Plan Review Notes For Permit 09060005 |
Permit Number |
09060005 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-06-18 13:52:56 | *****DENIED***** | | | | | | 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004 | | EDITION. ADD COMMENT TO SHEET 2 (OF SEVEN). | | | | 2. EFFECTIVE 12/31/2008, THE 2006 EDITION OF NFPA 101 | | SHALL BE REFERENCED. AMEND ELECTRICAL NOTE #1 AND FIRE | | PROTECTION NOTE #1 ON SHEET 7 (OF SEVEN). | | | | 3. THE SMOKE DETECTOR / SMOKE ALARM DEVICES AREN'T | | READILY VISIBLE DUE TO CLARITY OF PLANS AS SHOWN ON | | SHEET 6 (OF SEVEN). | | | | 4. INDICATE THE TYPE OF DEVICE THAT IS/ARE BEING AND OR | | WILL BE USED IN THE LIVING UNIT. BE ADVISED THAT SMOKE | | DETECTORS (SD) ARE TIED INTO THE BUILDING'S FIRE ALARM | | SYSTEM, WHEREAS SMOKE ALARMS (SA) SHALL SOUND ONLY | | WITHIN THE DWELLING UNIT AND SHALL NOT ACTUATE THE | | BUILDING FIRE ALARM SYSTEM, UNLESS OTHERWISE PERMITTED | | BY THE AUTHORITHY HAVING JURISDICTION (AHJ). | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|