Plan Review Notes For Permit 09050539 |
Permit Number |
09050539 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-06-01 09:36:00 | 2007 FBC /ASCE 7-05 | | INSTALL (4) ACCORDION SHUTTERS | | | | DENIED BY BUILDING | | | | 1) THE WALL PRESSURES THAT ARE SPECIFIED FOR THE | | OPENINGS ARE INCORRECT. THEY WILL BE HIGHER THAN | | INDICATED FOR 140 MPH, EXPOSURE C AND MEAN ROOF HEIGHT | | OF 20 FEET. SEE 2007 FBC R TABLES R301.2(2) AND | | R301.2(3). PLEASE CORRECT INSTALLATION SCHEDULE. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|