Plan Review Notes
Plan Review Notes For Permit 09060005
Permit Number 09060005
Review Stop E
Sequence Number 1
Notes
Date Text
2009-06-17 15:16:45 
  
  
  
 ** DENIED PLANS *
  
 1) NOTE: THE ELECTRICAL PLANS NEED TO STATE THE
 FOLLOWING MINIMUM CODES.
 PLEASE BE SURE THE FOLLOWING ARE STATED ON ELECTRICAL
 PLANS.
 2007 FBC W/ 2009 AMENDMENTS.
 2006 NFPA-101 ( PLANS STATE 2003 FOR THIS CODE)
 2002 NFPA-72
 2006 NFPA-1
 2005 NFPA-70 ( PLANS DO NOT GIVE YEAR)
  
 PER: FBC CHAPTER 35, FS 553.73, FAC 69A-60.004, .003
  
 2) NOTE: PLEASE SUBMIT ELECTRICAL PLANS WITHOUT THE
 MECHANICAL SHADED OVER THE ELECTRICAL DETAILS. SOME
 ITEMS ARE NOT CLEAR TO BE REVIEWED FOR CODE COMPLIANCE.
 THE KITCHEN PLANS FOR EXAMPLE ARE VERY CONGESTED AND
 NOT EASILY READ FOR CODE COMPLIANCE VERIFICATION OF
 210.52C1-5 FOR EXAMPLE.
 FBC 106.1.1 FOR CLARITY AND QUALITY OF SUBMITTED PLANS.
 NEC, 300,210,ETC
  
 3) NOTE: PLEASE SEE NFPA-72 FOR DEFINITIONS OF SMOKE
 DETECTION DEVICES. PER THE SYMBOL LEGEND THE PLANS
 STATE THERE IS GOING TO BE SMOKE DETECTORS. SMOKE
 DETECTORS ARE DEVICE WHICH DETECT HOWEVER DO NOT SOUND
 AN ALARM. IF THESE ARE INDEED SMOKE DETECTORS, PLEASE
 SUBMIT MORE DETAILS ON THE COMPLETE SYSTEM SHOWING THE
 HORNS, STROBES PANEL OR SOUNDING DEVICES TO ALERT THE
 OCCUPANT.
 PLEASE SEE NFPA-72 11.5.1.1, 11.8.3
 ** PLEASE SEE NFPA-72 DEFINITIONS OF SMOKE ALARMS. IF
 THESE ARE SMOKE ALARMS WHICH DETECT AND SOUND AN ALARM
 PLEASE ADJUST PLANS ACCORDINGLY.
  
 4) NOTE: PLEASE BE SURE TO SEE 210.4B FOR ANY DEVICES
 OR SINGLE YOKE BEING FED FROM MORE THAN ONE CIRCUIT.
 THIS MAY BE THE DISHWASHER/DISPOSAL WHICH WOULD REQUIRE
 A TWO POLE BREAKER. IT IS NOT CLEAR AT THIS TIME IF
 THIS IS THE SAME YOKE OR NOT.
  
 5) NOTE: PLEASE SEE 422.13 AS WATER HEATER LOAD UNDER
 THE 2005 NEC IS NOW CONSIDERED A CONTINUOUS LOAD WHICH
 REQUIRES 125% TO BE FIGURED INTO THE CALCULATIONS.
  
 6) NOTE: PLEASE SEE THE CODE SECTIONS REFLECTED ON THE
 LOAD CALCULATIONS ARE NOT FROM THE CURRENT EDITION OR
 EVEN PREVIOUS EDITION OF THE NEC. IN FACT PLANS STATE
 202.32, 202.30. THERE IS NO SECTION 202 LOCATED IN
 NFPA70. EVEN IF THESE WERE MISPRINTS TO BE
 220.30,220.32, THE CURRENT EDITION OF THE NEC WHICH IS
 THE ADOPTED 2005 DOES NOT CONTAIN THESE SECTIONS.
 PLEASE SEE NEW CODE WHICH WENT INTO AFFECT DECEMBER 8TH
 2006.
  
 7) NOTE: PLEASE SEE 210.52B1, 210.11C1, 220.53 AS EACH
 OF THE ONE OR MORE SMALL APPLIANCE CIRCUITS SHALL BE
 FIGURED AT 1500VA FOR EACH. NO LOAD IS SHOWN IN THE
 LOAD CALCULATIONS FOR THE DINING ROOM RECEPTACLE
 CIRCUIT.
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  