2009-05-29 08:21:35 | DENIED |
| REFERENCE: |
| FBC-2007 RESIDENTIAL |
| FBC-2007 CHAPTER 1 (ADMIN) |
| |
| A. THE FOLLOWING INFORMATION IS REQUIRED FOR GAS |
| PERMIT: |
| |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. -- SHOW THE METER AND THE PIPING OUT OF |
| THE METER TO INDICATE WHERE THE TEE TO THE COOKTOP |
| CONNECTS TO THE GAS PIPING. SHOW PIPE SIZE OUT OF THE |
| METER TO THE TEE ADDED TO THE SYSTEM. INDICATE BTU LOAD |
| ON EACH SIDE OF THE TEE. |
| |
| 2. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| THRU 402.6.1 AND TABLES 402.4(1) THRU |
| 402.4(33). -- INDICATE TOTAL BTU LOAD FOR THE SYSTEM. |
| |
| 3. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). -- ONLY DISTANCE SHOWN IS |
| FOR THE COOKTOP. |
| |
| 4. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| |
| 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2. |
| |
| B. THE VALUATION OF THE WORK APPEARS TO BE LOW. THE |
| PRICE OF THE COOKTOP SHALL BE INCLUDED IN THE COST OF |
| THE PERMIT. |
| 104.6.5 BUILDING PERMIT VALUATION. IF |
| IN THE OPINION OF THE BUILDING OFFICIAL |
| THE CLAIMED VALUATION OF BUILDING, AL- |
| TERATION, STRUCTURE, ELECTRICAL, GAS, |
| MECHANICAL OR PLUMBING SYSTEMS APPEARS |
| TO BE UNDERESTIMATED ON THE APPLICATION, |
| THE PERMIT SHALL BE DENIED, UNLESS THE |
| APPLICANT CAN SHOW DETAILED ESTIMATES |
| AND/OR BONA FIDED SIGNED CONTRACTS (EX- |
| CLUDING LAND VALUE) TO MEET THE APPROVAL |
| OF THE BUILDING OFFICIAL. FOR PERMITTING |
| PURPOSES, VALUATION FOR BUILDINGS AND |
| SYSTEMS SHALL BE FOUND IN MARSHALL AND |
| SWIFT OR THE SOUTHERN BUILDING CODE |
| CONGRESS INTERNATIONAL VALUATION TABLES, |
| LATEST EDITION, AND SHALL BE BASED ON |
| TOTAL REPLACEMENT VALUE TO INCLUDE |
| STRUCTURAL, ELECTRIC, PLUMBING, MECHAN- |
| ICAL, INTERIOR FINISH, NORMAL SITE WORK |
| (EXCAVATION AND BACKFILL FOR BUILDINGS), |
| ARCHITECTURAL AND DESIGN FEES, OVERHEAD |
| AND PROFIT, EXCLUDING ONLY LAND VALUE. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |
| |