2009-05-21 12:04:54RESIDENTIAL (R3) RE-ROOFING, BUILDING REVIEW CHECKLIST.
 REVIEW UNDER 2007 FLORIDA RESIDENTIAL CODE WITH 2009
 REVISIONS.
  
 1- SELECTED ASSEMBLY ON PAGE 32 OF NOA 08-0227.09
 SUBMITTED IS LIMITED BY GENERAL LIMITATION #9. THIS
 LIMITATION DOESN'T ALLOW FOR NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS. THE MAXIMUM DESIGN PRESSURE
 ON SELECTED ASSEMBLY IS -45PSF AND IT CAN'T BE
 INCREASED. DESIGN PRESSUES FOR THIS BUILDING IN THIS
 AREA ARE HIGHER THAN 45PSF. SEE GENERAL LIMITATION #9
 ON SHEET 39. NEED TO SELECT ASSEMBLY THAT IS LIMITED BY
 GENERAL LIMITATION #7 THAT DOES ALLOW FOR NAIL
 ENHANCING BY RUNNING RAS 117 CALCULATIONS. SEE GENERAL
 LIMITATION #7.
  
 2- ACCORDING TO NOA SUBMITTED GENERAL LIMITATION #7
 REQUIRES SIGNED AND SEALED RAS 117 CALCULATIONS.
 PROVIDE SIGNED AND SEALED CALCULATIONS.
 ***NOTE: DESIGN PROFESSIONAL WHEN RUNNING THE
 CALCULATIONS NEEDS TO TAKE INTO CONSIDERATION THAT
 ACCORDING TO THE 2009 REVISIONS TO THE 2007 FLORIDA
 RESIDENTIAL CODE THIS BUILDING IS LOCATED ON EXPOSURE
 C. SEE 2009 REVISIONS SEC. R301.
  