2009-06-17 15:16:45 | |
| |
| |
| |
| ** DENIED PLANS * |
| |
| 1) NOTE: THE ELECTRICAL PLANS NEED TO STATE THE |
| FOLLOWING MINIMUM CODES. |
| PLEASE BE SURE THE FOLLOWING ARE STATED ON ELECTRICAL |
| PLANS. |
| 2007 FBC W/ 2009 AMENDMENTS. |
| 2006 NFPA-101 ( PLANS STATE 2003 FOR THIS CODE) |
| 2002 NFPA-72 |
| 2006 NFPA-1 |
| 2005 NFPA-70 ( PLANS DO NOT GIVE YEAR) |
| |
| PER: FBC CHAPTER 35, FS 553.73, FAC 69A-60.004, .003 |
| |
| 2) NOTE: PLEASE SUBMIT ELECTRICAL PLANS WITHOUT THE |
| MECHANICAL SHADED OVER THE ELECTRICAL DETAILS. SOME |
| ITEMS ARE NOT CLEAR TO BE REVIEWED FOR CODE COMPLIANCE. |
| THE KITCHEN PLANS FOR EXAMPLE ARE VERY CONGESTED AND |
| NOT EASILY READ FOR CODE COMPLIANCE VERIFICATION OF |
| 210.52C1-5 FOR EXAMPLE. |
| FBC 106.1.1 FOR CLARITY AND QUALITY OF SUBMITTED PLANS. |
| NEC, 300,210,ETC |
| |
| 3) NOTE: PLEASE SEE NFPA-72 FOR DEFINITIONS OF SMOKE |
| DETECTION DEVICES. PER THE SYMBOL LEGEND THE PLANS |
| STATE THERE IS GOING TO BE SMOKE DETECTORS. SMOKE |
| DETECTORS ARE DEVICE WHICH DETECT HOWEVER DO NOT SOUND |
| AN ALARM. IF THESE ARE INDEED SMOKE DETECTORS, PLEASE |
| SUBMIT MORE DETAILS ON THE COMPLETE SYSTEM SHOWING THE |
| HORNS, STROBES PANEL OR SOUNDING DEVICES TO ALERT THE |
| OCCUPANT. |
| PLEASE SEE NFPA-72 11.5.1.1, 11.8.3 |
| ** PLEASE SEE NFPA-72 DEFINITIONS OF SMOKE ALARMS. IF |
| THESE ARE SMOKE ALARMS WHICH DETECT AND SOUND AN ALARM |
| PLEASE ADJUST PLANS ACCORDINGLY. |
| |
| 4) NOTE: PLEASE BE SURE TO SEE 210.4B FOR ANY DEVICES |
| OR SINGLE YOKE BEING FED FROM MORE THAN ONE CIRCUIT. |
| THIS MAY BE THE DISHWASHER/DISPOSAL WHICH WOULD REQUIRE |
| A TWO POLE BREAKER. IT IS NOT CLEAR AT THIS TIME IF |
| THIS IS THE SAME YOKE OR NOT. |
| |
| 5) NOTE: PLEASE SEE 422.13 AS WATER HEATER LOAD UNDER |
| THE 2005 NEC IS NOW CONSIDERED A CONTINUOUS LOAD WHICH |
| REQUIRES 125% TO BE FIGURED INTO THE CALCULATIONS. |
| |
| 6) NOTE: PLEASE SEE THE CODE SECTIONS REFLECTED ON THE |
| LOAD CALCULATIONS ARE NOT FROM THE CURRENT EDITION OR |
| EVEN PREVIOUS EDITION OF THE NEC. IN FACT PLANS STATE |
| 202.32, 202.30. THERE IS NO SECTION 202 LOCATED IN |
| NFPA70. EVEN IF THESE WERE MISPRINTS TO BE |
| 220.30,220.32, THE CURRENT EDITION OF THE NEC WHICH IS |
| THE ADOPTED 2005 DOES NOT CONTAIN THESE SECTIONS. |
| PLEASE SEE NEW CODE WHICH WENT INTO AFFECT DECEMBER 8TH |
| 2006. |
| |
| 7) NOTE: PLEASE SEE 210.52B1, 210.11C1, 220.53 AS EACH |
| OF THE ONE OR MORE SMALL APPLIANCE CIRCUITS SHALL BE |
| FIGURED AT 1500VA FOR EACH. NO LOAD IS SHOWN IN THE |
| LOAD CALCULATIONS FOR THE DINING ROOM RECEPTACLE |
| CIRCUIT. |
| |
| |
| |
| ** IMPORTANT ** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| |