Plan Review Notes
Plan Review Notes For Permit 09060076
Permit Number 09060076
Review Stop E
Sequence Number 2
Notes
Date Text
2009-10-10 08:14:49** DENIED**
  
 1) NOTE: NEW LIGHTING AND EXISTING LIGHTING APPEAR TO
 MEET REQUIRED MINIMUMS HOWEVER NEW LIGHTING DOES NOT
 INDICATE HOW OR WHERE THESE WILL BE CONTROLLED?
 FBC 13-415.AB.1.1,.1.2
 NO CIRCUITING ON PLANS TO SHOW WHERE LIGHTS WOULD BE
 FED. SEE 700.12F FOR UNIT EMERGENCY LIGHT FIXTURES TO
 LOCAL LIGHTING BRANCH CIRCUIT.
  
 ** THE ABOVE COULD HAVE BEEN A PROVISO HOWEVER AS THERE
 ARE STILL BUILDING REVIEW COMMENTS THIS SHEET COULD NOT
 BE STAMPED OR GIVEN A PROVISO AT THIS TIME.
  