Plan Review Notes For Permit 09050396 |
Permit Number |
09050396 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-05-22 09:15:06 | RESIDENTIAL (R3) SHUTTERS, BUILDING REVIEW CHECKLIST. | | REVIEW UNDER 2007 FLORIDA RESIDENTIAL CODE. | | | | 1- REVISE INSTALLATION SCHEDULE ANCHOR SPACING FOR | | OPENINGS 1, 3, 4, 5, 6, 7 AND 9 TO MATCH THE CALCULATED | | DESIGN PRESSURES. CALCULATED DESIGN PRESSURES ARE | | -57.2. THEREFORE ANCHOR SPACING FOR -57 CAN'T BE USED. | | NEED TO USE HIGHER DESIGN PRESSURES ANCHOR SPACING. | | | | 2- CLARIFY IF SUBSTRATE TO RECEIVE SHUTTERS IS POURED | | CONCRETE ON TOP AND BOTTOM. TYPICALLY THERE IS A | | PRECAST CONCRETE LINTEL OR POURED CONCRETE BEAM ON TOP, | | BUT WINDOW SILL MAY NOT BE POURED CONCRETE. PROVIDE | | PROOF THAT WINDOW SILL HAS MIN. 3,320 PSI CONCRETE | | STRENGTH AS REQUIRED BY THE PRODUCT APPROVAL OR USE THE | | CONCRETE BLOCK ANCHOR SPACING TO VERIFY COMPLIANCE WITH | | THE PRODUCT APPROVAL AND CALCULATED DESIGN PRESSURES | | REQUIRED BY SEC. R301 OF 2007 FLORIDA RESIDENTIAL CODE. | | REVISE ANCHOR SPACING AS REQUIRED. | | | | 3- REVISE LENGTH OF TAPCON. 1-3/4" TAPCON DOESN'T | | PROVIDE THE MIN. REQUIRED EMBEDMENT OF 1-3/4" ON | | CONCRETE INSTALLATIONS. | | NOTE: MINIMUM EMBEDMENT EXCLUDES STUCCO OR ANY OTHER | | FINISH. ALSO, MINIMUM EMBEDEMNT REQUIRED FOR CONCRETE | | BLOCK INSTALLATION IS 1-1/4" EXCLUDING STUCCO ALSO. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|