2009-06-19 16:26:31 | BUILDING PLAN REVIEW |
| PERMIT: 09060076 |
| ADD: 1335 OKEECHOBEE RD SUITE# 1000 |
| CONT: ATLANTIC GENERAL CONTRACTING |
| TEL: (561)434-4171 |
| |
| FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| W/ 2009 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER |
| MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC |
| BUILDING WITH 2009 SUPPLEMENTS. PLEASE UPDATE PLANS TO |
| ALSO INCLUDE THE 2007 EXISTING BUILDING CODE, CHAPTER |
| 10 ADDITIONS (MEZZANINE ADDING FUEL LOADS) . |
| |
| 2) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION |
| THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE |
| OF OCCUPANCY: |
| A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS |
| DESIGNED. |
| 2007 FL BUILDING CODE, EXISTING BUILDING, ADDING A |
| MEZANINE CONSTITUTES AN ADDITION SEE ASSOCIATED |
| CHAPTERFOR ADDITIONS. |
| B) THE TYPE OF CONSTRUCTION (FOR THE EXISTING BUILDING) |
| AS DEFINED IN CHAPTER 5, TABLE 503, CHAPTER 6, TABLE |
| 601. |
| C) PLANS INDICATE THERE IS A FIRE SPRINKLER SYSTEM, IS |
| IT A REQUIRED SYSTEM FOR AREA INCREASES IN THE |
| BUILDING? |
| D) PLANS INDICATE THE OCCUPANCY TYPE TO BE A STORAGE |
| OCCUPANCY, S1 OR S2? |
| |
| 3) THE PLAN INDICATES THE MEZZANINE LEVEL OCCUPANCY |
| SHALL BE USED FOR STORAGE. |
| |
| 3A) 110.4.2 STORAGE & FACTORY- INDUSTRIAL OCCUPANCIES. |
| IT SHALL BE THE RESPONSIBILITY OF THE OWNER, AGENT, |
| PROPIETOR OR OCCUPANT OF GROUP S AND GROUP F |
| OCCUPANCIES, OR ANY OCCUPANCY WHERE EXCESSIVE FLOOR |
| LOADING IS LIKELY TO OCCUR, TO EMPLOY A COMPETENT |
| ARCHITECT OR ENGINEER IN COMPUTING THE SAFE FLOOR LOAD |
| CAPACITY. ALL SUCH COMPUTATIONS SHALL BE ACCOMPANIED BY |
| AN AFFADAVIT FROM THE ARCHITECT OR ENGINEER STATING THE |
| SAFE ALLOWABLE FLOOR LOADS ON EACH FLOOR IN POUNDS PER |
| SQ FT.THE |
| COMPUTATIONS & AFFADAVIT SHALL BE FILED AS A PERMANENT |
| RECORD OF THE BLDG DEPT. |
| |
| 3B) 110.4.3.SIGNS REQUIRED. IN EVERY BUILDING OR PART |
| OF A BUILDING USED FOR STORAGE, INDUSTRIAL OR HAZARDOUS |
| PURPOSES, THE SAFE FLOOR LOADS, AS REVIEWED BY THE |
| BUILDING OFFICIAL ON THE PLAN, SHALL BE MARKED ON |
| PLATES OF APPROVED DE SIGN WHICH SHALL BE SUPPLIED & |
| SECURELY AFFIXED BY THE OWNER OF THE BUILDING IN A |
| CONSPICUOUS PLACE IN EACH STORY TO WHICH THEY RELATE. |
| SUCH PLATES SHALL NOT BE REMOVED OR DEFACED, & IF LOST, |
| REMOVED THE OWNER OF THE BUILDING SHALL REPLACE THEM. |
| |
| 4) NO PLANS WERE SUBMITTED FOR THE STRUCTURAL FRAMING |
| OF THE MEZANINE NOR STAIRWAY OR FOR LOADING OF THE |
| MEZZANINE LEVEL. |
| 106.3.5 MINIUMUM PLAN CRITERIA FOR COMMERCIAL |
| BUILDINGS. |
| NOT HAVING BUILDING INFORMATION TYPE , FIRE RETARDANT |
| CONSTRUCTION MAY ALSO BE A FACTOR WITH A PLYWOOD FLOOR. |
| |
| 5) PLANS INDICATE THE BUILDING HAS FIRE SPRINKLER |
| SYSTEM ALREADY BUT NO PLANS WERE SUBMITTED FOR FIRE |
| SPRINKLERS BENEATH THE MEZZANINE LEVEL. |
| |
| 6) GUARD RAILS, PLEASE PROVIDE COMPLIANCE WITH: |
| 618.4.6.1 RAILINGS, STAIR-RAILINGS AND OTHER SIMILAR |
| SAFEGUARDS SHALL BE DESIGNED TO RESIST A LOAD OF 50 |
| POUNDS PER LINEAL FOOT (74 KG/M) OR A CONCENTRATED LOAD |
| OF 200 POUNDS (690 N) APPLIED IN ANY DIRECTION AT THE |
| TOP OF SUCH BARRIERS AT ANY LOCATION ON THE SAFEGUARD, |
| WHICHEVER CONDITION PRODUCES THE MAXIMUM STRESSES. THE |
| REACTIONS AND STRESSES CAUSED BY THE ABOVE REFERENCED |
| UNIFORM AND CONCENTRATED LOADS SHALL BE CONSIDERED NOT |
| BE ACTING SIMULTANEOUSLY. |
| |
| 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| NOTE: A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, |
| AS A RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| ON REQUESTED ADDITIONAL COMMENTS MAY APPEAR THAT WERE |
| NOT PART OF THIS REVIEW. |
| |
| JIM WITMER C. B. O. |
| BUILDING PLAN REVIEW II |
| |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| E-MAIL: [email protected] |
| |