Plan Review Notes For Permit 09060054 |
Permit Number |
09060054 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-06-17 12:08:14 | ** DENIED PLANS * | | | | 1) NOTE: PLEASE SEE ASTME-17 2004 FOR ELEVATOR, | | EQUIPMENT ROOMS, SILLS AND COMMON AREAS. THIS IS NOTED | | ONLY FOR INFORMATION AS THERE ARE SOME ITEMS WHICH MAY | | COME UP AT THE END OF THE JOB BY THE ELEVATOR | | INSPECTOR. THE LOCAL AHJ DOES NOT REVIEW FOR CODE | | COMPLIANCE BASED ON THE ASTME-17. | | *** THERE ARE SOME ITEMS WHICH ARE KNOWN WHICH WOULD | | NEED TO BE ADDRESSED. | | | | 2) NOTE: PLEASE PROVIDE MORE INFORMATION ON THE TIME | | CURVES FROM THE COORDINATION STUDY. ON SHEET E1 THERE | | IS AN OVER LAP FROM ELEVATOR MAIN AND ELEVATOR | | CONTROLLER. | | IS THIS ELEVATOR PART OF THE LIFE SAFETY REQUIRED OR | | LEGALLY REQUIRED ELEVATORS? | | 240.12, 700.27, 701.18 | | | | 3) NOTE: PLEASE SHOW ALL LIGHTING, CIRCUITING IN | | ELEVATOR ROOMS. 6200.22,23,24 ETC | | ** PLEASE KEEP IN MIND COMMENT #1 ABOVE AS THE LIGHTING | | LEVELS AND OTHER REQUIREMENTS WILL NEED TO BE MET. | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|