| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| |
| THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009 |
| REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND |
| FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| |
| 1} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH |
| 210.52(A), 210.52(C), AND 210.8(A)(6) GFI. |
| |
| 2} 210.52(C)(1) WALL COUNTER SPACES A RECEPTACLE OUTLET |
| SHALL BE INSTALLED AT EACH WALL COUNTER SPACE THAT IS |
| 300 MM (12 IN.) OR WIDER. RECEPTACLE OUTLETS SHALL BE |
| INSTALLED SO THAT NO POINT ALONG THE WALL LINE IS MORE |
| THAN 600 MM (24 IN.) MEASURED HORIZONTALLY FROM A |
| RECEPTACLE OUTLET IN THAT SPACE. |
| |
| 3} 210.52(C) (2) ISLAND COUNTER SPACES AT LEAST ONE |
| RECEPTACLE SHALL BE INSTALLED AT EACH ISLAND COUNTER |
| SPACE WITH A LONG DIMENSION OF 600 MM (24 IN.) OR |
| GREATER AND A SHORT DIMENSION OF 300 MM (12 IN.) OR |
| GREATER. WHERE A RANGETOP OR SINK IS INSTALLED IN AN |
| ISLAND COUNTER AND THE WIDTH OF THE COUNTER BEHIND THE |
| RANGETOP OR SINK IS LESS THAN 300 MM (12 IN.), THE |
| RANGETOP OR SINK IS CONSIDERED TO DIVIDE THE ISLAND |
| INTO TWO SEPARATE COUNTERTOP SPACES AS DEFINED IN |
| 210.52(C)(4). |
| |
| 4} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE |
| PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI |
| PROTECTED PER 210.8(A) (1). |
| |
| 5} 106.1 SUBMITTAL DOCUMENTS. CONSTRUCTION DOCUMENTS, |
| SPECIAL INSPECTION AND STRUCTURAL OBSERVATION PROGRAMS, |
| AND OTHER DATA SHALL BE SUBMITTED IN TWO OR MORE SETS |
| WITH EACH APPLICATION FOR A PERMIT. ONLY ONE SET WAS |
| SUBMITTED FOR REVIEW. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| 561/805-6718 |
| |