Plan Review Notes
Plan Review Notes For Permit 09050385
Permit Number 09050385
Review Stop M
Sequence Number 1
Notes
Date Text
2009-05-27 16:29:472007 FBC
 LEVEL 2 ALTERATION
  
 DENIED BY MECHANICAL
  
 1) TWO SETS OF PLANS ARE REQUIRED TO BE SUBMITTED FOR
 PERMIT. FBC 106.1* CITY AMENDMENTS.
  
 2) UPDATE PLANS TO 2007 FBC, WHICH WENT INTO EFFECT ON
 MARCH 1, 2009.
  
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS, LISTING AND
 DUCTING REQUIREMENTS FOR THE UNDER FLOOR VENTED
 COOKTOP. FBC R M1503.3
  
 4) CLEARLY INDICATE THE SCOPE OF MECHANICAL WORK ON THE
 PLANS.
  
 5) PROVIDE PLANS SHOWING THE LOCATION OF EXISTING
 EQUIPMENT AND DUCTS AND SPECIFY THE NEW LOCATIONS OF
 THE EQUIPMENT AND DUCT WORK.
  
 6) IF INSTALLING NEW SYSTEM SHOW COMPLIANCE WITH 2007
 FBC R MECHANICAL. SUBMIT 2 COPIES OF MECHANICAL PLANS,
 MANUAL J CALCULATIONS, ETC.
  
 7) INDICATE THE CFM CAPACITY OF THE NEW BATHROOM VENT.
 FBC M1507.3
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]