Date Text
2009-06-17 12:08:14** DENIED PLANS *
  
 1) NOTE: PLEASE SEE ASTME-17 2004 FOR ELEVATOR,
 EQUIPMENT ROOMS, SILLS AND COMMON AREAS. THIS IS NOTED
 ONLY FOR INFORMATION AS THERE ARE SOME ITEMS WHICH MAY
 COME UP AT THE END OF THE JOB BY THE ELEVATOR
 INSPECTOR. THE LOCAL AHJ DOES NOT REVIEW FOR CODE
 COMPLIANCE BASED ON THE ASTME-17.
 *** THERE ARE SOME ITEMS WHICH ARE KNOWN WHICH WOULD
 NEED TO BE ADDRESSED.
  
 2) NOTE: PLEASE PROVIDE MORE INFORMATION ON THE TIME
 CURVES FROM THE COORDINATION STUDY. ON SHEET E1 THERE
 IS AN OVER LAP FROM ELEVATOR MAIN AND ELEVATOR
 CONTROLLER.
 IS THIS ELEVATOR PART OF THE LIFE SAFETY REQUIRED OR
 LEGALLY REQUIRED ELEVATORS?
 240.12, 700.27, 701.18
  
 3) NOTE: PLEASE SHOW ALL LIGHTING, CIRCUITING IN
 ELEVATOR ROOMS. 6200.22,23,24 ETC
 ** PLEASE KEEP IN MIND COMMENT #1 ABOVE AS THE LIGHTING
 LEVELS AND OTHER REQUIREMENTS WILL NEED TO BE MET.
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  