2009-06-18 14:19:19 | |
| ** DENIED PLANS * |
| |
| 1) NOTE: THE ELECTRICAL PLANS NEED TO STATE THE |
| FOLLOWING MINIMUM CODES. |
| PLEASE BE SURE THE FOLLOWING ARE STATED ON ELECTRICAL |
| PLANS. |
| 2007 FBC W/ 2009 AMENDMENTS. |
| 2006 NFPA-101 |
| 2002 NFPA-72 |
| 2006 NFPA-1 |
| 2005 NFPA-70 |
| |
| PER: FBC CHAPTER 35, FS 553.73, FAC 69A-60.004, .003 |
| |
| |
| 2) NOTE: PLEASE SEE 13-415.AB.5 AND 13-415.AB.5.1 FOR |
| LIGHTING PERFORMANCE CALCULATIONS. |
| |
| 3) NOTE: PLEASE INCLUDE ALL DEVICE LOCATIONS, HEIGHTS, |
| AND MINIMUM LEVELS PER FBC 11-4.28.1,.2 AND .3. ONLY IF |
| THERE IS FIRE ALARM PANEL AND/OR ANY DEVICES TO BE |
| INSTALLED. |
| |
| 4) NOTE: PLEASE PROVIDE LIGHTING FOR NORMAL AND |
| EMERGENCY EGRESS FOR STAIRS. SHOW NEW OR EXISTING TO |
| MEET NFPA- 101 2006, 7.8.1.3, 7.9.1.2, .2.2 |
| FAC 61G15-33.004 |
| |
| 5) NOTE: NEW LIGHTING CONTROLS SHALL MEET PRESCRIPTIVE |
| 13-415.AB.1.1,.1.2, .1.3 |
| |
| 6) NOTE: VALUE FOR SCOPE OF WORK SHALL BE APPLICABLE TO |
| SCOPE. THE PREVIOUS PERMIT FOR THIS SCOPE WHICH WAS |
| NEVER ISSUED WAS SUBSTANTIALLY HIGHER. PLEASE SEE FBC |
| 108.3 AS ADOPTED FOR VALUATION SHALL INCLUDE ALL LABOR, |
| MATERIALS, DESIGN COST AND EQUIPMENT WHETHER OR NOT ANY |
| OF THESE ARE OWNER SUPPLIED. |
| |
| 7) NOTE: PLEASE PROVIDE LICENSING FOR KC HUBBARD AND |
| ASSOCIATES. * DESIGNERS NOT LICENSED UNDER FS 481 OR |
| 471 ARE NOT PERMITTED TO DESIGN COMMERCIAL WORK PER |
| 481.229. |
| THIS HAS BEEN CONFIRMED WITH THE PROSECUTING ATTORNEY |
| FOR THE FLORIDA BOARD OF ARCHITECTS. PLANS MAY BE |
| RETAINED. |
| |
| |
| |
| |
| |
| |
| ** IMPORTANT ** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |