2009-06-03 11:12:12 | BUILDING PLAN REVIEW |
| PERMIT: 09060067 |
| ADD: 6882 N JOG RD |
| CONT:WEST CONSTRUCTION |
| TEL: (561)248-3868 |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 08090593 6880 N. JOG RD. OFFICE BUILDING TYPE II-B |
| 5,600 SQ FT |
| 6890 N. JOG RD. S-2 MAINTENANCE BUILDING TYPE II-B |
| 1,200 SQ FT |
| 6882 N JOG RD. PAVILION TYPE II-B 685 SQ FT. |
| |
| THE BUILDING OFFICIAL HAS REQUESTED THAT 3 SEPERATE |
| PERMIT APPLICATIONS WITH SEPERATE TRACKING NUMBERS AND |
| ADDREESSES BE ASIGNED TO ALLOW FOR THE MULTIPLE |
| INSPECTIONS THAT WILL BE REQUIRED FOR EACH BUILDING, |
| AND SEPERATE TRACKING OF INSPECTIONS. |
| |
| THE TWO SETS OF PLANS AND BACK UP DOCUMENTATION WILL BE |
| ALL THAT IS NEEDED, THE (MASTER 08090593)) PERMIT |
| NUMBER WILL HAVE ALL THE REVIEW DOCUMENTATION. |
| |
| 1) , 1ST UNDER PERMIT APPLICATION. THE RESPONSE |
| COMMENTS INDICATE THIS TO BE A PAVILION, TO BE PART OF |
| THIS PERMIT WE DO NEED INFORMATION AS FAR AS COMPONENTS |
| AND CLADDING YOU INDICATE THIS IS A PRE-ENGINEERED |
| CANOPY, EITHER IT HAS GONE THROUGH THE MANUFACTURED |
| BUILDING PROGRAM WITH THE STATE AND IS APPROVED AS A |
| MANUFACTURED MODULAR BUILDING PROGRAM WITH STATE |
| APPROVED PLANS OR IT WILL NEED PRODUCT APPROVALS FOR |
| THE ROOFING ASSEMBLY. WITHOUT PLANS THIS AREA WILL BE |
| EXEMPTED FROM THE PERMIT AND PLANS TO BE SUBMITTED |
| UNDER A SEPERATE PERMIT. |
| 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| YOUR RESPONCE AS TO SECTION 503.1.1 DEALS WITH SQUARE |
| FOOTAGE OF FIRE AREA AND THERE NOT BEING REQUIREMENTS |
| FOR RATED WALLS BEING BUILDINGS AND OPENING |
| PROTECTIVES. ONE ISSUE THAT WE HAVE IS WITH NO PLANS, |
| NO STRUCTURAL COLUMNS, BEAMS NOR ROOF SHEATHING IS |
| PROVIDED. THE ROOFING PRODUCT APPROVAL SUBMITTED 2004 |
| FL 3778-R1 |
| IS FOR NON-STRUCTURAL ROOF METAL, REQUIRING |
| SUBSHEATHING DECK. 1507.4.1. |
| |
| 2) SHEET S-4 INDICATES A FOOTING TYPE A BUT THE PLANS |
| ARE LACKING COLUMN AND BEAM INFORMATION, 1609.2.1 PART |
| OFTHE MAIN WIND FORCE-RESISTING SYSTEM. PLEASE PROVIDE |
| ADDITONAL INFORMATION, 106.1..2. 106.3.5 MINIMUM PLAN |
| REVIEW CRITERIA FOR BUILDINGS. |
| |
| 3) SHEET A-4 ALSO INDICATES THE ROOFING ASSEMBLY TO BE |
| A PREMANUFACTRED CANOPY, PLEASE PROVIDE PRODUCT |
| INFORMATION, TO BE PART OF THIS PERMIT WE DO NEED |
| INFORMATION AS FAR AS COMPONENTS AND CLADDING YOU |
| INDICATE THIS IS A PRE-ENGINEERED CANOPY, EITHER IT HAS |
| GONE THROUGH THE MANUFACTURED BUILDING PROGRAM WITH THE |
| STATE AND IS APPROVED AS A MANUFACTURED MODULAR |
| BUILDING PROGRAM WITH STATE APPROVED PLANS OR IT WILL |
| NEED PRODUCT APPROVALS FOR THE ROOFING ASSEMBLY. |
| WITHOUT PLANS THIS AREA WILL BE EXEMPTED FROM THE |
| PERMIT AND PLANS TO BE SUBMITTED UNDER A SEPERATE |
| PERMIT. 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR |
| BUILDINGS. |
| |
| INFORMATIONAL: GENERATOR PAD IS SHOWN ON SHEET SD-1, IS |
| THIS PAD AND GENERATOR AND ATTACHMENT TO SLAB WILL BE |
| REVIEWED UNDER A SEPERATE PERMIT. 1609.1.3 ANCHORAGE |
| AGAINST OVERTURNING, UPLIFT AND SLIDDING. ANCHORAGE |
| AGAINST OVERTURNING IS NOT THE RESPONSIBILITY OF THE |
| GENERATOR MANUFACTURER BUT THE DESIGNER OF RECORD. |
| |
| |
| JIM WITMER C. B. O. |
| BUILDING PLAN REVIEW II |
| |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| E-MAIL: [email protected] |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| |
| |