Plan Review Notes For Permit 09060005 |
Permit Number |
09060005 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-06-19 15:25:44 | REVIEW #: 1ST | | ACTION: DENIED | | | | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | 1. PLEASE SHOW CFM QUANTITIES FOR EACH SUPPLY REGISTER | | ON PLANS IN ACCORDANCE WITH FBC-M 603.1 | | | | 2. NO BATHROOM EXHAUST IS SHOWN ON PLANS. EXHAUST IS | | REQUIRED IN THE BATHROOM PER FBC-EB 709.1 AND FBC-M | | 402.3.1. | | | | 3. NOTE #4 ON PAGE 6 CALLS FOR WASHER AND DRYER BUT NO | | SUCH APPLIANCES COULD BE FOUND ON PLANS. PLEASE CLARIFY | | IN ACCORDANCE WITH FBC-B 106.1.1. | | | | 4. SOME DUCT SIZES PROPOSED ON PAGE 6 WILL NOT FIT | | BASED ON THE SIZES OF SOFFITS SHOWN ON PAGE 3. PLEASE | | COORDINATE FLOOR PLANS TO ASSURE THE REQUIRED VOLUMES | | OF AIR CAN BE DELIVERED TO EACH SPACE IN ACCORDANCE | | WITH FBC-M 603.1. | | | | 5. PLEASE ENSURE PLANS ARE PROPERLY SIGNED, SEALED AND | | DATED IN ACCORDANCE WITH FS 481. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|