Plan Review Notes
Plan Review Notes For Permit 09050409
Permit Number 09050409
Review Stop E
Sequence Number 1
Notes
Date Text
2009-05-27 12:08:29BUILDING PLAN REVIEW
 PERMIT: 09050409
 ADD: 6901 WASHINGTON RD
 CONT: ATLAS POOLS
 TEL: (561)386-4385
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 ELECTRICAL:
  
 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009 SUPPLEMENTS, PLEASE UPDATE PLANS TO
 THE CURRENT CODE.
  
 2) THE PERMIT APPLICATION & PLANS INDICATE NEW 360 SQ
 FT POOL, 650 SQ FT PAVER DECK & 100,000 BTU ELECTRIC
 HEAT PUMP. THE VALUE OF THE PERMIT APPLICATION
 INDICATES
 $18,800. THE CALCULATED VALUE IS $27,459.00. POOL
 $18,584, 650 SQ FT PAVER DECK $4875.00 & ELECTRIC HEAT
 PUMP $4,000.00.
 W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT FEES.
 ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL,
 AND PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT,
 A FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN
 ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE
 APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 3) THE EQUIPOTENTIAL BONDING SHEET IS A SHEET SIGNED BY
 A LICENSED ENGINEER REQUIRING ORIGINAL SIGNATURE WITH
 RAISED SEAL. PLEASE SUBMIT ORIGINALS.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
  
 4) PLEASE PROVIDE A COMPLETE LOAD CALCULATION FOR
 EXISTING LOADS AND THE NEW POOL PUMP AND ELECTRIC HEAT
 PUMP. NEC 2005 ARTICLE 220.87.
  
 5) 13-612.1.ABC.2.3.2 COVERS REQUIRED. SPAS AND HEATED
 SWIMMING POOLS SHALL BE EQUIPPED WITH A COVER DESIGNED
 TO
 MINIMIZE HEAT LOSS.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.