Plan Review Notes
Plan Review Notes For Permit 09060052
Permit Number 09060052
Review Stop B
Sequence Number 1
Notes
Date Text
2009-06-03 10:30:07RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST.
 REVIEW UNDER 2007 FLORIDA RESIDENTIAL CODE.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK UP.
  
 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. PERMIT VALUATION WAS UPDATED AS REQUIRED BY SEC.
 108.3 CITY AMENDMENTS TO FBC.
 THEREFORE, OWES $135.78.
  
 3- THERE ARE TWO DIFFERENT PRODUCT APPROVALS SUBMITTED
 FOR ROOF SHINGLES. NOA 05-1115.08 SUBMITTED EXPIRED ON
 04/22/08. AND NOA 07-1120.14 SUBMITTED WAS SUPERSEDED
 BY MIAMI-DADE COUNTY. SEE ATTACHED COPY FROM MIAMI DADE
 COUNTY WEBSITE. NEED TO PROVIDE TWO COPIES OF CURRENT
 SHINGLES PRODUCT APPROVAL.
  
 4- COMMENTS TO FLAT ROOF NOA 09-0224.01 SUBMITTED:
 A) MARK WHICH APPROVED ASSEMBLY IS GOING TO BE
 INSTALLED.
  
 B) MARK WHICH BASE SHEET FASTENING OPTION IS GOING TO
 BE INSTALLED.
  
 C) PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL
 LIMITATION #7.
 NOTE: ASSEMBLIES WITH GENERAL LIMITATION #9 CAN'T BE
 USED IN THIS AREA.
  
 D) ACCORDING TO GENERAL LIMITATION #7 ON SHEET #31 OF
 NOA SUBMITTED, THE RAS 117 CALCULATIONS NEED TO BE
 SIGNED AND SEALED BY THE DESIGN PROFESSIONAL. PROVIDE
 SIGNED AND SEALED CALCULATIONS.
  
 E) CLARIFY WHY THIS NOA WAS REVIEWED AND APPROVED BY
 THE ENGINEER LUIS LOPEZ.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712