES AND SIGNS. | | AWNINGS, CANOPIES, MARQUEES AND SIGNS SHALL BE | | CONSTRUCTED SO AS TO SUPPORT APPLICABLE LOADS AS | | SPECIFIED IN CHAPTER 16. AWNINGS, CANOPIES, MARQUEES | | AND SIGNS WITH LESS THAN 15 FEET (4572 MM) CLEARANCE | | ABOVE THE SIDEWALK SHALL NOT EXTEND INTO OR OCCUPY MORE | | THAN TWO-THIRDS THE WIDTH OF THE SIDEWALK MEASURED FROM | | THE BUILDING. STANCHIONS OR COLUMNS THAT SUPPORT | | AWNINGS, CANOPIES, MARQUEES AND SIGNS SHALL BE LOCATED | | NOT LESS THAN 2 FEET (610 MM) IN FROM THE CURB LINE. | | | | |
|