Plan Review Notes For Permit 09050449 |
Permit Number |
09050449 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-06-09 10:30:49 | SIGN BUILDING REVIEW CHECKLIST. | | REVIEW UNDER 2007 FBC WITH 2009 REVISIONS. | | | | 1- ENGINEER DRAWINGS NEED TO INDICATE CURRENT BUILDING | | CODE 2007 FBC WITH 2009 REVISIONS. AND ASCE TO BE | | REFERENCED IS ASCE 7-05 NOT ASCE 7-02. PLANS SUBMITTED | | ARE REFERENCING THE FBC 2004 AND 2006 REVISIONS. REVISE | | AS REQUIRED. | | | | 2- SPECIFY HOW LONG ARE THE (4) LAG SCREWS. SEC. | | 106.1.2 CITY AMENDMENTS TO FBC. | | | | 3- ENGINEER DRAWINGS DON'T PROVIDE SPECIFICATIONS FOR | | VERTICAL ALUMINUM MEMBERS HOLDING THE SIGN. ALSO, | | SPECIFICATIONS SHOWN FOR ALUMINUM HORIZONTAL BAR DON'T | | MATCH SIZE SHOWN ON ELECTRICAL SHEET. REVISE AS | | REQUIRED TO MATCH. | | | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|