Plan Review Notes For Permit 09050385 |
Permit Number |
09050385 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-05-27 16:29:47 | 2007 FBC | | LEVEL 2 ALTERATION | | | | DENIED BY MECHANICAL | | | | 1) TWO SETS OF PLANS ARE REQUIRED TO BE SUBMITTED FOR | | PERMIT. FBC 106.1* CITY AMENDMENTS. | | | | 2) UPDATE PLANS TO 2007 FBC, WHICH WENT INTO EFFECT ON | | MARCH 1, 2009. | | | | 3) SUBMIT MANUFACTURER'S SPECIFICATIONS, LISTING AND | | DUCTING REQUIREMENTS FOR THE UNDER FLOOR VENTED | | COOKTOP. FBC R M1503.3 | | | | 4) CLEARLY INDICATE THE SCOPE OF MECHANICAL WORK ON THE | | PLANS. | | | | 5) PROVIDE PLANS SHOWING THE LOCATION OF EXISTING | | EQUIPMENT AND DUCTS AND SPECIFY THE NEW LOCATIONS OF | | THE EQUIPMENT AND DUCT WORK. | | | | 6) IF INSTALLING NEW SYSTEM SHOW COMPLIANCE WITH 2007 | | FBC R MECHANICAL. SUBMIT 2 COPIES OF MECHANICAL PLANS, | | MANUAL J CALCULATIONS, ETC. | | | | 7) INDICATE THE CFM CAPACITY OF THE NEW BATHROOM VENT. | | FBC M1507.3 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|