Plan Review Notes
Plan Review Notes For Permit 09060005
Permit Number 09060005
Review Stop E
Sequence Number 2
Notes
Date Text
2009-07-04 12:10:18 
 ** DENIED PLANS 2ND REVIEW **
 SOME NOTES FROM PREVIOUS REVIEW STILL NOT ADDRESSED.
 SOME NEW NOTES BASED ON SOME INFORMATION SHOWN NOT ON
 PREVIOUS PLANS.
 AS STATED ON PREVIOUS REVIEW, IF THERE ARE QUESTIONS OR
 COMMENTS OR IF THERE ARE ANY NOTES NOT TYPED IN A CLEAR
 MANNER PLEASE CALL. NO CONTACT WAS MADE FROM LAST
 REVIEW AND IT APPEARS PERHAPS SOME NOTES WERE NOT
 UNDERSTOOD.
  
 1) NOTE: AS THE SCALE IS VERY SMALL AND THERE IS A LOT
 OF ITEMS SHOWN ON PLANS. AS STATED ON PREVIOUS REVIEW
 PLANS ARE CONGESTED. CIRCUITING IS NOT CLEAR. SOME
 ITEMS STILL DO NOT INDICATE CIRCUITING. SEE REDLINED
 PLANS. OTHERS SUCH AS CIRCUIT 2A, 9B, 7B AND 12A ARE
 STATED AS GENERAL LIGHTING. PLEASE SEE COMMENTARY FROM
 THE 2005 NEC IN 408.4. THESE NEED TO BE SPECIFIC TO
 ROOMS AND AREAS IN WHICH THEY FEED. LIVING ROOM
 LTS/RECEPTS, KITCHEN LIGHTS ETC OR OTHER DESIGNATION.
 408.4, 210.52, 210.11 ETC
  
 2) NOTE: MINIMUM OF TWO SMALL APPLIANCE CIRCUITS IS
 REQUIRED PER 210.52B1, 210.11C1, 220.53. LIGHTING
 CIRCUIT 7B IS SHOWN CONNECTED TO RECEPTACLE IN ONE AREA
 WHICH IS NOT PERMITTED.
 THE KITCHEN PLANS ARE NOT CLEAR.
  
 3) NOTE: PLEASE SEE GUEST BATH. THIS ROOM SHOWS THE
 CIRCUIT TO GFI AS 5B. THIS IS SHOWN AS A BEDROOM
 CIRCUIT ON PANEL SCHEDULE WITH #14AWG AND 15AMP
 BREAKER. THIS IS NOT PERMITTED. PLEASE SEE 210.11C3 AS
 BATH GFI CIRCUITS/RECEPTACLES ARE ONLY PERMITTED TO BE
 CIRCUITED ONE OF TWO WAYS. IN EITHER CASE THEY ARE ALSO
 REQUIRED TO BE 20AMP AND #12.
  
 4) NOTE: PLEASE SEE 210.52 AS SOME RECEPTACLES ARE
 MISSING FOR WALL SPACES. SEE ONE SET OF PLANS WHICH ARE
 REDLINED.
 WALL IN MASTER BEDROOM, WALL IN OTHER GUEST ROOM.
  
 5) NOTE: PLEASE SEE S1 AND S2 NOTES ON PLANS. THE
 SYMBOL LEGEND STATES S 1 AND S2 ARE SMOKE ALARMS, YET
 THE NOTES STATE S2 IS A SMOKE DETECTOR WHICH IS NOT THE
 SAME. S2 NOTE ALSO STATES ONLY TO BE INTERCONNECTED
 WHEN WITHIN 20FT OF COOKING APPLIANCES.
  
 A) ALL SMOKE DETECTION DEVICES WHETHER OR NOT SMOKE
 ALARMS OR DETECTORS ARE REQUIRED TO BE INTERCONNECTED
 IN THIS R OCCUPANCY.
 B) ALL SHALL BE CIRCUITED SINGLE STATION INTERCONNECTED
 AND ON ONE OF THE ARC FAULT PROTECTED CIRCUITS PER
 210.12. SINCE S2 OUTSIDE SLEEPING ROOM IS REQUIRED TO
 BE INTERCONNECTED WITH THE S1 UNITS, THIS MUST ALSO BE
 ON THE SAME AFCI CIRCUIT.
  
 NFPA-72 11.8.3,11.5.1, NEC 210.12.
  
  
  
 ** ONLY NOTED FOR INFORMATION. LOW VOLTAGE SHOWN ON
 PLANS WILL BE REQUIRED TO BE UNDER SEPARATE PERMIT. MAY
 USE THESE PLANS AS A REFERENCE FOR TURN AROUND PERMIT.
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  