 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH
 210.52(A), 210.52(C), AND 210.8(A)(6) GFI.
  
 2} 210.52(C)(1) WALL COUNTER SPACES A RECEPTACLE OUTLET
 SHALL BE INSTALLED AT EACH WALL COUNTER SPACE THAT IS
 300 MM (12 IN.) OR WIDER. RECEPTACLE OUTLETS SHALL BE
 INSTALLED SO THAT NO POINT ALONG THE WALL LINE IS MORE
 THAN 600 MM (24 IN.) MEASURED HORIZONTALLY FROM A
 RECEPTACLE OUTLET IN THAT SPACE.
  
 3} 210.52(C) (2) ISLAND COUNTER SPACES AT LEAST ONE
 RECEPTACLE SHALL BE INSTALLED AT EACH ISLAND COUNTER
 SPACE WITH A LONG DIMENSION OF 600 MM (24 IN.) OR
 GREATER AND A SHORT DIMENSION OF 300 MM (12 IN.) OR
 GREATER. WHERE A RANGETOP OR SINK IS INSTALLED IN AN
 ISLAND COUNTER AND THE WIDTH OF THE COUNTER BEHIND THE
 RANGETOP OR SINK IS LESS THAN 300 MM (12 IN.), THE
 RANGETOP OR SINK IS CONSIDERED TO DIVIDE THE ISLAND
 INTO TWO SEPARATE COUNTERTOP SPACES AS DEFINED IN
 210.52(C)(4).
  
 4} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI
 PROTECTED PER 210.8(A) (1).
  
 5} 106.1 SUBMITTAL DOCUMENTS. CONSTRUCTION DOCUMENTS,
 SPECIAL INSPECTION AND STRUCTURAL OBSERVATION PROGRAMS,
 AND OTHER DATA SHALL BE SUBMITTED IN TWO OR MORE SETS
 WITH EACH APPLICATION FOR A PERMIT. ONLY ONE SET WAS
 SUBMITTED FOR REVIEW.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  