Plan Review Notes
Plan Review Notes For Permit 09060005
Permit Number 09060005
Review Stop M
Sequence Number 1
Notes
Date Text
2009-06-19 15:25:44REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PLEASE SHOW CFM QUANTITIES FOR EACH SUPPLY REGISTER
 ON PLANS IN ACCORDANCE WITH FBC-M 603.1
  
 2. NO BATHROOM EXHAUST IS SHOWN ON PLANS. EXHAUST IS
 REQUIRED IN THE BATHROOM PER FBC-EB 709.1 AND FBC-M
 402.3.1.
  
 3. NOTE #4 ON PAGE 6 CALLS FOR WASHER AND DRYER BUT NO
 SUCH APPLIANCES COULD BE FOUND ON PLANS. PLEASE CLARIFY
 IN ACCORDANCE WITH FBC-B 106.1.1.
  
 4. SOME DUCT SIZES PROPOSED ON PAGE 6 WILL NOT FIT
 BASED ON THE SIZES OF SOFFITS SHOWN ON PAGE 3. PLEASE
 COORDINATE FLOOR PLANS TO ASSURE THE REQUIRED VOLUMES
 OF AIR CAN BE DELIVERED TO EACH SPACE IN ACCORDANCE
 WITH FBC-M 603.1.
  
 5. PLEASE ENSURE PLANS ARE PROPERLY SIGNED, SEALED AND
 DATED IN ACCORDANCE WITH FS 481.
  